3.   Pump Setup 

 

ORM0043_2 

Modulating Controller Application Manual 

Page 7 

 

If 

Fail On Pump Flt

 

is active then the actuator will 

position based on the fault override settings. 

3.4   Pump Fault 

The 

Pump Fault

 

input is used to indicate that there is a 

fault with the pump motor and should be linked to the 
digital input provided by the pump indicating whether 
the pump is healthy or not. 

If 

Pump Fault

 

is active then the 

Pump Fault

 

output is set 

active and 

Pump Output

 

is turned off as the pump is in 

fault. If 

Fail On Pump Flt

 

is active then the actuator will 

position based on the fault override settings. 

3.5   Pump Overrun Fault 

Pump Run Max

 

time can be set to specify the 

maximum length of time that the pump can continuously 
run for. This is included to prevent the pump being used 
beyond its certified limits and prevent the possibility of it 
running indefinitely. 

Once the 

Pump Output

 

has been continuously active for 

greater than the 

Pump Run Max

 

time, 

Overrun Fault

 

is 

latched active. Once 

Overrun Fault

 

is active it turns 

Pump Output

 

off which prevents the pump being run 

and because the 

Overrun Fault

 

is latched the pump 

cannot be run until the fault is reset. 

If 

Fail On Pump Flt

 

is active then the actuator will 

position based on the fault override settings. 

To reset 

Overrun Fault

Clear Fault

 

must be set active. 

This immediately resets the fault and then 

Clear Fault

 

is 

automatically set 

to off (such that it doesn’t 

automatically clear 

Overrun Fault

 

if it were to occur 

again).  

Alternatively the switch can be held away for more than 
three seconds in Automatic mode which will also reset 

Overrun Fault

3.6   Low Oil Level 

A level switch can be linked to 

Low Oil Level

 

input to 

indicate when the pump oil reservoir has reached a low 
level limit. 

If 

Low Oil Level

 

is active for greater than 

Lx Limit Delay

 

time, then 

Low Level Fault

 

output is set active.  

If 

Lo Lvl Pump Lock

 

is also active then 

Pump Output

 

is 

turned off which prevents the pump running if there is 
insufficient oil in the reservoir. If 

Fail On Pump Flt

 

is also 

active then the actuator will position based on the fault 
override settings. 

3.7   High Oil Temperature 

A temperature switch can be linked to 

High Oil Temp

 

input to indicate that the oil temperature has reach a 
high temperature limit. 

If 

High Oil Temp

 

is active for greater than 

Tx Limit Delay

 

time, then 

High Temp Fault

 

output is set active.  

If 

Hi Tmp Pump Lock

 

is also active then 

Pump Output

 

is 

turned off which prevents the pump running if there is 
an unusually high oil temperature. If 

Fail On Pump Flt

 

is 

active then the actuator will position based on the fault 
override settings. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for Orange EHPC210

Page 1: ...ower Limited The content of this document may not be used for purposes other than that for which it has been supplied and may not be reproduced either wholly or in part nor may it be used by or its co...

Page 2: ...m Values 13 6 4 System Times 14 6 5 HART Variables 14 This manual provides instruction on the setup and analysis of the modulating controller application Section 2 details specific actuator modules in...

Page 3: ...be linked to the input providing the actuator position signal which provides a calibrated 0 100 value In standard operation 4 20mA Cmd Input should be active meaning that the command value is taken f...

Page 4: ...or both limits of the pulse zone these being the set pulse zone Limit and when the command and actual position are equal Blnce A transfer function is then used within the application to set the requir...

Page 5: ...ide When the controller is in automatic mode if the actuator goes into fault the actuator can be forced to drive to a required location If Fault Open and Fault Close are both off or both are set activ...

Page 6: ...n the actuator will position based on the fault override settings High Pressure SP is a high pressure alarm set point which is used to indicate that the pressure has exceeded the maximum allowable acc...

Page 7: ...uator will position based on the fault override settings To reset Overrun Fault Clear Fault must be set active This immediately resets the fault and then Clear Fault is automatically set to off such t...

Page 8: ...settings because it cannot be certain the pressure has not dropped below the minimum allowable supply pressure 4 2 Controller Access Whenever the controller is powered on the Controller On output is s...

Page 9: ...Actuator is fully closed Pump Output Pump is running ACTUATOR POSITION Provides the current actuator position based on the analogue signal If the signal is in fault 0 0 will be shown COMMAND Provides...

Page 10: ...urrently present Below are the statuses that can be displayed Healthy Accumulator is operating within required limits Pump Output Pump is running Acc Press Fault Pressure signal is in fault Pump Fault...

Page 11: ...signal fault Common Fault Set active when there is a signal indicating an external fault Pump On Demand Set active to enable use of pump on demand features Run Pump To Opn Set active to run the pump w...

Page 12: ...mand signal is in fault Common Fault Set active when there is a signal indicating a common fault Pump Output Set active when the pump is required to run Pump Fault Set active when there is a signal in...

Page 13: ...ic DZ Value indicating how much the command signal must be less than the feedback position when the actuator is static before it starts to close Close Moving DZ Value indicating how much the feedback...

Page 14: ...e position when the actuator is opening Close Limit Move Time that the Close Solenoid pulses active when at the pulse zone limit when the actuator is closing Close Blnce Move Time that the Close Solen...

Reviews: