DB-300-9
11
4.5
Removal clearance for filter cartridge
Oil separators for NH
3
• OAC14011A .. OAC25112A
• OAS322 .. OAS3088
• OAHC65051A .. OAHC100051A
Combined and secondary oil separators must be moun-
ted such that the filter cartridges can be taken out (see
figure 2, page 11).
X
Fig. 2: Removal clearance for filter cartridge
Type
Removal clearance for fil-
ter cartridge (= X)
OAC14011A
460 mm
OAC25112A
460 mm
OAS322
120 mm
OAS744
260 mm
OAS1055
300 mm
OAS1655
600 mm
OAS3088
600 mm
OAHC65051A
460 mm
OAHC80051A
460 mm
OAHC100051A
460 mm
4.6
Delivery condition
The pressure vessel is sealed in the delivery condition
and filled with inert gas. The inert gas overpressure is
0.2 .. 0.5 bar. All Rotalock and flange connections are
closed by blanking plates. These plates must be re-
moved before commissioning.
4.7
Connecting the pipelines
The pipe connections are suitable for pipes in all com-
mon dimensions in millimetres and inches. Brazed con-
nections have stepped diameters. The pipe will im-
merge more or less depending on its dimensions. If not
required the end with the largest diameter can be cut-
off.
DANGER
Risk of bursting the pressure device due to
mechanical stress.
Serious injuries are possible.
Connect the pipeline to the pressure unit without
stress!
First relieve the excess pressure from the pressure
vessel: Open the connections carefully.
WARNING
The pressure equipment is under pressure!
Serious injuries are possible!
Depressurise the pressure equipment!
Wear safety goggles!
Remove shut-off valves and/or solder connections.
!
!
NOTICE
Potential chemical reactions due to air penetra-
tion!
Install the open pressure vessel immediately in
the system.
Reseal the pressure vessel during installation breaks.
!
!
NOTICE
Do not overheat the shut-off valves!
Cool the valve body during and after the brazing
operation.
Maximum brazing temperature 700°C!
When brazing or welding, rinse the corresponding con-
ductive parts with inert gas.
Summary of Contents for F062H(P)
Page 3: ...DB 300 9 3 8 Decommissioning 33 ...
Page 35: ...DB 300 9 35 8 Außer Betrieb nehmen 65 ...
Page 67: ...DB 300 9 67 8 Mettre hors service 98 ...
Page 99: ...Notes ...