December 2019
143
Installation, Operation and Maintenance Manual
VCIOM-08500-EN
Appendix
Appendix
To guarantee that weather-proof and explosion-proof characteristics are maintained,
screw the cable gland or the external ATEX-certified apparatus tightly (at least 5 turns of
engagement) and coat them with a thread sealant.
NOTICE
The cables and cable glands MUST be selected considering the maximum temperature of
the cable indicated on the label fixed to the base ICON3000 unit. When selecting cables and
cable glands, the maximum temperature of the cable (indicated on the product label of the
base ICON3000) must be considered.
C.7.5
Installation in Environments with Explosive Dusts
Special attention must be paid to the following points:
•
Before assembly, joint surfaces must be greased with Aeroshell grease.
•
The cable glands must at a minimum possess a protection degree of IP66 or IP68
(15 m depth / 90 hours) according to IEC/EN 60529 standard.
•
Periodically measure the quantity of dust deposited on the surface of the
actuator body. Clean the dust if it accumulates to more than 5mm high (relative
to the actuator body).
C.8
Maintenance
WARNING
Installation, configuration, commissioning, maintenance, and repairs must be performed
by approved and qualified personnel only.
C.8.1
Periodic Inspection
•
Inspect the general condition of the ICON3000 and the possible optional
additional extension at regular intervals. The recommended frequency of
inspection is once every two years but this frequency could change depending
on the installation and working conditions. Any crack on the surface, broken
windows, or loose bolts must be reported for repair.
•
Keep the external surfaces of the unit clean: if the unit is installed in a dusty
environment, the specification stated in IEC/EN 60079-14 is to be followed
(ensuring in particular that the dust layer does not exceed 5 mm).
•
If the actuator is covered by an intumescent coating ("Kmass"), an electrostatic
charge risk is present; only anti-static cloth may be used when cleaning is
required. When performing maintenance, avoid rubbing actions against the
actuator (or any other friction-inducing action) that could electrostatically
charge the unit.
•
Check the condition of cable connections and mounting bolts; any loose
connection must be tightened.