Modulating Controller Application Manual 

Page 10 

 

Cmd Fault Stay 

 Faulting last due to a command signal 

fault, but the standard fault position is either open or 
closed. 

Main Fault Open

 - Faulting open due to a common 

fault 

Main Fault Close

 - Faulting close due to a common 

fault 

Main Fault Stop

 - Faulting last due to a common fault 

Pump Fault Open

 - Faulting open due to a pump fault 

Pump Fault Close

 - Faulting close due to a pump fault 

Pump Fault Stop

 - Faulting last due to a pump fault 

Supply Flt Open

 - Faulting open due to a supply 

pressure fault 

Supply Flt Close

 - Faulting close due to a supply 

pressure fault 

Supply Flt Stop

 - Faulting last due to a supply pressure 

fault 

Hard Seat Open

 - Held open at the open limit 

Hard Seat Close

 - Held closed at the close limit 

5.2   Screen 2 

An example of the second display screen is shown below: 

 

ACCUMULATOR STAT 

The accumulator status line is used to show the details of 
the accumulator and any faults that are currently 
present. Below are the statuses that can be displayed: 

Healthy 

- Accumulator is operating within required 

limits 

Pump Output

 - Pump is running 

Acc Press Fault 

- Pressure signal is in fault

 

Pump Fault 

- Pump is in fault

 

Overrun Fault 

- Pump has run continuously beyond its 

maximum allowable time

 

Low Level Fault 

- Pump reservoir level is below level 

switch set point

 

High Temp Fault

 - Pump reservoir temperature is 

above temperature switch set point

 

Low Press Fault  

- Pressure is below minimum allowable 

pressure

 

High Press Fault 

- Pressure is above maximum 

allowable pressure

 

HIGH PRESSURE SP 

Pressure set point indicating the pressure at which a high 
accumulator pressure fault will be raised. 

PUMP STOP SP 

Pressure set point indicating the pressure at which the 
pump is stopped due to the correct pressure being 
present in the accumulator. 

ACCUM PRESSURE 

The current accumulator pressure based on an analogue 
signal. 

PUMP START SP 

Pressure set point indicating the pressure at which the 
pump starts to run in order to build pressure in the 
accumulator. 

LOW PRESSURE SP 

Pressure set point indicating the pressure at which a low 
accumulator pressure fault will be raised. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for Orange EHPC210

Page 1: ...ower Limited The content of this document may not be used for purposes other than that for which it has been supplied and may not be reproduced either wholly or in part nor may it be used by or its co...

Page 2: ...m Values 13 6 4 System Times 14 6 5 HART Variables 14 This manual provides instruction on the setup and analysis of the modulating controller application Section 2 details specific actuator modules in...

Page 3: ...be linked to the input providing the actuator position signal which provides a calibrated 0 100 value In standard operation 4 20mA Cmd Input should be active meaning that the command value is taken f...

Page 4: ...or both limits of the pulse zone these being the set pulse zone Limit and when the command and actual position are equal Blnce A transfer function is then used within the application to set the requir...

Page 5: ...ide When the controller is in automatic mode if the actuator goes into fault the actuator can be forced to drive to a required location If Fault Open and Fault Close are both off or both are set activ...

Page 6: ...n the actuator will position based on the fault override settings High Pressure SP is a high pressure alarm set point which is used to indicate that the pressure has exceeded the maximum allowable acc...

Page 7: ...uator will position based on the fault override settings To reset Overrun Fault Clear Fault must be set active This immediately resets the fault and then Clear Fault is automatically set to off such t...

Page 8: ...settings because it cannot be certain the pressure has not dropped below the minimum allowable supply pressure 4 2 Controller Access Whenever the controller is powered on the Controller On output is s...

Page 9: ...Actuator is fully closed Pump Output Pump is running ACTUATOR POSITION Provides the current actuator position based on the analogue signal If the signal is in fault 0 0 will be shown COMMAND Provides...

Page 10: ...urrently present Below are the statuses that can be displayed Healthy Accumulator is operating within required limits Pump Output Pump is running Acc Press Fault Pressure signal is in fault Pump Fault...

Page 11: ...signal fault Common Fault Set active when there is a signal indicating an external fault Pump On Demand Set active to enable use of pump on demand features Run Pump To Opn Set active to run the pump w...

Page 12: ...mand signal is in fault Common Fault Set active when there is a signal indicating a common fault Pump Output Set active when the pump is required to run Pump Fault Set active when there is a signal in...

Page 13: ...ic DZ Value indicating how much the command signal must be less than the feedback position when the actuator is static before it starts to close Close Moving DZ Value indicating how much the feedback...

Page 14: ...e position when the actuator is opening Close Limit Move Time that the Close Solenoid pulses active when at the pulse zone limit when the actuator is closing Close Blnce Move Time that the Close Solen...

Reviews: