E.6.2
Checks to be performed before installation
Before installing extensions for additional entries or additional electronic cards on a base
ICON3000 unit, the following checks are recommended:
•
Condition of joint surfaces between compartment covers and the main housing.
•
Condition of the threads on the conduit entries.
•
Whether the enclosure covers or the actuator body are cracked or broken.
E.7 Installation
NOTICE
Installation must be carried out in accordance to the applicable standards EN/IEC 60079-14
and EN/IEC 60079-17 regarding the electrical installations in Hazardous Areas (other than
mines) classified as Zones 1, 2 (gas) and Zones 21, 22 (dust) following EN/IEC 60079-10-1
and EN/IEC 60079-10-2 and any other applicable national standards and rules.
E.7.1
Working Condition
WARNING
Verify that the actuator nameplate conforms to the applicable certification, ambient
temperature range, and site safety requirements.
E.7.1.1
Models and Temperature
ICON3000-010, ICON-020, ICON-030, ICON-040, ICON-050 from -25 °C to +60 °C
(from -13 °F to +140 °F)
E.7.2
Identification of Entries
E.7.2.1
Base Actuator
The ICON3000 electric actuator is equipped with 5 entries (3 are standard; the 4th and
5th are supplied upon request).
With reference to Figure E-5, the thread form/size for each entry is as follows:
Table E-4.
Entry
NPT size
Alternative (Metric size ISO 965)
1
1"
M32x1.5
2
1 1/2"
M40x1.5
3
1"
M32x1.5
4 (optional)
3/4"
M25x1.5
5 (optional)
3/4"
M25x1.5