3.1.5 ADC Setting
Figure 22: ADC Setting
Parameter Name
Description
ADC Choose
ADC0 to ADC2 is available for standard TG501, while ADC3
to ADC6 is for customized version TG501.
ADC type
Analog data type, Current or Voltage, the default is Current
4-20mA.
Upper Range
The upper range of analog input, refer to your sensor spec.
Lower Range
The lower range of analog input, refer to your sensor spec.
Input the Max
Cur(Vol)
The upper range of the sensor corresponds to the current or
voltage value input
Input the Min
Cur(Vol)
The lower range of the sensor corresponds to the current or
voltage value input
3.2 Modbus RTU Protocol
Please refer to Bivocom Modbus RTU protocol instruction for more details.