December 2019
85
Installation, Operation and Maintenance Manual
VCIOM-08500-EN
Section 10: View Routines
View Routines
Data logger modes:
•
OFF: the data logger is not active.
•
RECORDER mode: the ICON3000 measures and memorizes the following 3 data:
-
Main voltage supply (V)
-
Motor temperature (°C)
-
Temperature inside the electronics compartment (°C)
•
T-RECORDER mode: the ICON3000 measures and memorizes the following 3 data:
-
Torque in OP/CL
-
Motor temperature (°C)
-
Voltage
In RECORDER and T-RECORDER mode, the SAMPLING TIME fixes the time interval
among two sets of measures. Up to 256 sets of measures (equivalent to 256x4 samples)
can be memorized. The sampling time can be configured from 1 to 3600 seconds.
As the memory becomes full, the recorder stops recording or overwrites the previous
data according to the selected MEMORY MODE (“stop when full” or “continuous”).
If “continuous” was selected, as a new set of measures is achieved the oldest one is
canceled and the new one becomes the latest. Up to 10,000 cycles of full memory
overwriting are performed, and then the recorder stops. In T-RECORDER mode, the
recording operation is also stopped if a torque alarm is raised in opening or in closing.
This additional feature allows the user to maintain memory of the last 256 samples and
see the trend of torque, motor temperature, and main voltage prior to the alarm. A new
start of T-RECORDER clears the data stored in the memory. By using a PDA or PC, the
recorded data can be viewed by a graph where time is on the X axis and the measured
data on the Y axis.
Figure 68 below shows a graph with a sampling time of 2 seconds in RECORDER mode
(electronics temperature and motor temperature).
Figure 68
Recorder Mode