Status and warning messages
Message
Description
EPM Contains Earlier Firmware Version
This error will appear when you try to change a VFD parameter and the EPM firmware is older than the VFD’s
firmware.
To correct this condition
, press the STOP button, and then press the Memory/Enter button. Use the UP/DOWN
button to scroll to
P199
. Press the Memory/Enter button. Use the UP/DOWN button to scroll to a setting of
5
. Press
the Memory/Enter button to save the change. The VFD is now able to read/write the EPM properly.
Current Limit
Verify proper motor wiring and HP. Check for short circuits. Increase acceleration time.
Decel Override
Fan is stopping too fast, causing a DC Buss overvoltage. Drive is backing off the deceleration rate to prevent HP
(Over-voltage) fault.
Error
Invalid data or invalid command entered.
Fast Current Limit
Overload
Check for short circuits throughout the load. Increase accel time.
Flying Restart Attempt after Fault
Program Attempt Made in OEM Settings Mode
(P199=1)
Parameter changes are not permitted.
Reset EPM to OEM Defaults Failure
The EPM’s OEM dataset is missing or corrupt.
Fault Lockout
Auto restart failure after five unsuccessful restart attempts.
Start Pending
The drive has tripped and is waiting to restart.
Fan Stopped
Output frequency is 0 Hz.
Fault messages
Message
Description
High Temperature fault
Check for excessive load or a dirty heatsink. Improve the drive cooling ability.
Assertion Level fault
Check the assertion level switch relative to P120.
Personality fault
Drive hardware error
Cycle power, and then reprogram EPM. If the fault will not clear, replace the drive and EPM.
Control fault
Drive hardware error
Cycle power, and then reprogram EPM. If the fault will not clear, replace the drive and EPM.
Troubleshooting (cont.)
Troubleshooting the fan controller
Some controller issues can be resolved before requesting service. Review the below warning and fault messages and diagnostics
before contacting Customer Service for support.
Summary of Contents for Basic 6
Page 1: ...INSTALLATION GUIDE For help call 1 877 BIG FANS or visit www bigassfans com Basic 6 ...
Page 6: ...Notes ...
Page 48: ...Notes ...
Page 50: ......
Page 63: ......