background image

2.   Actuator 

 

ORM0043_2 

Modulating Controller Application Manual 

Page 5 

 

Close

 

and 

Hard Seat Fast

 

are active then only the 

Command Signal

 

needs to be below the 

Close Limit

 

to 

hold the 

Close Solenoid

 

active. This can be used to 

ignore pulse zones and fully close the actuator quickly if 
the actuator is normally in a stepping mode. 

2.7   Digital Override 

When 

Remote Open

 

is active, the internal command is 

set to 100% and will override the current command 
signal. The controller will then position as if the 
command signal had been set to 100%. 

When 

Remote Close

 

is active, the internal command is 

set to 0% and will override the current command signal. 
The controller will then position as if the command signal 
had been set to 0%. 

If both 

Remote Open

 

and 

Remote Close

 

are active then 

they cancel each other out and the controller continues 
to position based on the command signal. 

Any fault condition overrides a digital override unless 

Remote Override

 

is active. If this is set active then the 

controller will operate based on the digital override 
signals even if a fault has occurred. 

2.8   Manual Override 

When the controller is in manual mode the 

Manual 

Mode

 

output is set active.  

If in manual mode and 

Manual Enable

 

is active then the 

actuator can be positioned using the control switch. 
Turning the switch away sets the internal command to 
100%, and turning the switch towards sets the internal 
command to 0%, and the controller will position the 
actuator based on these values. When the switch is 
returned to the centre the internal command matches 
the 

Feedback

 so the actuator immediately stays put. If 

Manual Enable

 

is turned off then the actuator cannot be 

positioned manually. 

If 

Manual Fast Pos

 

is active then pulse zones are ignored 

and the actuator will open or close without pulsing the 
solenoids. This can be used to move the actuator quickly 
if it is normally in a stepping mode. 

2.9   Fault Override 

When the controller is in automatic mode, if the actuator 
goes into fault the actuator can be forced to drive to a 
required location. If 

Fault Open

 

and 

Fault Close

 

are both 

off, or both are set active the actuator will fail last. If 

Fault Open

 

is active and 

Fault Close

 

is off, on a fault the 

internal command will be set to 100%. If 

Fault Open

 

is off 

and 

Fault Close

 

is active, on a fault the internal command 

will be set to 0%. In both cases the controller will 
position the actuator based on these values. 

If 

Fault Fast Pos

 

is active then pulse zones are ignored 

during a fault and the actuator will open or close without 
pulsing the solenoids. This can be used to move the 
actuator quickly if it is normally in a stepping mode. 

2.10   System Fault 

If any fault is active in the controller then the 

System 

Fault

 

output is set active. 

2.11   Feedback Signal Fault 

If 

Feedback

 signal is in fault for greater than 

Sig Fault 

Delay

 

then 

Feedback Fault

 

output is set active.  

If 

Fail On Fdbk Flt

 

is active then the actuator will position 

based on the fault override settings. If 

Fail On Fdbk Flt

 

is 

off then the actuator will stay last. 

2.12   Command Signal Fault 

If 

Command Signal

 

is in fault for greater than 

Sig Fault 

Delay

 

then 

Command Fault

 

output is set active. 

If 

Fail On Cmd Flt

 

is active then the actuator will position 

based on the fault override settings. 

If 

4-20mA Cmd Ctrl

 

is active and 

Fail On Cmd Flt

 

is off 

then the actuator will stay last. 

If both 

4-20mA Cmd Ctrl

 

and 

Fail On Cmd Flt

 

are off then 

the command fault will have no effect on controller 
operation. 

2.13   Common Fault 

The 

Common Fault

 

input is used to indicate than an 

external fault has occurred and the controller must go 
into fault mode. 

If 

Common Fault

 

is active then the 

Common Fault

 

output 

is set active and the actuator will position based on the 
fault override settings. The 

Aux Solenoid

 

output is also 

set active such that and external fault can be used to 
quickly fault the actuator. 

If 

Cmn Flt Stop Pmp

 

is also active then the 

Pump Output

 

will be set off which prevents the pump from running if a 
common fault is present. 

 

 

Summary of Contents for Orange EHPC210

Page 1: ...ower Limited The content of this document may not be used for purposes other than that for which it has been supplied and may not be reproduced either wholly or in part nor may it be used by or its co...

Page 2: ...m Values 13 6 4 System Times 14 6 5 HART Variables 14 This manual provides instruction on the setup and analysis of the modulating controller application Section 2 details specific actuator modules in...

Page 3: ...be linked to the input providing the actuator position signal which provides a calibrated 0 100 value In standard operation 4 20mA Cmd Input should be active meaning that the command value is taken f...

Page 4: ...or both limits of the pulse zone these being the set pulse zone Limit and when the command and actual position are equal Blnce A transfer function is then used within the application to set the requir...

Page 5: ...ide When the controller is in automatic mode if the actuator goes into fault the actuator can be forced to drive to a required location If Fault Open and Fault Close are both off or both are set activ...

Page 6: ...n the actuator will position based on the fault override settings High Pressure SP is a high pressure alarm set point which is used to indicate that the pressure has exceeded the maximum allowable acc...

Page 7: ...uator will position based on the fault override settings To reset Overrun Fault Clear Fault must be set active This immediately resets the fault and then Clear Fault is automatically set to off such t...

Page 8: ...settings because it cannot be certain the pressure has not dropped below the minimum allowable supply pressure 4 2 Controller Access Whenever the controller is powered on the Controller On output is s...

Page 9: ...Actuator is fully closed Pump Output Pump is running ACTUATOR POSITION Provides the current actuator position based on the analogue signal If the signal is in fault 0 0 will be shown COMMAND Provides...

Page 10: ...urrently present Below are the statuses that can be displayed Healthy Accumulator is operating within required limits Pump Output Pump is running Acc Press Fault Pressure signal is in fault Pump Fault...

Page 11: ...signal fault Common Fault Set active when there is a signal indicating an external fault Pump On Demand Set active to enable use of pump on demand features Run Pump To Opn Set active to run the pump w...

Page 12: ...mand signal is in fault Common Fault Set active when there is a signal indicating a common fault Pump Output Set active when the pump is required to run Pump Fault Set active when there is a signal in...

Page 13: ...ic DZ Value indicating how much the command signal must be less than the feedback position when the actuator is static before it starts to close Close Moving DZ Value indicating how much the feedback...

Page 14: ...e position when the actuator is opening Close Limit Move Time that the Close Solenoid pulses active when at the pulse zone limit when the actuator is closing Close Blnce Move Time that the Close Solen...

Reviews: