Does the burner light?
W
ere the gas lines
purged of air?
Purge lines.
Check for the proper
orifice and air plate inside
the burner
.
Is the gas outlet pressure
3.5" for Natural Gas
(10
.5" for LP)?
Adjust the valve pressure
.
Is the inlet gas pressure during
ignition correct? (Natural 4.
6"
min., LP should be 11")
Measure voltage on valve
terminals. Is there 24 V
during ignition time
?
Is there gas outlet
pressure available during
the ignition period?
Check gas line stop cock.
Contact gas company
.
Are the wires connecting
the ignition module OK?
Replace/correct wires.
Replace ignition module
.
Turn valve ON.
Is the knob on the gas
valve in the ON position
?
Replace gas valve
.
Does the burner stay on
?
Are the wires
connecting the module
and electrode OK?
Inspect the ignition/flame
sense electrodes. Are they
in good condition
?
Measure the flame current
between the F+ and F-
terminals on the ignition
module using a 0–10 direct
current microamp meter
.
Is the flame above 2μAdc
?
Replace ignition module
.
Replace/correct wires.
Clean or replace electrode
.
Does the burner turn off
when the call for heat
ends
?
Check the thermostat and
check the continuity of the
ground wire
.
TROUBLESHOO
T ENDS.
If problems persist, contact
Big
Ass
Fans.
Contact Big
Ass
Fans.
www
.big
ass
fans.
com
NO
Replace electrode
.