20
KT-200-2
The fans start when the condensing
temperature is 5 K above the current
ambient temperature or minimum 15°C.
With high ambient temperatures, they
are always operated at max. speed
from t
c
= 50°C.
This characteristic causes a
considerably reduced power
consumption of the condenser fans, in
particular with lower compressor
speeds.
To achieve additional savings in
systems with electronic injection valves,
the lower switch-on level of the
condenser fan (menu 4.2.5.8
M
IN
.S
ET
or
M
IN
.S
OLL
) may be reduced. On the
other hand, it might be necessary to
increase the lower switch-on level in
case of unfavourable configuration to
guarantee a certain minimum pressure
upstream of the injection valve.
When the upper switching threshold
(menu 4.2.5.10
M
AX
.S
ET
or
M
AX
.S
OLL
) is
exceeded, the condenser fans are
operated at maximum speed,
independently of the ambient
temperature.
凝縮温度が現在の外気温を
5 K
上回るか、
最低
15°C
になるとファンが起動します。
外気温が高い場合、
t
c
= 50°C
以上になる
とファンは常に最高速度で作動します。
この特性のため、特にコンプレッサーが
低速のときにはコンデンサーファンの消
費電力が大幅に低減します。
電子噴射弁付きシステムでは、さらに節
約できるよう、コンデンサーファンの下
限スイッチングレベル(メニュー
4.2.5.8
M
IN
.S
ET
または
M
IN
.S
OLL
)を下げることが
できます。一方で、不利となる設計の場
合には、噴射弁の上流側の最低圧力を保
証するために下限スイッチングレベルを
上げる必要があります。
上限スイッチングレベル(メニュー
4.2.5.10
M
AX
.S
ET
または
M
AX
.S
OLL
)を超えた場合
には、コンデンサーファンは外気温に関
係なく最高速度で作動します。
n Fan speed in %
t
c
Condensing temperature
t
amb
Ambient temperature
①
to
③
Speed characteristics (low sound
mode)
①
Example: 13°C ambient temperature
②
Example: 27°C ambient temperature
③
Example: 38°C ambient temperature
n
ファン速度(
%
)
t
c
凝縮温度
t
amb
外気温
①~③ 速度特性曲線(静音モード)
① 例:外気温
13°C
② 例:外気温
27°C
③ 例:外気温
38°C
Fig. 10 Characteristic of the fan speed in
low sound mode
図
10
静音モード時のファン速度の特性
E
IN
/ O
N
E
IN
/ O
N
E
IN
/ O
N