background image

3.   Pump Setup 

 

ORM0043_2 

Modulating Controller Application Manual 

Page 6 

 

3.1   Pump On Demand 

Pump on demand can be used on hydraulic positional 
systems and refers to operating a pump to open and/or 
close the actuator. To use pump on demand features, 

Pump On Demand

 

must be turned active. 

If 

Run Pump To Opn

 

is active then when the actuator is 

opening 

Pump Output

 is set active. 

If 

Run Pump To Clse

 

is active then when the actuator is 

closing 

Pump Output

 is set active. 

In certain cases the pump is required to continue running 
for a set time once the actuator has stopped moving, 
either to prevent constant stop/start of the pump, or to 
build pressure at the actuator limits. 

To use this feature 

Pump Run On

 

time should be set to 

the required run on time and once the actuator is stay 
put, the 

Pump Output

 

will be held active for the duration 

of the run on time. If a pump run on is not required then 
the 

Pump Run On

 

time should be set to zero seconds. 

3.2   Pump On Pressure 

Pump on pressure can be used on hydraulic positional 
systems and refers to operating a pump to maintain 
pressure in an accumulator. To use pump on pressure 
features, 

Pump On Pressure

 

must be turned active. 

Two methods of maintaining pressure can be used 

 

using a pressure transmitter or using pressure switches. 

If using a pressure transmitter then 

Press Swtch Ctrl

 

should be turned off and 

Accum Pressure

 

should be 

linked to an analogue input to indicate the accumulator 
pressure. 

Four pressure set points can be set to provide actions 
based on the accumulator pressure. 

Pump Start SP

 

is the minimum desired accumulator 

pressure. 

Pump Stop SP

 

is the maximum desired 

accumulator pressure. When 

Accum Pressure

 

drops 

below the 

Pump Start SP

, the 

Pump Output

 

is latched on 

and will remain on until 

Accum Pressure

 

rises above the 

Pump Stop SP

 

at which point the 

Pump Output

 

will be 

turned off.  

Low Pressure SP

 

is a low pressure alarm set point which 

is used to indicate that the pump is not able to build 
pressure in the accumulator. If the 

Accum Pressure

 

drops below the 

Low Pressure SP

 

for greater 

than 

Px 

Limit Delay

 

then 

Low Press Fault

 

output is set active. If 

Fail On Pump Flt

 

is active then the actuator will position 

based on the fault override settings. 

High Pressure SP

 

is a high pressure alarm set point which 

is used to indicate that the pressure has exceeded the 
maximum allowable accumulator pressure possibly 
caused by the pump continuously running. If the 

Accum 

Pressure

 

rises above the 

High Pressure SP

 

for greater 

than 

Px Limit Delay

 

the 

High Press Fault

 

output is set 

active. 

If using pressure switches to control accumulator 
pressure then 

Press Switch Ctrl

 

should be set to active. 

If using a single pressure switch then 

Single Px Switch

 

should be set active and the pressure switch must be 
linked to 

Pump Start Swtch

. The application 

automatically sets 

Pump Start Swtch

 

and 

Pump Stop 

Swtch

 

active and off based on the single pressure switch 

status. 

If using two pressure switches then 

Single Px Switch

 

should be turned off, the switch indicating low pressure 
should be linked to 

Pump Start Swtch

 

and the switch 

indicating high pressure should be linked to 

Pump Stop 

Swtch

For both cases, if the 

Pump Start Swtch

 

is active for 

greater than 

Px Limit Delay

, the 

Pump Output

 

is latched 

on and will remain on until the 

Pump Stop Swtch

 

is 

active for greater than 

Px Limit Delay

 

at which point the 

Pump Output

 

will be turned off. The 

Px Limit Delay

 

can 

be increased to prevent signal noise causing the pump to 
start and stop frequently, or set to zero to cause the 
operation to be instant. 

For both pressure switch control and pressure 
transmitter control, if 

Manual Stop Pump

 

is active then 

when the controller is in Manual mode and the switch is 
in the centre, 

Pump Output

 

is set off. This is such that if 

there is an issue with the pump, the pump can be 
stopped instantly by going into Manual mode.  

NOTE: If in Manual mode, 

Manual Stop Pump

 

is active 

and the switch is turned either away or towards the 
pump will operate as normal such that pressure can be 
built in the accumulator when trying to position the 
actuator. 

3.3   Accumulator Pressure Signal Fault 

If 

Pump On Pressure

 

is active and 

Press Swtch Ctrl

 

is off 

(i.e. in accumulator pressure transmitter control) and 

Accum Pressure

 

signal is in fault for greater than 

Sig 

Fault Delay

 

then 

Acc Press Fault

 

output is set active. The 

Pump Output

 

is also turned off as the pump cannot be 

run without a valid pressure signal as it cannot be known 
if the maximum pressure limit has been reached. 

Summary of Contents for Orange EHPC210

Page 1: ...ower Limited The content of this document may not be used for purposes other than that for which it has been supplied and may not be reproduced either wholly or in part nor may it be used by or its co...

Page 2: ...m Values 13 6 4 System Times 14 6 5 HART Variables 14 This manual provides instruction on the setup and analysis of the modulating controller application Section 2 details specific actuator modules in...

Page 3: ...be linked to the input providing the actuator position signal which provides a calibrated 0 100 value In standard operation 4 20mA Cmd Input should be active meaning that the command value is taken f...

Page 4: ...or both limits of the pulse zone these being the set pulse zone Limit and when the command and actual position are equal Blnce A transfer function is then used within the application to set the requir...

Page 5: ...ide When the controller is in automatic mode if the actuator goes into fault the actuator can be forced to drive to a required location If Fault Open and Fault Close are both off or both are set activ...

Page 6: ...n the actuator will position based on the fault override settings High Pressure SP is a high pressure alarm set point which is used to indicate that the pressure has exceeded the maximum allowable acc...

Page 7: ...uator will position based on the fault override settings To reset Overrun Fault Clear Fault must be set active This immediately resets the fault and then Clear Fault is automatically set to off such t...

Page 8: ...settings because it cannot be certain the pressure has not dropped below the minimum allowable supply pressure 4 2 Controller Access Whenever the controller is powered on the Controller On output is s...

Page 9: ...Actuator is fully closed Pump Output Pump is running ACTUATOR POSITION Provides the current actuator position based on the analogue signal If the signal is in fault 0 0 will be shown COMMAND Provides...

Page 10: ...urrently present Below are the statuses that can be displayed Healthy Accumulator is operating within required limits Pump Output Pump is running Acc Press Fault Pressure signal is in fault Pump Fault...

Page 11: ...signal fault Common Fault Set active when there is a signal indicating an external fault Pump On Demand Set active to enable use of pump on demand features Run Pump To Opn Set active to run the pump w...

Page 12: ...mand signal is in fault Common Fault Set active when there is a signal indicating a common fault Pump Output Set active when the pump is required to run Pump Fault Set active when there is a signal in...

Page 13: ...ic DZ Value indicating how much the command signal must be less than the feedback position when the actuator is static before it starts to close Close Moving DZ Value indicating how much the feedback...

Page 14: ...e position when the actuator is opening Close Limit Move Time that the Close Solenoid pulses active when at the pulse zone limit when the actuator is closing Close Blnce Move Time that the Close Solen...

Reviews: