www.bkte.pl
AL200 swinghandle manual
13
5.2
Electrical opening
Electric opening is made by shorting the CTRL input to the GND or +12V potential. If the CTRL input is not connected anywhere, then the
swinghandle remains closed.
CTRL input state
Swinghandle lock status
CTRL input not
connected
Lock is closed
CTRL input not
connected to
GND or +12V
Lock is open
5.3
Handle position indication
The device has an optical sensor of the handle position, thanks to which this information can be transferred to an external access control system.
The state of the STATUS output corresponds to the position of the handle. The STATUS output has overload protection. If the current through
the transistor is greater than 50mA, the output will be turned off. The STATUS output will return to normal operation after removing the overload
and changing the position of the handle.
Position of the handle
STATUS output state
Handle closed
STATUS output inactive (NPN
transistor is OFF)
Handle open
STATUS output active (NPN
transistor is ON)
or