KB-120-8
23
4
Mounting
4.1
Vibration dampers
The compressor can be rigidly mounted if there is no
risk of damage caused by vibration in the pipeline sys-
tem connected to it. Otherwise the compressor must be
mounted on vibration dampers.
Mounting the suction gas and discharge gas lines:
• Place the compressor on the vibration dampers or
mount it rigidly. In this position (= operational posi-
tion), connect the suction gas and discharge gas
lines and make sure that they are stress-free. Select
the vibration dampers according to the following
tables:
Compressor
Kit number, article number
(4 pieces)
Hardness
2MME-07K .. 2DME-7K
370 005 02
60 Shore
4FME-7K .. 4DME-10K
370 005 02
60 Shore
4TME-20K .. 4PME-25K
370 005 03
55 Shore
6TME-35K, 6PME-40K
370 005 03
55 Shore
2NSL-05K .. 2FSL-4K
370 000 19
43 Shore
2ESL-4K .. 2CSL-6K
370 000 20
55 Shore
4FSL-7K .. 4CSL-12K
370 000 20
55 Shore
Tab. 2: Vibration dampers 2MME-07K .. 6PME-40K, 2NSL-05K .. 4CSL-12K
Compressor
Kit number, art-
icle number
(2 pieces)
Crankcase side
Hardness
Kit number, art-
icle number
(2 pieces)
Motor side
Hardness
4VSL-15K .. 4NSL-30K
370 002 11
60 Shore
370 002 10
65 Shore
Tab. 3: Vibration dampers 4VSL-15K .. 4NSL-30K