KBF + KMF (E6) 07/2017
page 74/155
Pressing the
Reset alarm
icon mutes the buzzer for all active alarms. The icon then disappears.
•
Acknowledging while the alarm condition persists: Only the buzzer turns off. The visual alarm indica-
tion remains on the controller display. The alarm remains in the list of active alarms.
When the alarm condition has ended, the visual alarm indication is automatically cleared. The alarm is
then no longer in the list of active alarms.
•
Acknowledging after the alarm condition has ended: The buzzer and the visual alarm indication are
reset together. The alarm is then no longer in the list of active alarms.
•
The zero-voltage relay alarm output resets together with the alarm.
11.4 Tolerance range settings
In this menu you can set the deviation between the actual value and setpoint which that shall cause a
tolerance range alarm.
This function only activates after the set-point has been reached once.
Path:
Main menu > Settings > Various
Submenu “Various”.
•
Select the field “Range alarm delay” and enter the time in minutes, after which the range alarm shall
be triggered. Setting range: 15 min to 120 min. Confirm entry with
Confirm
icon.
•
Select the field ”Temperature range” and enter the desired value for the temperature range. Setting
range: 2 °C to 10 °C. Confirm entry with
Confirm
icon.
•
Select the field “Humidity range” and enter the desired value for the humidity range. Setting range: 5%
r.H. to 20% r.H. Confirm entry with
Confirm
icon.
After completing the settings, press the
Confirm
icon to take over the entries and exit the menu,
or
press
the
Close
icon to exit the menu without taking over the entries.
If there are actual values outside the tolerance range the following information icons for the correspond-
ing parameter are displayed:
Icon
Signification
Information
“Temperature range”
The temperature value is outside the tolerance range
“Humidity range”
The humidity value is outside the tolerance range
If the condition persists, an alarm is triggered after the configured interval (“range alarm delay”). It is visu-
ally indicated in Normal display. If the alarm buzzer is activated (chap. 11.5) there is an audible alert. The
zero-voltage relay alarm output (option, chap. 19.5) switches to transmit the alarm. The alarm is shown in
the list of active alarms (chap. 11.3).
Summary of Contents for KBF 115
Page 137: ...KBF KMF E6 07 2017 page 137 155 23 8 Dimensions size 115 ...
Page 138: ...KBF KMF E6 07 2017 page 138 155 23 9 Dimensions size 240 ...
Page 139: ...KBF KMF E6 07 2017 page 139 155 23 10 Dimensions size 720 ...
Page 140: ...KBF KMF E6 07 2017 page 140 155 23 11 Dimensions size 1020 ...
Page 142: ...KBF KMF E6 07 2017 page 142 155 ...
Page 143: ...KBF KMF E6 07 2017 page 143 155 ...
Page 144: ...KBF KMF E6 07 2017 page 144 155 24 2 EU Declaration of Conformity for KMF ...
Page 145: ...KBF KMF E6 07 2017 page 145 155 ...
Page 146: ...KBF KMF E6 07 2017 page 146 155 ...
Page 148: ...KBF KMF E6 07 2017 page 148 155 ...
Page 149: ...KBF KMF E6 07 2017 page 149 155 25 Product registration ...