12’–24’ BASIC 6
®
WWW.BIGASSFANS.COM ©2012 DELTA T CORP. ALL RIGHTS RESERVED
2
About this fan
The specifications of the fan depend on the size and model.
Technical specifications
Fan
size
Motor size Gear
ratio
Controller
rating
Minimum required
supply circuit size
Nominal
output
voltage, 3Φ*
Maximum full load
current
Power
consumption Max RPM
Airfoil
length
Suggested
distance
from ceiling
12 ft
(3.6 m)
1.0 hp
(0.75 kW) 15.8
1.0 hp
(0.75 kW)
20 A @ 100–125 V, 1 Φ
15 A @ 200–250 V, 1 Φ
10 A @ 200–250 V, 3 Φ
10 A @ 400–480 V, 3 Φ
10 A @ 575–600 V, 3 Φ
240 V
240 V
240 V
480 V
600 V
11.0 A
5.5 A
3.2 A
1.6 A
1.3 A
600 W
111 RPM
64’’
(163 cm) 5 ft (1.5 m)
14 ft
(4.3 m)
1.0 hp
(0.75 kW) 15.8
1.0 hp
(0.75 kW)
20 A @ 100–125 V, 1 Φ
15 A @ 200–250 V, 1 Φ
10 A @ 200–250 V, 3 Φ
10 A @ 400–480 V, 3 Φ
10 A @ 575–600 V, 3 Φ
240 V
240 V
240 V
480 V
600 V
11.0 A
5.5 A
3.2 A
1.6 A
1.3 A
660 W
94 RPM
76”
(193 cm) 5 ft (1.5 m)
16 ft
(4.9 m)
1.5 hp
(1.1 kW)
20.0
1.5 hp
(1.1 kW)
25 A @ 200–250 V, 1 Φ
15 A @ 200–250 V, 3 Φ
10 A @ 400–480 V, 3 Φ
10 A @ 575–600 V, 3 Φ
240 V
240 V
480 V
600 V
9.8 A
4.9 A
2.4 A
1.9 A
830 W
87 RPM
88’’
(224 cm) 6 ft (1.8 m)
18 ft
(5.5 m)
1.5 hp
(1.1 kW)
20.0
1.5 hp
(1.1 kW)
25 A @ 200–250 V, 1 Φ
15 A @ 200–250 V, 3 Φ
10 A @ 400–480 V, 3 Φ
10 A @ 575–600 V, 3 Φ
240 V
240 V
480 V
600 V
9.8 A
4.9 A
2.4 A
1.9 A
1180 W
85 RPM
100”
(254 cm) 6 ft (1.8 m)
20 ft
(6.1 m)
2.0 hp
(1.5 kW)
25.1
2.0 hp
(1.5 kW)
25 A @ 200–250 V, 1 Φ
15 A @ 200–250 V, 3 Φ
10 A @ 400–480 V, 3 Φ
10 A @ 575–600 V, 3 Φ
240 V
240 V
480 V
600 V
12.4 A
6.2 A
3.2 A
2.6 A
1130 W
69 RPM
112’’
(284 cm) 7 ft (2.1 m)
24 ft
(7.3 m)
2.0 hp
(1.5 kW)
28.3
2.0 hp
(1.5 kW)
25 A @ 200–250 V, 1 Φ
15 A @ 200–250 V, 3 Φ
10 A @ 400–480 V, 3 Φ
10 A @ 575–600 V, 3 Φ
240 V
240 V
480 V
600 V
12.4 A
6.2 A
3.2 A
2.6 A
1400 W
61 RPM
136’’
(345 cm) 7 ft (2.1 m)
* Output voltage will not exceed Input voltage, with the exception of 120 V models. All controllers produce 3 Φ output power, regardless of input phase.
Motor
• 1 to 2 hp motor
• NEMA Design B
•
208/230/460 Volts AC
• 1725 RPM
•
60 Hz, 3-phase
• Insulation: Class F
• Rating: 40° C Ambient–Continuous
Reduction gear
•
Concentric Helical Gear Reducer
•
Gear Hardened to 58-62 Rockwell C
•
Precision finished for low noise and long service life
• Double seals keep oil in and contaminants out
• Lubricated for life with synthetic oil
Pre-Installation
Summary of Contents for Basic 6