background image

IS200 Electro-Hydraulic Actuator Positioner 

 

 

Orange Instruments Limited. 

Drwg. No.: 1357-007     Issue : K     Date : 07/10/2013          Page : 

9 of 9 

Iss c - Certificate number added.   Iss D - Ta changed to -20 to +60    
Iss E - Details of fail modes, timers and retrans. O/P added.   Retrans. Signal barrier changed to KFD0-CC-Ex1  
Iss F 

– Details of change in Max/min on & off times + addition of 10R in line with pos o/p –ve 

Iss G 

– Stepping times range change to allow finer adjustment 15/11/2007 

Iss H 

– CE Cert. of Conformity details added, Ta to –40degC, 60079:0,26 mods 25/06/2008 

Iss J 

– Harmonised standards in C of C modified to meet current status 04/08/2008 

Iss K -  Markings changed to meet EN 60079-0:2012 02/10/2103 
ATEX Certified Equipment - Change Authority ATEX Manager ONLY 

IS200 Terminal Descriptions 

 

All wiring should be in suitable braided or armoured cable with blue outer casing or sleeving.   Terminate braids 

at one end 

only

 to local metal enclosures. 

 

Terminal 

Description 

 

 

 

 

Voltage 

 

Comment 

 

Increase Sove output 

 

 

<16V 

 

Always at supply potential 

 

 

Increase Solenoid 

–ve output 

 

 

<16V 

 

Set to 0V to energise solenoid 

 

Increase Solenoid ve   

 

<16V 

 

Must be an isolated, IS supply 

 

Increase Solenoid Supply 0V 

 

 

0V 

 

No connection 

 

Decrease Sove output   

 

<16V 

 

Always at supply potential 

 

 

Decrease Solenoid 

–ve output   

 

<16V 

 

Set to 0V to energise solenoid 

 

Decrease Solenoid ve   

 

<16V 

 

Not required if only one solenoid 

 

Decrease Solenoid Supply 0V   

 

0V 

 

is ever energised at one time 

10 

 

No connection 

11

 

 

Instrument ve    

 

 

<16V 

 

Must be an isolated, IS supply 

12

 

 

Instrument Supply 0V 

  

 

 

0V 

 

 

13 

 

ESD Solenoid/Fault -ve output   

 

<16V 

 

Set to 0V to energise solenoid   

14 

 

Increase Sove output 

 

 

<16V 

 

Always at supply potential 

15 

 

Increase Solenoid Supply 0V 

 

 

 

 

 

16 

 

Increase Solenoid ve 

 

 

<16V 

 

Must be an isolated, IS supply 

17

 

 

No connection 

18 

 

Actual position ve 

 

 

<5V 

 

Scaled to actuator movement 

19 

 

Actual position signal -ve 

 

 

<5V 

 

Fit 10R resistor in loop 

20 

 

Command ve 

(4-20mA) 

 

<5V  

 

240R shunt 

21 

 

Command signal -ve 

(4-20mA) 

 

<5V  

 

 

22 

 

Feedback potentiometer maximum 

 

5V 

 

Potentiometer >1000R 

23 

 

F/B potentiometer wiper / 4-20mA +ve  <5V 

 

Current signal optional - IS source 

24 

 

F/B potentiometer minimum / 4-20mA -ve 

<5V 

 

 

Summary of Contents for IS200

Page 1: ...IS200 Intrinsically Safe Actuator Positioner Operation Installation and Maintenance Manual Operation Installation and Maintenance Manual ORM0006 IS200 O M Rev 0...

Page 2: ...co uk Northampton NN3 6XF United Kingdom The IS200 has the following specific approvals Name and Type ACTUATOR POSITIONER TYPE IS200 Certificate Number Baseefa 03ATEX0686X Specific Marking of Explosi...

Page 3: ...t panel of the enclosure Wiring To comply with the IS Certification the IS200 must be wired as shown in the circuit on Page 7 Wiring should be completed by suitably trained personnel taking into accou...

Page 4: ...s required the ON and OFF timers for the open and close solenoids have to be set This operation is best performed when the actuator hydraulics are isolated but the settings can be trimmed during norma...

Page 5: ...sh twice briefly every second 6 Use the INCREASE and DECREASE buttons to set the actuator to the required position for the maximum 20mA command signal As before this can be any position within the mec...

Page 6: ...standards in C of C modified to meet current status 04 08 2008 Iss K Markings changed to meet EN 60079 0 2012 02 10 2103 ATEX Certified Equipment Change Authority ATEX Manager ONLY IS200 dimensions a...

Page 7: ...y Safe barriers before connection to the IS200 See circuits on Page 7 COMMAND SIGNAL INPUT 4 20mA nominal 240R input impedance ANALOGUE POSITION OUTPUT SIGNAL 0 4 9V can be calibrated anywhere in this...

Page 8: ...2 24V dc 7 8 16 15 16V 1 2 24V dc 7 8 3 4 16V 1 2 24V dc 7 8 8 9 4 20mA 1 5 6 4 20mA Command MK35 Li Ex0 2 24V dc 7 8 20 21 0 4 9V 1 9 8 KFD0 CC Ex1 2 18 19 6 7 2 1 13 14 or Fault O P ESD Soln Instume...

Page 9: ...16V Always at supply potential 2 Increase Solenoid ve output 16V Set to 0V to energise solenoid 3 Increase Solenoid Supply ve 16V Must be an isolated IS supply 4 Increase Solenoid Supply 0V 0V 5 No c...

Reviews: