December 2019
158
Installation, Operation and Maintenance Manual
VCIOM-08500-EN
Appendix
Appendix
E.2
Instructions for Proper Installation
WARNING
Before installation, it is mandatory to check if the nameplate associated with the
extension for additional entry specifies the appropriate degree of protection and ambient
temperature limits as requested by the rules applicable to the plant/location where the
ICON3000 is installed.
Installation in environments with the presence of an explosive atmosphere not covered
by the specified grade of protection, or in environments that could reach a temperature
higher than the maximum specified on the label, will invalidate the safety warnings and
the warranty.
NOTICE
Check if the label, as the example here above, is fixed on the unit and completed with all the
appropriate information.
E.2.1
Marking
Figure E-4
Template of the label for ICON3000
IECEx INE YY.NNNNX
= IECEx reference certificate (CoC)
INERIS YY ATEX NNNNX = ATEX reference certificate
0080
= Notified body for ATEX quality assurance (INERIS)
II
= Group II (surface industries)
2
= Category 2 apparatus
G
= Explosive atmospheres caused by gas, mists, or vapors
D
= Explosive atmospheres caused by gas dusts
IP66/68
= Degree of protection