5 Commissioning

The compressor is already thoroughly
dried, tested for leaks and under pres-
sure with holding charge (N

2

). 

Attention!

Test the strength pressure and
the tightness of the entire plant
preferably with dry nitrogen (N

2

).

Compressor must be isolated
from circuit when using dried air
– keep the shut-off valves closed.
Danger of oil oxidation!

Danger!

By no means the compressor
may be pressure tested with
oxygen or other industrial 
gases!

Warning!

Never add refrigerant to the test
gas (N

2

or air) – e. g. as leak

indicator.
Critical shift of the refrigerant
ignition limit with high pressure
possible!
Environmental pollution with
leakage or when deflating!

5.1 Strength pressure test

Evaluate the refrigerant circuit 
(as semb ly) according to EN 378-2 
(or valid equivalent safety standards). 
The compressor had been already
tested in the factory for strength pres-
sure. Therefore a tightness test (5.2)
is sufficient.

However, if the whole assembly is
tested for strength pressure:

Danger!

Test pressure may not exceed
the maximum operating pres-
sures indicated on the name
plate!
If necessary leave the shut-off
valves closed!

!

!

!

5 In Betrieb nehmen

Der Verdichter ist ab Werk sorgfältig
getrocknet, auf Dichtheit geprüft und
mit Schutz  gas (N

2

) befüllt.

Achtung!

Druckfestigkeit und Dichtheit der
gesamten Anlage bevorzugt mit
getrockneten Stickstoff (N

2

) prüfen.

Bei Verwendung von getrockne-
ter Luft Verdichter zum Kreislauf
hin abtrennen – Absperrventile
unbedingt geschlossen halten.
Gefahr von Oxidation des Öls!

Gefahr!

Verdichter darf keinesfalls mit
Sauerstoff oder anderen techni-
schen Gasen abgepresst wer-
den! 

Warnung!

Dem Prüfmedium (N

2

oder Luft)

keinesfalls Kältemittel beimi-
schen – z. B. als Leck-Indikator.
Kritische Verschiebung der
Kältemittel-Zündgrenze bei
Überdruck möglich!
Umweltbelastung bei Leckage
und beim Abblasen!

5.1 Druckfestigkeit prüfen

Kältekreislauf (Baugruppe) ent-
sprechend EN 378-2 prüfen (oder 
gültigen äqui va lenten Sicher heits -
normen). Der Verdichter wurde 
bereits im Werk einer Prüfung auf
Druckfestigkeit unterzogen. Eine
Dichtheits prüfung (5.2) ist deshalb
ausreichend.
Wenn dennoch die gesamte Bau-
grup pe auf Druckfestigkeit geprüft
wird:

Gefahr!

Prüfdruck des Verdichters darf
die maximal zulässigen Drücke
nicht überschreiten, die auf 
dem Typschild genannt sind!
Bei Bedarf Absperrventile
geschlossen halten!

!

!

!

KB-104-4

5 Mise en service

Le compresseur est soigneusement
séché en usine, son étanchéité est
contrôlée et il est rempli avec un gaz 
de protection (N

2

).

Attention !

Essayer la résistance à la pression
et l'étanchéité de toute l'installation
préféremment avec l'azote sec (N

2

).

Compresseur doit être separé du
circuit quand l'air sec est vitilisé.
– maintenir les vannes d'arrêt
fermées.
Danger d'oxidation d'huile !

Danger !

Ne faire, en aucun cas, les essais
de pression sur le compresseur
avec de l'oxygène ou tout autre 
gaz technique ! 

Avertissement !

Ne jamais ajouter fluide frigorigène
au gaz d'essai (N

2

ou air) – par ex.

comme indicateur de fuite.
Décalage critique de la limite d'in-
flammabilité du fluide frigorigène
possible, en cas de surpression !
Pollution de l'environnement en 
cas de fuite ou d'évacuation du 
système !

5.1 Essayer la résistance à la pression

Essayer le circuit frigorifique (groupe 
as semb lé) correspondant à EN 378-2 
(ou normes de sécurité équivalentes, 
qui sont valables). Le compresseur était
déjà essa yé à l'usine sur son résistance 
à la pression. Par ça un essai d'étan-
chéité (5.2) est suffisiant.

En cas d'essayer néanmoins la rési-
stance à la pression du tout le groupe
assemblé:

Danger !

Le timbrage ne doit pas excéder 
les pressions de service maximales
qui sont marquées sur la plaque
d'identité !
En cas utile laisser les vannes
d'arrêt fermées !

!

!

!

Summary of Contents for ECOLINE

Page 1: ...Y 44CES 18 Y 4VE S 6Y 4NE S 20 Y 44VE S 14 Y 44NE S 40 Y 4JE 13Y 4FE 35 Y 44JE 30 Y 44FE 70 Y 6JE 22Y 6FE 50 Y 66JE 50 Y 66FE 100 Y 8GE 50 Y 8FE 70 Y 2DES 3 F1Y 4FES 5 F1Y 4CES 9 F3Y 4VES 7 F3Y 4NES 2...

Page 2: ...ctively valid guidelines The compressors are constructed according to the state of the art and valid regulations Particular emphasis has been placed on the users safety Retain these Operating Instruct...

Page 3: ...ure Incorrect handling may cause injury to skin and eyes Wear safety goggles while work ing on compressor Do not open connections before pressure has been released Caution During operation surface tem...

Page 4: ...nbedingt vermeiden Weitere K ltemittel auf Anfrage Alternativ le siehe Technische Informationen KT 500 und KT 510 Further refrigerants upon request For alternative oils see Technical Informations KT 5...

Page 5: ...compressors with spreader bar only 3 2 Compressor installation Place of installation Install the compressor horizontally For operation under extreme condi tions e g aggressive or corrosive atmospheres...

Page 6: ...ition posi tion de travail raccorder les conduites d aspiration et de refoulement sans contraintes sur celles ci S curit de transport des groupes Pour les livraisons de groupes les l ments antivibrato...

Page 7: ...de C t carter Schwingungsd mpfer Anti vibration mountings Amortisseurs de vibrations Motorseite Motor side C t moteur A B 4VE S 6Y 4NE S 20 Y 370 003 05 gelb yellow jaune 370 003 07 braun brown brun 3...

Page 8: ...to the size the tube can be pushed more or less into the fitting If not required the end with the largest diameter can be cut off Shut off valves During operation keep shut off valves either complete...

Page 9: ...protection gas Install cleaning suction side filter mesh size 25 m Attention Compressor damage possible Generously sized high quality fil ter driers must be used to ensure a high degree of dehy dratio...

Page 10: ...nfusions la t te de cylindre et la bride de la vanne sont iden tifi es avec un indice SU ou plut t CR Une goupille de positionnement log e dans la bride assure un assemblage cor rect voir figure 3 3 4...

Page 11: ...ications about start unloading see Technical Information KT 110 D marrage vide SU Accessoire particulier pour 4VE S 6 Y 6FE 50 Y En cas de montage ult rieur une chan ge du t te de culasse est n cessai...

Page 12: ...ol CRII System optional for 4FES 3 Y 4CES 9 Y 4VE S 6Y 4NE S 20 Y 4JE 13Y 4FE 35 Y 6JE 22Y 6FE 50 Y 8GE 50 Y 8FE 70 Y 44FES 6 Y 66FE 100 Y Retrofit requires exchange of the cylinder head Mounting posi...

Page 13: ...F 2 HP 1 8 27 NPTF 1 8 27 NPTF 4FES 3 Y 4CES 9 Y 4FES 5 1Y 4CES 9 F3Y 4VES 7Y 4NES 20 Y 4VES 7 F3Y 4NES 20 F4Y 2KES 05 Y 2FES 3 Y SL DL 5 8 1 HP 1 8 27 NPTF 3 LP 1 8 27 NPTF 6 7 16 20 UNF 10 M8x1 5 11...

Page 14: ...4 18 NPTF DL SL 4JE 13Y 4FE 35 Y 6JE 22Y 6FE 50 Y 4VE 7Y 4NE 20 Y DL 7 16 20 UNF 4 3 LP SL 5 8 1 4 18 NPTF 21 1 2 14 NPTF 6 M10x1 5 10 12 16 M20x1 5 1 HP 2 HP 1 8 27 NPTF 1 8 27 NPTF 7 M20x1 5 12 7 16...

Page 15: ...el correspondant SL DL 3 LP 1 8 27 NPTF 5 7 16 20 UNF 1 4 18 NPTF 8 22EES 2 Y 22CES 4 Y 5 7 16 20 UNF 1 8 27 NPTF 8 DL SL DL 3 LP 1 8 27 NPTF 1 8 27 NPTF 1 HP 44FES 6 Y 44CES 18 Y 3 4 14 NPTF 1 2 14 N...

Page 16: ...sistance de carter 11 Raccord de la pression d huile 12 Raccord de la pression d huile 16 Raccord pour contr le d huile sonde d huile opto lectronique OLC K1 ou pressostat diff rentielle d huile Delt...

Page 17: ...mounting Achtung Danger of motor damage Incorrect electric wiring or opera ting the compressor with wrong voltage or frequency may leed to overloading of the motor Observe specifications on name plate...

Page 18: ...e 50 50 S lection de contacteurs du moteur 1er Contacteur PW 1 60 de courant de service maximal 2i me Contacteur PW 2 60 de courant de service maximal Version moteur 3 en fonctionnement avec convertis...

Page 19: ...S 9 Y 4VE S 6Y 4NE S 20 Y 2DES 3 F1Y 4NES 20 F4Y is mounted inside the terminal box The cables for the motor temperature sensor are already connected Other connections should be made accord ing to Tec...

Page 20: ...sskasten KB 104 4 Sonde de temp rature du gaz au refoulement Accessoire sp ciale 4FES 3 Y 4CES 9 Y 4FES 5 F1Y 4CES 9 F3Y 4VE S 6Y 4NE S 20 Y 4VES 7 F3Y 4NES 20 F4Y 4JE 13Y 4FE 35 Y 6JE 22Y 6FE 50 Y 8G...

Page 21: ...ener gized during standstill for outdoor installation of the compres sor long shut off periods high refrigerant charge danger of refrigerant condensation into the compressor Connections are according...

Page 22: ...g der K ltemittel Z ndgrenze bei berdruck m glich Umweltbelastung bei Leckage und beim Abblasen 5 1 Druckfestigkeit pr fen K ltekreislauf Baugruppe ent sprechend EN 378 2 pr fen oder g ltigen quivalen...

Page 23: ...kcase heater Open all shut off valves and solenoid valves Evacuate the entire system including compressor using a vacuum pump connected to the high and low pressure sides When the pump is switched off...

Page 24: ...ans l vaporateur Apr s la mise en service il peut s av rer n cessaire de proc der un appoint de fluide frigorig ne Le compresseur tant en service introduire le fluide frigorig ne du c t aspiration de...

Page 25: ...iquid slugging at start Adjust oil level within the marked sight glass range Oil temperature approx 15 20 K above ambient temperature resp suction side saturation tempera ture Setting and function of...

Page 26: ...tiel d huile lectronique option pour les com presseurs avec pompe huile integr e 4VE 6Y 4NE 20 Y 4JE 13Y 4FE 35 Y 6JE 22Y 6FE 50 Y 8GE 50 Y 8FE 70 Y pression diff rentielle de coupure 0 65 bar tempori...

Page 27: ...nt possible Avoid strong vibrations Cycling rate The compressor should not be started more than 8 times per hour Thereby a minimum running time should be guaranteed motor min running time to 5 5 kW 2...

Page 28: ...ue la conduite d aspiration ou le compresseur Inversion automatique des ordres de d marrage sur les installations avec plusieurs circuits frigorifiques L utilisation d un changeur de cha leur gaz aspi...

Page 29: ...and terminals with contact grease e g Shell Vaseline 8401 contact grease 6432 or equivalent Furthermore for the compressors 2KES 05 Y 4CES 9 Y the con densing water may be drained by per manently rem...

Page 30: ...sine En cas de r alisation sur le site ou de fonc tionnement aupr s des limites du domai ne d application autoris un premi r rem placement est pr conis e apr s environ 100 heures de fonctionnement Net...

Page 31: ...Do not release the refrigerant but dispose it properly Warning Compressor can be under pressure Severe injuries possible Wear safety goggles Loosen the threaded joints or flanges at the compressor val...

Page 32: ...au GmbH Eschenbr nnlestra e 15 71065 Sindelfingen Germany Tel 49 0 70 31 932 0 Fax 49 0 70 31 932 147 bitzer bitzer de www bitzer de Subject to change nderungen vorbehalten Toutes modifications r serv...