Glossary of Terms

ASHRAE

The American Society of Heating, Refrigerating and Air-Condi-
tioning Engineers. It focuses on building systems, energy effi-
ciency, indoor air quality, refrigeration and sustainability technol-
ogies.  ASHRAE publishes guidelines for Ultraviolet lamp systems 
for treatment of both air and surfaces.

Irradiance (UV)

The power per unit area received from a UV source in the form 
of electromagnetic radiation at a wavelength or in a wavelength 
range.  For evaporator coil surface disinfection, ASHRAE recom-
mends a minimum of 50-100 μW/cm2 as measured on the coil 
surface at 254nm.

Cooling Effects

Lamp UV output is critically dependent on mercury vapor pres-
sure, which in turn is dependent on temperature.  Below 80°F 
[27°C] UV output can decrease by as much as 50%.  Cooling 
effects are noted and are factored into CoilCare® system design.

Reflectance

Ultraviolet light can be reflected off of surfaces, the degree of 
which depends on the specific material.  CoilCare®’s reflectors 
can re-direct and focus up to 1.75 times more irradiance onto 
the coil surface than the same system without reflectors.

Ultraviolet

Ultraviolet (UV) light is an electromagnetic radiation with a wave-
length from 400 nm to 10 nm, shorter than that of visible light 
but longer than X-rays. UV radiation constitutes about 10% of 
the total light output of the Sun. UV light can also be produced 
by specialized lights, and UV systems have been used for over a 
century to disinfect water, surfaces, and air.

UVGI

Ultraviolet germicidal irradiation (UVGI) is a disinfection method 
that uses short-wavelength ultraviolet (UV-C) light to kill or inac-
tivate microorganisms by destroying nucleic acids and disrupting 
their DNA, leaving them unable to perform vital cellular func-
tions. UVGI is used in a variety of applications, such as food, air, 
and water purification.

Summary of Contents for CoilCare Series

Page 1: ...COILCARE X 2017 BioZone Scientific International Inc 81200012B Installation Instructions and Operating Manual CoilCare Series...

Page 2: ...g efficiently The system is equipped with a UV lamp and a reflector to direct and focus UV light on the coil surface The water resistant power supply is easy to mount and can withstand the humid envir...

Page 3: ...veness expected at beyond 48in 1219mm radius from lamp center axis When coil depth is more than 12in 305mm treating both sides of the coil may be indicated 12 305 mm max space between lamps 6 152 mm m...

Page 4: ...tibility 4 Recommendations for Effective CoilCare Installations EMT Conduit In most situations when the system is mounted to surfaces perpendicular to the surface to be irradiated L brackets are attac...

Page 5: ...t Use pipe coupling to extend the vertical support between the floor and ceiling for a snug fit Channel Strut In situations where larger coil surfaces require CoilCare systems comprising several UV la...

Page 6: ...of the HVAC system that is convenient for access to the electrical supply and for connection to the UV lamps The power supply is weather resistant and is suitable for mounting to the interior or exter...

Page 7: ...r handler and exterior for connections as needed INSTALLATION INSTRUCTIONS 7 1 Connect Lamps and Cables Arrangecablesasneededforinstallation Ifnecessary use the Optional 3 4 or 1 cable strain relief t...

Page 8: ...g Label The UV Warning Label contains fields convenient to record installation and service information It is recommended to record installation and service details on the UV Warning Label as those fun...

Page 9: ...DISCONNECT BEFORE SERVICING OPERATION AND MAINTENANCE 9 As needed periodically wipe the UV lamps with a clean cloth or alcohol swab to remove any accumulated dust or dirt This process should be perfor...

Page 10: ...ow after they have exceeded their rated lifespan however their germ killing effectiveness diminishes with time so they must be replaced on schedule for the system to function properly Contactyourlocal...

Page 11: ...tional Inc are used with this equip ment Consequential and incidental damages are not recoverable under this warranty Manufacturer assumes no liability for any harm which may occur as a result of the...

Page 12: ...low 80 F 27 C UV output can decrease by as much as 50 Cooling effects are noted and are factored into CoilCare system design Reflectance Ultraviolet light can be reflected off of surfaces the degree o...