MK (E3) 07/2009
page 22/70
6.2
Function overview program controller MB1
The main operation level contains the following
different screens:
•
Normal display
(Idle Mode or Manual Mode or
Program Mode)
•
Event List
•
Chart recorder function
•
Contact page
Button
VIEW ->
permits toggling between the
screens.
The
NORMAL DISPLAY
enables comparison of the
current temperature (W) to the set-point value (X).
CONTACT PAGE
08:43:55 20.10.09
Service Hotline
International: +49 7462 205 555
USA Toll Free: +1 866 885 9794
or +1 631 224 4340
: +7 495 988 1517
Россия и СНГ
service@binder-world.com
www.binder-world.com
CONFIG
VIEW->
VIEW->
Best conditions for your success
Contact BINDER service easily.
NORMAL DISPLAY
Idle Mode
W
X
08:43:55 15.12.07
CONFIG
VIEW->
PGM
TEMP
0.0
26.8
°C
HAND
or
W
X
08:43:55 15.12.07
CONFIG
VIEW->
PGM
X - TEMP
26.8
°C
HAND
No heating or refrigeration. The actual value (X) approximates ambient temperature. The fan is operating.
NORMAL DISPLAY
Manual Mode
W
X
08:43:55 15.12.07
CONFIG
VIEW->
PGM
TEMP
40.0
36.8
°C
HAND
The temperature value is maintained according to
the previous entered set-point (W).
NORMAL DISPLAY
Program Mode
W
X
08:43:55 15.12.07
PROGRAM 01/SEC1 00:09:59
CONFIG
HAND VIEW->
PGM
TEMP
40.0
36.8
°C
AUTO
A temperature program entered before via a pro-
gram table is run.
EVENT LIST
An overview over the last 16 events or error condi-
tions of the unit is displayed.
CHART RECORDER FUNCTION
Graphical display of the current temperature data,
offering to review the previous measurements on a
history screen. A memory interval of 5s corresponds
to a supervision period of 2.5 days.
08:43:55 15.12.07
08:43:55 15.12.07