CHAPTER 4: WEB GRAPHICAL USER INTERFACE (GUI)
4.3 SENSORS PAGE
FIGURE 4-44. SENSORS PAGE
On this page, you can view all sensors connected to the unit per port.
Non-connected sensors will be also displayed, until you re-attach or manually remove them from the configuration.
FIGURE 4-45. MAIN BOARD SCREEN
You could also rename the unit’s Main board by clicking on the pencil icon.
NOTE: The maximum supported cable length to use with EME1TS/EME1THS:
Maximum extension cable length from the AlertWerks Gateway sensor port to the EME1TS/EME1THS using CAT5 =
28 Feet
Maximum extension cable length from the AlertWerks Gateway sensor port to the EME1TS/EME1THS using CAT5e
& CAT6 = 60 Feet
CAUTION: If you’re using analog pins on the sensor ports (with manually on-lined DCV sensors, and pin 7 of the RJ-
45 connector) make sure that the voltage doesn’t exceed 3 Volts. Otherwise, you can damage the unit!