background image

3

Assembly, Commissioning, Periodical Tests

1.   Check the resistance. In the non-activated state between 8.1 kOhm and 

8.6 kOhm (typical 8.2 kOhm).

2.  Check the wiring. F1 (ESR26: F1 and F2) fitted with max. 2 A slow blow?
3.   Switch on the unit. When operational the green LED illuminates (with 

ESR26 both green LED’s)

4.   Activate the signal transmitter. The corresponding yellow LED illuminates 

(with ESR26 both yellow LED’s) and the output relay de-energises.  

5.   The red LED (with ESR26 both red LED’s) illuminates and the output relay 

deenergises when a terminal of the signal transmitter is not connected.

Important:

Assembly and wiring according to local regulations. The minimal 

cross-sectional area is 0.14 mm

2

. May only be installed in a IP54 

housing.

For periodical testing, the contacts J1 and J4  (with ESR26 J2 and J3) must 
be bridged consecutively (see Layout). Each time a Stop must occur. The test 
«interruption» is achieved by disconnecting the signal transmitter. Stop must 
occur.
We recommend that the tests be documented.

The tests are to be carried out by trained personell using a tool with 
insulated handle.

ESR25/26

Switching Units

Operating Instructions

ENGLI

SH

209491S

06/16

General

The difference between the ESR25 and ESR26 is that the ESR26 has two se-
parate evaluation circuits.

Function

Connected sensors are monitored with a terminating resistance of  8.2 kOhm 
to detect changes in the constant flowing zero-signal current. Both relays are 
energised in the non-active condition.

If one or more sensors are activated
• the total resistance drops towards zero ohm
• when the resistance falls below the defined limit (2 kOhm)
• the relays de-energise
• the yellow LED illuminates

When a fault occurs in the sensor circuit (cable breakage, sensor defect…)
• the total resistance increases
• when the resistance exceeds the defined limit (9 kOhm)
• the relays de-energise
• the red LED illuminates

Status LED

Supply

Function

green yellow red 

Output

Off

open

On

ready

closed

On

one sensor activated

open

On

short-circuit or test

open

On

cable breakage

open

Connection

• max. total length of sensor with cable 50 m
• max. total area of sensor 5 m

2

• multiple sensors are connected in series
• the total resistance must not exceed 8.2 kOhm

Important: 

–  The installed fuse is absolutely neccesary. It protects the relay 

contacts against «welding» when overloaded.

–  Suppressors (220 Ohms/0.1 uF) are to be connected across the in-

ductive loads.

–  Periodical function test are to be made. 

 

The designated test contacts are to be bridged (see Layout).

The protection of the unit will be endangered by non-adherence of 
these operating manual instructions.
The user acts at his own risk!

Block Diagram

Sensor 1

22(5)
32(8)

R1

R3

24(7)
34(9)

A1(2)
A2(10)

Supply

Voltage

Sensor 2

or 8.2kOhm resistance

F1

11(1)

Drive

Circuit

21(6)

ESR25

• two parallel sensor inputs
• safety output
• supply voltage 24 VACDC
• redundant evaluation of the sensor

ESR26

• two separate sensor inputs
• two separate safety outputs
• supply voltage 24 VACDC
• redundant evaluation of both channels

Sensor 1

22(5)

32(8)

R1

R3

R2

R4

24(7)

34(9)

A1(2)

A2(10)

Supply

Voltage

Sensor 2

F1

F2

11(1)

Drive

Circuit 1

Drive

Circuit 2

21(6)

14(3)

12(4)

Summary of Contents for ESR25

Page 1: ...samtwiderstand gegen Null Ohm die definierte Schaltgrenze wird unterschritten ca 2 kOhm die Relais fallen ab die gelbe LED leuchtet Bei Störung im Signalgeberkreis Kabelbruch Signalgeberausfall der Gesamtwiderstand steigt die definierte Schaltgrenze wird überschritten ca 9 kOhm die Relais fallen ab die rote LED leuchtet Status LED Speisung Funktion grün gelb rot Ausgang Aus offen Ein bereit geschl...

Page 2: ...terprüfbescheinigung In Kombinationen mit Schaltleisten Notifizierte Stelle Suva Bereich Technik SCESp 0008 Kenn Nr 1246 Produktvarianten ESR25 24VACDC ESR26 24VACDC Identifizierung des Baujahrs Kontakt EU Konformitätserklärung Bircher Reglomat AG Wiesengasse 20 CH 8222 Beringen www bircher reglomat com Ausführung entstanden sind sowie Schäden die aus anderen Gründen entstanden sind welche die Bir...

Page 3: ...e condition If one or more sensors are activated the total resistance drops towards zero ohm when the resistance falls below the defined limit 2 kOhm the relays de energise the yellow LED illuminates When a fault occurs in the sensor circuit cable breakage sensor defect the total resistance increases when the resistance exceeds the defined limit 9 kOhm the relays de energise the red LED illuminate...

Page 4: ...tantly develops its pro ducts further Bircher Reglomat AG reserves the right to make changes to any of the products described in this document without prior notice Warranty and liability Year Month Day 2015 06 17 Housing NORYL red Face Black Dimensions 85 x 74 x 36 mm Isolation Class IP30 Isolation Class IP54 Temperature Range 20 C to 55 C Power Supply 24 VACDC 10 Frequency 50 60 Hz Power Consumpt...

Reviews: