background image

 

www.bkte.pl

 

 

AL200 swinghandle manual 

14 

 

5.4

 

LED signalling 

The swinghandle has a three-color LED indicating the status of its operation. 

LED state 

Swinghandle working state 

 

 

Orange is on 

The device is in programming mode 

 

Orange blinking (1Hz) 

The device is booting (within 3 seconds after connecting the power) 
or firmware error (if it blinks for more than 3 seconds) 

 

Red is on 

The electric lock of the device is closed (no control on the CTRL input) 

 

Red blinking (1Hz) 

The electric lock of the device is closed (no control on the CTRL input), but the 
handle is open. 

 

Green is on 

The electric lock of the handle is open (controlled on the CTRL input) 

 
 

6

 

Accessories  

Product 

Description 

Part number 

 

AW285 - AL200 swinghandle 8-wire connection cable, length 5m; connectors: 1-plug, 
2-ferrules 

122AW002850 

 

AW240 - AL200 swinghandle 4-wire connection cable, length 0.5m; connectors: 1-plug, 
2-ferrules 

122AW002400 

 

AR221 - AL200 swinghandle Unique 125kHz card reader (RS-H3-05-M12) 

122AR002210 

 

EMC-1 - UNIQUE EM 125 kHz thin proximity card 

122AA101004 

 

 

GST18A12-P1J - Power supply 18W 12VDC 1.5A; AC socket C14; DC plug 5.5/2.1; no AC cord 

122AA100015 

 

BKT AC power cord - socket IEC 320 C13 10A, plug DIN 49441(unischuko) 16A, 3 x 1,0 mm2 
black  2m 

11480784.2 

 

Cable with DC 5.5/2.1 inlet; straight; 0.5mm2; black; 3m 

122AA100016 

LED 

Summary of Contents for AL200

Page 1: ...arter Poland Lochowska 69 Str 86 005 Biale Blota Phone 48 52 36 36 750 e mail export bkte pl 2022 BKT Elektronik www bkte pl BKT AL200 Electronic locking monitoring swinghandle with mechanical override user manual version 3 ...

Page 2: ... out dimensions 6 3 2 4 Cogwheel dimensions 6 3 2 5 Cam dimensions 6 3 3 Single point assembly 7 3 4 Multi point assembly 7 3 5 Connectors 8 4 Standalone mode 9 4 1 Connection 9 4 2 Master card programming 10 4 3 Adding new user card 11 4 4 Removing user card 11 4 5 Removing all user cards 11 4 6 LED signalling 12 5 Operation mode in the access control system 12 5 1 Connection 12 5 2 Electrical op...

Page 3: ...key override Available inserts for the master key system For use with indoor cabinets Installation in a standard 150x25mm cut out Can be installed in a single and multi point locking system requires additional elements cam or cogwheel mechanism which should be ordered separately 1 3 Working modes In the current version manufacturing date from Q2 2022 see chapter 6 Accessories the handle can work i...

Page 4: ...ompliance with standards EN 61000 4 2 2009 Electrostatic discharge immunity test EN 61000 4 3 2007 Radiated radio frequency electromagnetic field immunity test EN 61000 4 4 2012 Electrical fast transient burst immunity test EN 61000 4 5 2014 Surge immunity test EN 61000 4 6 2014 Immunity to conducted disturbances inducted by radio frequency fields EN 61000 6 4 2007 A1 2011 Electromagnetic compatib...

Page 5: ...mounting elements Additional mounting elements dedicated to the respective cabinet must be ordered separately 3 1 Package Contents Packaging AL200 swinhandle Fastening element with screw Quick Start Guide 3 2 Dimensions 3 2 1 Swinghandle dimensions 3 2 2 AR221 reader dimensions Mounting hole Make a hole in the door at such a distance from the swinghandle that the length of the reader cable will en...

Page 6: ...www bkte pl AL200 swinghandle manual 6 3 2 3 Cut out dimensions 3 2 4 Cogwheel dimensions 3 2 5 Cam dimensions or ...

Page 7: ... 122AM002024 Cam bolt M6x8 7 122AM002100 Cam h 0mm locking height H 18mm 3 4 Multi point assembly 1 122AL002000 AL200 swinghandle 2 Fastening element with screw 3 122AM002001 Cogwheel mechanism 4 122AM002002 Cogwheel mechanism adapter 5 122AM002003 Bushing for cam 6 122AM002004 Cam bolt M6x16 7 122AM002005 Cogwheel screw F4 1x22 8 122AM002006 Cam h 0mm locking height H 24mm 1 2 4 3 5 7 6 1 2 4 3 6...

Page 8: ...ng the swinghandle from an external system Opening the handle CTRL shorted to GND or 12V Closing the handle CTRL not connected 5 SENSOR Door sensor input for the future use Do not connect 6 GND GND for the door sensor for the future use Do not connect 7 CANL CAN bus interface CANL for the future use Do not connect 8 CANH CAN bus interface CANH for the future use Do not connect 4 pin socket type 53...

Page 9: ... readers in the cabinet Devices used see chapter 6 Accessories 1 AL200 swinghandle 122AL002000 2 AR221 card reader 122AR002210 3 Any reader with Wiegand interface 4 AW240 cable 122AW002400 5 AW285 cable 122AW002850 6 Power supply 12V 1 5A 122AA100015 7 DC power cord 122AA100016 8 AC power cord 11480784 2 9 Junction box 122AA100006 Connection diagram of the handle with the reader in standalone mode...

Page 10: ...ntil the green LED on the handle lights up continuously 5 Close the handle when the green LED is on then the green LED will start blinking 2Hz The green LED is on for 5 seconds If the handle is not closed within this time it will return to normal operation 6 Touch the prepared master card to the reader when the green LED is blinking The green LED flashes for 5 seconds Correct programming of the us...

Page 11: ...the user card memory is full You must then remove a single card see chapter 4 4 Removing user card or delete all saved cards see chapter 4 5 Removing all user cards 4 4 Removing user card The procedure removes a single user card from memory The removed card will not open the handle Action State after performing the action 1 Check if the user card is already saved in the memory Touching the written...

Page 12: ...andle is open for 2 seconds after touching the authorized user card 5 Operation mode in the access control system The handle can work as only a cabinet door opening mechanism in a larger access control system It can cooperate with any access control system eg BKT ACS or any other company The handle should be connected to the access controller that controls its operation The handle can transmit inf...

Page 13: ...optical sensor of the handle position thanks to which this information can be transferred to an external access control system The state of the STATUS output corresponds to the position of the handle The STATUS output has overload protection If the current through the transistor is greater than 50mA the output will be turned off The STATUS output will return to normal operation after removing the ...

Page 14: ... handle is open Green is on The electric lock of the handle is open controlled on the CTRL input 6 Accessories Product Description Part number AW285 AL200 swinghandle 8 wire connection cable length 5m connectors 1 plug 2 ferrules 122AW002850 AW240 AL200 swinghandle 4 wire connection cable length 0 5m connectors 1 plug 2 ferrules 122AW002400 AR221 AL200 swinghandle Unique 125kHz card reader RS H3 0...

Page 15: ... mount black IP55 122AA100006 7 Document revisions Version Changes Date 1 Initial version March 2021 2 Updated 3 2 3 3 and 3 4 July 2021 3 Support for rfid readers has been added for handles manufactured from 2Q2022 The device manufacturing date can be checked on the sticker February 2022 ...

Reviews: