background image

2.   Actuator 

 

ORM0043_2 

Modulating Controller Application Manual 

Page 3 

 

2.1   Solenoid Setup 

To ensure that the solenoids operate correctly based on 
the required actuator type, the digital output contact 
must be set to make the actuator stay put under normal 
conditions. This is achieved by making sure that no media 
can flow through the solenoids. 

A normally closed solenoid means that media doesn’t 

flow when the solenoid is de-energised, therefore the 
digital output contact must be made normally open 
(N/O) so that its default state is to deenergise the 
solenoid. 

A normally open solenoid means that media does flow 
when the solenoid is de-energised and so it must be 
energised to stop flow. Therefore the digital output 
contact must be made normally closed (N/C) so that its 
default state is to energise the solenoid. 

DOUBLE-ACTING ACTUATOR 

A double acting actuator with two normally closed 
solenoids such that on loss of power the actuator fails 
last. 

The contacts for digital outputs linked to 

Open Solenoid

 

and 

Close Solenoid

 

should both be set to normally open 

(N/O). 

SINGLE-ACTING SPRING CLOSE ACTUATOR 

A spring close single acting actuator with a normally 
closed opening solenoid, and normally open closing 
solenoid such that on loss of power the actuator fails 
close. 

The contact for digital output linked to 

Open Solenoid

 

should be normally open (N/O) and the contact for digital 
output linked to 

Close Solenoid

 

should be normally 

closed (N/C). 

SINGLE-ACTING SPRING OPEN ACTUATOR 

A spring open single acting actuator with a normally 
open opening solenoid, and normally closed closing 
solenoid such that on loss of power the actuator fails 
open. 

The contact for digital output linked to 

Open Solenoid

 

should be normally closed (N/C) and the contact for 
digital output linked to 

Close Solenoid

 

should be 

normally open (N/O). 

2.2   Modulating Control 

The primary aim of the modulating controller application 
is to move an actuator such that the actual actuator 
position matches the commanded actuator position.  

The 

Feedback

 

value should be linked to the input 

providing the actuator position signal which provides a 
calibrated 0-100% value. 

In standard operation, 

4-20mA Cmd Input

 

should be 

active meaning that the command value is taken from 

Command Signal

. The 

Command Signal

 should be linked 

to the isolated 4-20mA input signal which provides a 
calibrated 0-100% value. However, the analogue 
command signal can be overridden by setting 

Remote 

Cmd Ctrl

 

active. In this case the command value is taken 

from the 

Remote Command

 

value which enables the set 

point of the actuator to be set to a fixed value which can 
be changed via a communication channel. 

NOTE: If both 

4-20mA Cmd Input

 

and 

Remote Cmd Input

 

are active then 

Remote Cmd Input

 

takes precedence. 

In Automatic mode, when the commanded position is 
greater than 

Feedback

 

position, the 

Open Solenoid

 

and 

Opening

 outputs are set active. When the command 

position is less than 

Feedback

 

position, the 

Close 

Solenoid

 and 

Closing

 outputs are set active. 

NOTE: positioning is dependent on dead zone and pulse 
zone values as described below. 

2.3   Dead Zones 

Dead zones affect positioning accuracy as a response to 
the required command position. In this application there 
are individual dead zones for both opening and closing 
directions, as well as for when the actuator is static and 
when it is moving. 

When the actuator is static, 

Open Static DZ

 

and 

Close 

Static DZ

 

values are used for control. These values 

specify how far the command signal must move away 
from the current actuator position before the actuator 
will move. 

If the actuator is opening, 

Open Moving DZ

 

and 

Close 

Static DZ

 

values are used for control. These values 

specify the position range that, when reached, the 
actuator will stop opening and become static. 

If the actuator is closing, 

Open Static DZ

 

and 

Close 

Moving DZ

 

values are used for control. These values 

specify the position range that, when reached, the 
actuator will stop closing and become static. 

As soon as the actuator becomes static the dead zone 
values will instantly revert to 

Open Static DZ

 

and 

Close 

Static DZ

. This means that moving dead zones must be 

set smaller than static dead zones such that when the 
actuator stops moving it is within the static dead zone 
range and will remain static. 

Summary of Contents for Orange EHPC210

Page 1: ...ower Limited The content of this document may not be used for purposes other than that for which it has been supplied and may not be reproduced either wholly or in part nor may it be used by or its co...

Page 2: ...m Values 13 6 4 System Times 14 6 5 HART Variables 14 This manual provides instruction on the setup and analysis of the modulating controller application Section 2 details specific actuator modules in...

Page 3: ...be linked to the input providing the actuator position signal which provides a calibrated 0 100 value In standard operation 4 20mA Cmd Input should be active meaning that the command value is taken f...

Page 4: ...or both limits of the pulse zone these being the set pulse zone Limit and when the command and actual position are equal Blnce A transfer function is then used within the application to set the requir...

Page 5: ...ide When the controller is in automatic mode if the actuator goes into fault the actuator can be forced to drive to a required location If Fault Open and Fault Close are both off or both are set activ...

Page 6: ...n the actuator will position based on the fault override settings High Pressure SP is a high pressure alarm set point which is used to indicate that the pressure has exceeded the maximum allowable acc...

Page 7: ...uator will position based on the fault override settings To reset Overrun Fault Clear Fault must be set active This immediately resets the fault and then Clear Fault is automatically set to off such t...

Page 8: ...settings because it cannot be certain the pressure has not dropped below the minimum allowable supply pressure 4 2 Controller Access Whenever the controller is powered on the Controller On output is s...

Page 9: ...Actuator is fully closed Pump Output Pump is running ACTUATOR POSITION Provides the current actuator position based on the analogue signal If the signal is in fault 0 0 will be shown COMMAND Provides...

Page 10: ...urrently present Below are the statuses that can be displayed Healthy Accumulator is operating within required limits Pump Output Pump is running Acc Press Fault Pressure signal is in fault Pump Fault...

Page 11: ...signal fault Common Fault Set active when there is a signal indicating an external fault Pump On Demand Set active to enable use of pump on demand features Run Pump To Opn Set active to run the pump w...

Page 12: ...mand signal is in fault Common Fault Set active when there is a signal indicating a common fault Pump Output Set active when the pump is required to run Pump Fault Set active when there is a signal in...

Page 13: ...ic DZ Value indicating how much the command signal must be less than the feedback position when the actuator is static before it starts to close Close Moving DZ Value indicating how much the feedback...

Page 14: ...e position when the actuator is opening Close Limit Move Time that the Close Solenoid pulses active when at the pulse zone limit when the actuator is closing Close Blnce Move Time that the Close Solen...

Reviews: