Identification of the year of manufacture

10.2

Year of

manu-

facturing

Week

red LED

green LED

Fault

Remedy

dark

continu-
ously lit

Radar tripping when door is closing

1. Set angle of radar further away from the door.

2. Adjust radar field size.

Radar false tripping without
apparent external influence

1. Avoid light sources (e.g. fluorescent tubes) in the immediate vicinity of the detector.

2. No moving objects (e.g. plants, advertising posters, etc.) in the vicinity of the detector.

3. Avoid strong vibration at the radar detector
4. Possible influence from a second radar detector in the vicinity (very unlikely)

continu-
ously lit

dark

AIR tripping when door is closing

1. Set angle of AIR detector further away from the door

AIR false tripping without apparent 
external influence

1. Avoid light sources (e.g. fluorescent tubes) in the immediate vicinity of the detector.
2. Avoid puddles of water on the ground.
3. Avoid strong vibration at the AIR detector.
4. Influence of overlapping AIR field from another detector.  

Set new Reglobeam address or CAN bus address.

5. Reduce sensitivity of the AIR.

dark

dark

Door stays open

1. Switch AIR exit contact logic to other value

flashing

dark

1: Self test (RAM/ROM)

2: Watchdog

1. Disconnect device from supply voltage
2. Clean lens
3. Restart device
4. If device displays fault again or does not start 

renew device

dark

flashing

3: Radar fault

4: Radar exit fault (SM)

1. Disconnect device from supply voltage
2. Check plug on microwave module
3. Restart device
4. If device displays fault again or does not start 

renew device

flashing

dark

5: AIR fault

6: AIR exit fault

1. Disconnect device from supply voltage
2. Restart device
3. If device displays fault again or does not start 

renew device

Remedying malfunctions

8

Most important technical data

9

Declaration of conformity, identification of the year of manufacture by means of the serial number

10

11

Contact data

Manufacturer:

Bircher Reglomat AG

Wiesengasse 20

CH-8222 Beringen

Switzerland

www.bircher-reglomat.com

Remedying false tripping

8.1

Remedying detector malfunctions

8.2

Declaration of conformity

10.1

red LED

green LED

LCD 

Fault

Remedy

PrimeTec / PrimeScan 
Technology

Active infrared (wavelength: 880nm), radar double field module 

➝ 

PrimeTec (24.125 GHz)

Number of IR spots

36

IR spot dimensions

3 cm x 3 cm (at 2.2 m mounting height)

Response time

< 200 ms

Mounting height

1.8 – 4 m

Angle setting of IR spots

5° - 7° continuously adjustable

Electrical power supply 

120 mA @ 11.5 – 32 VDC

Power consumption

< 4 watts

Making current

240 mA

Output (AIR / Radar)

Optocoupler (50 VDC, 50mA)

Protection class

Suitable for use acc. to IP54

EMC / RTTE

acc. to EMC and RTTE directives

Remote control range

3 m

Operating temperature

- 20° to 60° C

Dimensions

PrimeTec: 260 x 60 x 48.5mm (LxWxD), PrimeScan: 216 x 60 x 47.5mm (LxWxD)

Weight

PrimeTec: 250g, PrimeScan: 180g

Life cycle

20 years

Manufacturer: 

Bircher Reglomat AG,  Wiesengasse 20, CH-8222 Beringen, Switzerland, www.bircher-reglomat.com

Authorised rep:

Bircher Reglomat GmbH, Robert Bosch Strasse 3, D-71088 Holzgerlingen, Germany

Notified Body:

TÜV NORD CERT GmbH, Langemarckstrasse 20, D-45141 Essen, NB 0044, EC-type-examination certificate No. 44 205 10 554810

Following directives have been observed: 2006/42/EC, R&TTE Directive 1999/5/EC, EMV-Directive 004/108/EC
Following standards have been taken into account:  EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, DIN 18650-1:2005, EN 12978:2003+A1:2009, 

EN ISO 13849-1:2008, Cat. 2/PLd (AIR) & Cat. 3/PLd (Radar),  IEC 61494-1, AutSchR, 1997/BS7036-1 & BS7036-2

Signee:

CEO, L. Oberholzer / QHSE, K. Kuhn / 20.5.2010, CH-8222 Beringen

Product variant: 

PrimeTec A ES, PrimeScan A, PrimeTec A ES/01, PrimeTec A ES.SM.V, PrimeTec A.SM.F, PrimeTec A.SM/01, PrimeTec A.SM/02, PrimeTec A.SM/03

Reviews: