•  Air Velocity: 400-500 fpm [2-2.5m/s] maximum

•  Air Temperature: 40°F – 110°F maximum [4°C – 43°C]

•  Lamp Distance from Coil: 6in – 48in [152mm – 1219mm]

•  Electrical Wiring: compliant with local and national code, UL/ETL standards

•  Safety Measures: alarms and disconnects, warning signage, employee training

•  Lamp Disposal: in accordance with local and national regulations (see lamprecycle.org 

for more information)

•  Insulation Guidelines for Safety: the use of UV resistant materials such as aluminum 

reflectors, shielding, jacketing, and tape, may be indicated to protect non-UV-compatible 

materials  in  the  treatment  area.    Contact  BioZone  Scientific  if  specific  questions  arise 

concerning material compatibility.

4

Recommendations for Effective CoilCare Installations

EMT/Conduit

In  most  situations,  when  the  system  is  mounted  to  surfaces  perpendicular  to  the 
surface  to  be  irradiated,  L-brackets  are  attached  to  the  wall  or  support  with  self-
tapping screws.  

Measure the distance between the L-brackets and cut tubing 1” less than the distance 
between L-brackets.  Extend  the  tubing between the  L-brackets  and  fasten  at  each 
end. 

1.

Install Framing

INSTALLATION INSTRUCTIONS

First,  determine  the  ideal  mounting  location  within  the  HVAC  system,  and  then 
configure the CoilCare system accordingly. CoilCare can be mounted to the air handler 
wall or similar support several ways depending on the size, orientation, and distance 
between the mounting surfaces and surfaces to be irradiated.  

Contact your BioZone commercial UV specialist with any questions or concerns prior 
to installation.

Summary of Contents for CoilCare Series

Page 1: ...COILCARE X 2017 BioZone Scientific International Inc 81200012B Installation Instructions and Operating Manual CoilCare Series...

Page 2: ...g efficiently The system is equipped with a UV lamp and a reflector to direct and focus UV light on the coil surface The water resistant power supply is easy to mount and can withstand the humid envir...

Page 3: ...veness expected at beyond 48in 1219mm radius from lamp center axis When coil depth is more than 12in 305mm treating both sides of the coil may be indicated 12 305 mm max space between lamps 6 152 mm m...

Page 4: ...tibility 4 Recommendations for Effective CoilCare Installations EMT Conduit In most situations when the system is mounted to surfaces perpendicular to the surface to be irradiated L brackets are attac...

Page 5: ...t Use pipe coupling to extend the vertical support between the floor and ceiling for a snug fit Channel Strut In situations where larger coil surfaces require CoilCare systems comprising several UV la...

Page 6: ...of the HVAC system that is convenient for access to the electrical supply and for connection to the UV lamps The power supply is weather resistant and is suitable for mounting to the interior or exter...

Page 7: ...r handler and exterior for connections as needed INSTALLATION INSTRUCTIONS 7 1 Connect Lamps and Cables Arrangecablesasneededforinstallation Ifnecessary use the Optional 3 4 or 1 cable strain relief t...

Page 8: ...g Label The UV Warning Label contains fields convenient to record installation and service information It is recommended to record installation and service details on the UV Warning Label as those fun...

Page 9: ...DISCONNECT BEFORE SERVICING OPERATION AND MAINTENANCE 9 As needed periodically wipe the UV lamps with a clean cloth or alcohol swab to remove any accumulated dust or dirt This process should be perfor...

Page 10: ...ow after they have exceeded their rated lifespan however their germ killing effectiveness diminishes with time so they must be replaced on schedule for the system to function properly Contactyourlocal...

Page 11: ...tional Inc are used with this equip ment Consequential and incidental damages are not recoverable under this warranty Manufacturer assumes no liability for any harm which may occur as a result of the...

Page 12: ...low 80 F 27 C UV output can decrease by as much as 50 Cooling effects are noted and are factored into CoilCare system design Reflectance Ultraviolet light can be reflected off of surfaces the degree o...