LAMP 

CONNECTOR

UV LAMP

PUSH FIRMLY 

TOGETHER

Mount Power Supply (continued)

Use  the  supplied  self-tapping  sheet  metal  screws 
to  mount  the  power  supply  in  place  through  the 
mounting holes on the sides of the base. 

It  is  recommended  to  use  junction  boxes,  our 
optional 3/4” or 1” cable strain relief, or other sealing 
methods in order to pass the power cord and lamp 
cables  between  the  interior  of  the  air  handler  and 
exterior for connections, as needed.

INSTALLATION INSTRUCTIONS

7

1.

Connect Lamps and Cables

Arrange cables as needed for installation. If necessary 
use the Optional 3/4” or 1” cable strain relief to pass 
cables through cabinets, air system walls, etc. 

Optional 10’ cable extensions are available for longer 
runs. 

When  UV  lamps,  power  supplies,  and  cables  are 
in place, join the UV lamp and lamp connectors by 
aligning the electrical pins and corresponding slots 
on  the  lamp  connectors  and  pushing  them  firmly 
together. Note that lamp connector may need to be 
rotated to matchup with the lamp pins. 

2.

2.

Summary of Contents for CoilCare Series

Page 1: ...COILCARE X 2017 BioZone Scientific International Inc 81200012B Installation Instructions and Operating Manual CoilCare Series...

Page 2: ...g efficiently The system is equipped with a UV lamp and a reflector to direct and focus UV light on the coil surface The water resistant power supply is easy to mount and can withstand the humid envir...

Page 3: ...veness expected at beyond 48in 1219mm radius from lamp center axis When coil depth is more than 12in 305mm treating both sides of the coil may be indicated 12 305 mm max space between lamps 6 152 mm m...

Page 4: ...tibility 4 Recommendations for Effective CoilCare Installations EMT Conduit In most situations when the system is mounted to surfaces perpendicular to the surface to be irradiated L brackets are attac...

Page 5: ...t Use pipe coupling to extend the vertical support between the floor and ceiling for a snug fit Channel Strut In situations where larger coil surfaces require CoilCare systems comprising several UV la...

Page 6: ...of the HVAC system that is convenient for access to the electrical supply and for connection to the UV lamps The power supply is weather resistant and is suitable for mounting to the interior or exter...

Page 7: ...r handler and exterior for connections as needed INSTALLATION INSTRUCTIONS 7 1 Connect Lamps and Cables Arrangecablesasneededforinstallation Ifnecessary use the Optional 3 4 or 1 cable strain relief t...

Page 8: ...g Label The UV Warning Label contains fields convenient to record installation and service information It is recommended to record installation and service details on the UV Warning Label as those fun...

Page 9: ...DISCONNECT BEFORE SERVICING OPERATION AND MAINTENANCE 9 As needed periodically wipe the UV lamps with a clean cloth or alcohol swab to remove any accumulated dust or dirt This process should be perfor...

Page 10: ...ow after they have exceeded their rated lifespan however their germ killing effectiveness diminishes with time so they must be replaced on schedule for the system to function properly Contactyourlocal...

Page 11: ...tional Inc are used with this equip ment Consequential and incidental damages are not recoverable under this warranty Manufacturer assumes no liability for any harm which may occur as a result of the...

Page 12: ...low 80 F 27 C UV output can decrease by as much as 50 Cooling effects are noted and are factored into CoilCare system design Reflectance Ultraviolet light can be reflected off of surfaces the degree o...

Reviews: