background image

                        TECHNICAL DATA OF PRODUCT                                         

   

INSTALLATION AND USERS GUIDE   

DESCRIPTION AND USING

Switching power supply JSD-300-XXX/DIN2_CH_ODP is intended for power supply of controlling and monitoring  
electronic devices in telecommunication and industrial area in environment with no danger of explosion. The 

power supply is equipped by remote control and automatic  report of the measured parameters.  The power 
supply contain a input power factor correction.

The power supply is placed in a metal box with possibility a DIN35 rail mounting. Input and output connection is  
made by screw terminals. Output is SELV type. Operation of the power supply is indicated by green LED and  

signalized by relay contacts. Charger contains battery Low Voltage Disconnector (LVD).  

TECHNICAL SPECIFICATIONS

Input voltage

  

180-260 VAC

Frequency

47-63 Hz

Input current

    

1,7 A at 230 VAC

Power Factor

0,99

Output voltage and current

see label

Battery output current limit

see label

Disconnecting voltage

41,5 V+/-0,5 V for 545 version; 21 V+/-0,5 V for 275 version; 

10,5 V+/-0,5 V for 138 version

Dielectric strength 

4000 VAC input-output, 1500 VAC input-cover

Isolating resistivity

more than 50 MΩ

Potentional free relay conector ALARM
Maximal contact current 

1 A

Maximal switching voltage

125 VAC, 60 VDC

Maximal switchnig load

62,5 VA, 30 W

Dielectrical strenght coil-contact

500 VAC

ENVIROMENTAL CONDITIONS 

Operating temperature

-20 to 50 ºC

Humidity (non condensing)

10 to 90% RH

Altitude

up to 2000 m above sea level

Environment

without danger of explosion

IP protection

IP20

Weight

1,4 kg

Material of the cover

Al + FeZn

Dimensions

155 x 175 x 70 mm (D x H x W)

Class of device

I.

Internal fuse

T6,3A/250V

TECHNICAL STANDARDS

Safety

 EN 60950-1

EMC

 EN 61000-6-1 ed. 2

 EN 61000-6-3 ed. 2

PACKING AND STORAGE

The product is delivered in a box made of white cardboard. Installation and user guide is enclosed to the supply.  

The product is to be stocked in temperatures from -20 to 70 °C, in relative humidity to 95 %, in areas where can 
be no ship is  sweating on the products.  The product  cannot  be striked, exposed to mechanical  shock  and 

injurious gases.

INSTRUCTIONS FOR INSTALLATION

Connecting of the device can be made only by qualified persons. Screw clamps  allows to connect wires of 
crosscut from 0,5 to 2,5 mm

2

. The operating position of the power supply is  vertical. The product is intended for 

installation to an area with no danger of explosion.

CONNECTION

Battery

  terminals are connect through internal Low 

Voltage   Disconnector.   At   the   voltage   decrease 
under disconnecting level is battery disconnect from 
the output. Is necessary to ensure external battery 
protection (fuse T20A is recommended).

Battery   output   is   equipped   by   a   charging   current 
limiter. Load output is not limited. Is recommended 
to   ensure   output   protection   (fuse   T16A   is 
maximum).   The   power   supply   has   IU   charging 
characteristic.
 
Terminals  

COM

,  

NO  

are   terminals   of   the 

signalization relay – signal 

PowerOK

 (power supply 

under   operation   -   terminals  

COM

  and  

NO 

connected.

Terminals   T+   and   T-   are   intend   for   temperature 
sensor.

By pushing BATTERY CONNECT button is possible 
to   start   battery   backup   after   replacing   discharged 
battery for fully charged one.

       
SETTING IN OPERATION

The Supply is intended for permanent operating, has a T6,3A/250V fuse on input and there is no need to have it 
secondary secured. Terminal of supply voltage must be possible to switch off. After wiring output terminals and 

connecting input voltage is the Supply ready for operating.

SERVICE AND REPAIRING

The product does not require servicing or maintenance.
The product is to be repaired by the producer. Products for repairing are to be send in a box that protects it from  

damage during delivering.

DURABILITY

Minimum effective life of the product is 50 000 hours.

 