background image

 

11 

OPERATING INSTRUCTIONS 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

CURRENT LIMITING 

 

Overload  (Foldback)  current  limiting  gives  protection  against 

excessive  overload  and  short  circuit  output.  When  an  overload 
(foldback) condition exists, the unit drops out of voltage regulation and 
the  OVERLOAD  indicator  will  be  illuminated.  The  foldback 
characteristic  shown  in  the  graph  in  Fig.  3  takes  effect  before  the 
primary  fuse  blows,  dropping  the  output  voltage  and  current  in 
proportion  to  the  degree  of  overload.  If  the  output  is  short-circuited 
(maximum  overload  condition),  the  output  current  drops  below  its 
rating at 3V. Monitoring the output voltage and current will detect any 
such overload conditions. 
 

CONNECTING TWO SUPPLIES IN SERIES  
(Refer to Fig. 4) 

 

The  outputs  of  two  supplies  may  be  connected  in  series  to 

provide  a  variable  6-to-28  volts  output.  The  maximum  output 
current  will  remain  at  12  amps.  See  Fig.  4  for  the  connection 
scheme. 

 

The voltage is controlled by both VOLTAGE controls and is 

equal  to  the  sum  of  the  two  V  meter  readings.  Adjust  voltage 
so that each power supply provides about half the total voltage. 
 

CONNECTING TWO SUPPLIES IN PARALLEL  
(Refer to Fig. 5) 

 

The  outputs  of  two  Model  1686  power  supplies  may  be 

connected  in  parallel  to  double  the  current  capacity  to  24 
amperes.  The  output  voltage  remains  at  3-to-14  volts  output. 
See Fig. 5 for the connection scheme. 

 
The  voltage  level of  both VOLTAGE  controls  should be  set 

simultaneously  to  the  same  value.  Fine  adjust  the  VOLTAGE 
controls  for  equal  readings  on  the  A  meters.  This  will  allow 
each  power  supply  to  provide  one-half  of  the  total  current. 
Current  will  be  equal  to  the  sum  of  both  A  meters.  Current 
limiting  resistors  are  not  required  since  hook-up  wire 
resistance will provide sufficient isolation. 

 

Summary of Contents for 1686A

Page 1: ...1 INSTRUCTION MANUAL MODEL 1686A 3 to 14 VOLT DC POWER SUPPLY...

Page 2: ...hazard a If the equipment under test is the hot chassis type a serious shock hazard exists unless the equipment is unplugged just turning off the equipment does not remove the hazard or the precaution...

Page 3: ...3 Instruction Manual for MODEL 1686A 3 to 14 VOLT DC POWER SUPPLY 22820 Savi Ranch Parkway Yorba Linda California 92887...

Page 4: ...Power Supply Hook up and Operation 9 Considerations 10 Current Limiting 11 Connecting Two Supplies in Series 11 Connecting Two Supplies in Parallel 11 page MAINTENANCE 14 Fuse Replacement 14 Line Vol...

Page 5: ...y radios such as CB transceivers VHF UHF commercial equipment marine car telephone and 2 meter transceivers The power supply utilizes thermostatically controlled fan cooling for improved heat dissipat...

Page 6: ...voltage Short Circuit METERING Voltmeter Range Accuracy 0 to 20V 7 F S Ammeter Range Accuracy 0 to 20A 7 F S AC Input 115 230 VAC 10 50 60Hz POWER CONSUMPTION 400 W TEMPERATURE RANGE HUMIDITY Operatio...

Page 7: ...eed 2 amperes 10 Line Cord 11 Fuse 12 Fan 1 POWER Switch Turns power supply on and off Power on indicated by pilot lamp above switch 2 Power ON light Lights when power is turned on 3 OVERLOAD Indicato...

Page 8: ...8 CONTROLS AND INDICATORS Figure 1 Front Panel Controls and Indicators Model 1686A Figure 2 Rear Panel...

Page 9: ...Observe all TEST INSTRUMENT SAFETY precautions listed in the front of this manual EQUIPMENT PROTECTION PRECAUTIONS CAUTION The following precautions will help avoid damage to the power supply 1 Avoid...

Page 10: ...nugly to assure low resistance 2 Connect the red OUTPUT terminal of the power supply to the positive polarity input of the equipment being powered 3 Connect the black OUTPUT terminal of the power supp...

Page 11: ...provide a variable 6 to 28 volts output The maximum output current will remain at 12 amps See Fig 4 for the connection scheme The voltage is controlled by both VOLTAGE controls and is equal to the sum...

Page 12: ...12 OPERATING INSTRUCTIONS Figure 4 Connecting Two Power Supplies in Series for a 6 to 28 Volt Output...

Page 13: ...13 OPERATING INSTRUCTIONS Figure 5 Connecting Two Power Supplies in Parallel for 3 to 14 Volt Output at Double Amperage...

Page 14: ...e bottom of the chassis To convert to a different line voltage perform the following procedure 1 Make sure the power cord is unplugged 2 Turn the unit over bottom up and reset the LINE VOLTAGE SELECT...

Page 15: ...14 50 0 10 volts on the multimeter 4 Set the power supply front panel VOLTAGE control for a reading of 14 00 0 10 volts on the multimeter 5 Adjust Trimmer VR4 so that the meter pointer on the V meter...

Page 16: ...tive load for a reading of 15 amps on the unit s A meter scale 8 Adjustable Trimmer VR2 clockwise unit the output voltage read on the multimeter drops by 0 05 to 0 20 V INSTRUMENT REPAIR SERVICE Becau...

Page 17: ...ccount must include payment in the form of a money order or credit card For the most current repair charges please visit www bkprecision com and click on service repair Return all merchandise to B K P...

Page 18: ...nstrument via our website www bkprecision com Exclusions This warranty does not apply in the event of misuse or abuse of the product or as a result of unauthorized alterations or repairs The warranty...

Page 19: ...et is removed for servicing a serious shock hazard exists if the chassis is touched Not only does this present a dangerous shock hazard but damage to test instruments or the equipment under test may r...

Page 20: ...20 B K Precision Corporation 22820 Savi Ranch Parkway Yorba Linda California 92887 www bkprecision com 2014 B K Precision Corporation 481 370 9 001 Printed in China V043014...

Reviews: