background image

10

OPERATING INSTRUCTIONS

5 VDC Output

The 5 Vdc is a fixed voltage supply providing up to 500 mA (0.5 amp) 

continuous. The 5 Vdc output is available at the two right 

OUTPUT 5V

 tie 

points. Be sure to observe polarity.

1.

The  12V  and  5V  supplies  will  provide  up  to  1  amp 
for  a  short  period,  but  thermal  shutdown  may  occur 
when  the  output  is  overloaded  for  a  few  minutes. 
Upon  thermal  shutdown  there  will  be  now  output.  If 
thermal  shutdown  occurs,  remove  the  load  and  wait 
15  minutes  for  the  power  supply  to  cool.  Normal 
operation may then resume.

2.

Overloading May also cause sever ripple I the output 
which  could  disrupt  operation  of  the  circuit  being 
powered.  Excessive  ripple  will  produce  a  loud  hum 
in devices with speakers.

3.

You  can  prevent  overloading  by  measuring  the 
output  current  with  an  external  multimeter.  Set  the 
meter to measure current (a 2 amp range is desirable, 
or  a  10  amp  range  may  be  used)  and  connect  is 
"series"  with  the  load.  Load  current  up  to  500  mA 
may  be  operated  continuously,  load  current  greater 
than  500  mA  must  be  short  term,  maximum  short 
term current is 1 amp.

DUAL OR TRIPLE OUTPUT

Two  of  the  outputs,  or  all  three  of  the  outputs  may  be  used 

simultaneously if desired. The three outputs are fully isolated from ground, 
and each other, thus each output may be connected for the either positive 
or negative polarity.

A typical example of a triple output application would be powering a 

circuit board that requires three voltages, such as +5, +12V and -12V. Fig. 
4  shows  how  the  outputs  would  be  connected  for  this  example,  and  the 
following procedures reviews the steps of hook-up.

1.

The  variable  supply  would  be  set  for  12V.  WE  will  assign  the 
variable  supply  as  the  +12V  source  and  the  fixed  12V  supply  as 
the -12V source.

2.

Connect the - terminal of the 5V supply to circuit board common 
and the + terminal to the +5V input of the board.

3.

Connect  the  -  terminal  of  the  variable  supply  to  circuit  board 
common  (or  the  terminal  of  the  5V  supply).  Connect  the  + 
terminal of the variable supply to the +12V input of the board.

4.

Connect  the  +  terminal  of  the  fixed  12V  supply  to  circuit  board 
common  (or  the  -  terminal  of  the  5V  and  variable  supplies). 
Connect the - terminal of the fixed 12V supply to the -12V input 
of the board.

CONNECTING OUTPUTS IN SERIES

When  the  30  volt  output  of  the  variable  supply  is  not  adequate,  the 

outputs  may  be  connected  in  series  to  provide  a  variable  17  to  47  volt 
output. Since the supplies are connected in series, the maximum current is 
the  same  as  for  the  fixed  voltage  supplies,  that,  500  mA  continuous  or  1 
amp peak. Connections for the configuration are shown in Fig. 5.  

CAUTION

Summary of Contents for 1671A

Page 1: ...INSTRUCTION MANUAL MODEL 1671A INSTRUCTION MANUAL MODEL 1671A Triple Output DC POWER SUPPLY...

Page 2: ...Some circuits retain high voltage long after the equipment is turned off 2 Use only a polarized 3 wire ac outlet This assures that the power supply chassis case and ground terminal are connected to a...

Page 3: ...Instruction Manual For Model 1671A Triple Output DC POWER SUPPLY B K Precision Corporation 22820 Savi Ranch Parkway Yorba Linda California 92887...

Page 4: ......

Page 5: ...Operation 7 Variable Voltage Output 7 Typical Constant Voltage Output 8 Setting Current Limit 8 Typical Constant Current Operation 8 Page Constant Voltage Current Characteristics 9 12 Vdc Output 9 5 V...

Page 6: ...ii...

Page 7: ...mps each One common application for these power supply is powering of circuit boards while troubleshooting Many circuit boards require two or three input voltages with the most common values being 5 v...

Page 8: ...LINE REGULATION 108 TO 132 VAC 0 05 10 mV RIPPLE AND NOISE 5 mV rms CONSTANT CURRENT MODE LOAD REGULATION 0 4 10 mA LINE REGULATION 108 TO 132 VAC 0 4 10 mA RIPPLE AND NOISE 10 mA rms PROTECTION Curr...

Page 9: ...N 1 RIPPLE AND NOISE 5 mV rms PROTECTION Short circuit protection thermal overload protection OUTPUT NO 3 VOLTAGE Fixed 5 VDC 5 CURRENT 0 to 500 mA continuous POLARITY Positive or Negative CONNECTORS...

Page 10: ...fluctuation up to 10 of normal voltage DIMENSIONS H x W x D 4 9 x 8 5 x 11 5 124 x 216 x 292mm WEIGHT approx 14 3 lbs 6 5 kg ACCESSORIES SUPPLIED Instruction Manual Spare fuse OPTIONAL ACCESSORIES Po...

Page 11: ...le supply Read value on V Meter 6 A Meter Indicates output current of variable supply 7 V Meter Indicates output voltage of variable supply 8 OUTPUT Terminal Red Positive polarity output terminal 9 OU...

Page 12: ...CONTROLS AND INDICATORS Figure 1 Front Panel Controls and Indicators Model 1671A Figure 2 Rear Panel Model 1671A 6 14 15 16...

Page 13: ...vent internal heat build up Typically a two inch space at the sides as well as a six inch space at the top and rear of the power supply is adequate DO NOT block the fan opening at the rear of the powe...

Page 14: ...OLTAGE control will not increase the output current Setting Current Limit 1 Determine the maximum safe current for the device to be powered 2 Rotate the VOLTAGE control away from zero until some low v...

Page 15: ...ant as the lad increases up until the point where the preset current limit is reached At that point the output current becomes constant and the output voltage drops in proportion to further increases...

Page 16: ...outputs are fully isolated from ground and each other thus each output may be connected for the either positive or negative polarity A typical example of a triple output application would be powering...

Page 17: ...11 Figure 4 Example of Triple Output Hook up for 5V 12V and 12V Figure 5 Connecting Outputs in Series for Variable 17 to 47 volt output OPERATING INSTRUCTIONS...

Page 18: ...n fuse then replace only with a fuse of the correct rating The fuse is located on the rear panel see Fig 2 LINE VOLTAGE 115V 230V FUSE VALUE F4AL250V F2AL250V INSTRUMENT REPAIR SERVICE Because of the...

Page 19: ...ccount must include payment in the form of a money order or credit card For the most current repair charges please visit www bkprecision com and click on service repair Return all merchandise to B K P...

Page 20: ...n form online at www bkprecision com within fifteen 15 days of purchase Exclusions This warranty does not apply in the event of misuse or abuse of the product or as a result of unauthorized alteration...

Page 21: ...nsformer etc any time the equipment is connected to an ac outlet even if the equipment is turned off 7 B K Precision products are not authorized for use in any application involving direct contact bet...

Page 22: ...B K Precision Corporation 22820 Savi Ranch Parkway Yorba Linda California 92887 www bkprecision com 2016 B K Precision Corporation Printed in China 122116...

Page 23: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information B K Precision 1671A 1671A NIST W DATA...

Reviews: