background image

4

CONTROLS AND INDICATORS

LEDs Display:
The Powered Chassis features two LEDs on the left front of the chassis, these
LEDs display the status of the two power supplies.

Function

Color/State

Description

Top LED

Yellow / ON

Power OK in right power supply

Bottom LED

Yellow / ON

Power OK in left power supply

Note: Left/right direction as viewed from the front of the chassis.

SITE PREPARATION REQUIREMENTS

1. Power: Assure the 48VDC power can supply 3A of current.
2. The operating temperature of this equipment is 0-40 degrees C. If installed

in a closed or multiunit rack assembly, the operating ambient temperature
of the rack must not exceed the maximum rated 40 degrees C temperature.

3. Installation of the equipment should be such that the air flow in the front and

back of the unit is not compromised or restricted.

4. Never use this equipment to carry any weight except its own, never use it as

a shelf to support weight of other equipment.

5. Installing this equipment into a rack in such a way as to make it unstable

may cause injury or death. Always make sure that the rack you are installing
this equipment into is properly secure, stable, balanced and designed to
carry the weight and weight distribution of this equipment.

6. When rack-mounting this equipment, the rack should be appropriately

earth-grounded.

7. This equipment requires 48 VDC / 3.0 Amps per power supply. Appropriate

overloading protection should be provided on all DC power source outlets
utilized.

8. Wiring methods used for the connection of the equipment to the primary

power supply shall be in accordance with the National Electrical Code, ANSI/
NFPA 70, and the Canadian Electrical Code, Part I, C22.1.

UNPACKING

a. Visual Inspection: Inspect equipment in order to detect any physical damage.

Any evidence of damage should be noted and reported immediately.

INVENTORY

Review contents, the following items should be included:

(1)

FlexPoint Powered Chassis unit.

(2)

Power supplies (2 for model LMC200A-2PS-DC, 1 for model LMC200A-DC).

(14) L shape tabs.
(14) Screws
(1)

User’s manual (this document).

Please note any missing items or discrepancies and report them immediately.

INSTALLATION

WARNING:

 Only a DC power source that complies with safety extra low

voltage (SLEV) requirements can be connected to the DC-input power supply.

Tools and Equipment Required:

Flat-head screwdriver (not supplied)
Wire cutter/stripper (not supplied)
Three-conductor 14 AWG copper power cable (recommended; not supplied)

Preparation:

Assure that the FlexPoint Chassis is physically installed in accordance with
the Site Preparation Requirements outlined earlier in this document.

WARNING REGARDING EARTHING GROUND:

a) This equipment shall be connected to the DC supply system earthing

electrode conductor or to a bonding jumper from an earthing terminal bar
or bus to which the DC supply system earthing electrode is connected.

b) This equipment shall be located in the same immediate area (such as,

adjacent cabinets) as any other equipment that has a connection
between the earthed conductor of the same DC supply circuit and the
earthing conductor, and also the point of earthing of the DC system. The
DC system shall not be earthed elswere.

c) The DC supply source is to be located within the same premises as this

equipment.

d) There shall be no switching or disconnecting devices in the earthed circuit

conductor between the DC source and the earthing electrode conductor.

5

Summary of Contents for FlexPoint LMC200A-2PS-DC

Page 1: ...ont of the chassis indicating that the power has been restored SPECIFICATION Indicators Power ON LED 2 Yellow power applied Dimensions Weight W 19 0 xD 7 0 xH 3 5 9 lb Power 48VDC 3 0 Amps for model 4386 2ea 48VDC 3 0 Amps for model 4385 Environmental Temperature 0 to 40 degrees C Humidity 0 90 non condensing JULY 2001 LMC200A 2PS DC LMC200A DC PSFP20 DC CUSTOMER SUPPORT INFORMATION Order toll fre...

Page 2: ...t in the Radio Interference Regulation of the Canadian Department of Communications Le présent appareil numérique n émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numéirques de las classe A prescrites dans le Règlement sur le brouillage radioélectrique publié par le ministère des Communications du Canada NORMAS OFICIALES MEXICANAS NOM ELECTRICAL SAFETY STATEMEN...

Page 3: ...to the FlexPoint Chassis by fastening the stripped ends to the 48VDC connector WARNING Note the wire colors used for making the positive negative and ground connections Use the same color assignment for the connection at the circuit breaker 7 Connect the power cable to the circuit breaker and switch the circuit breaker ON 8 Turn both FlexPoint Chassis power supply switches on and check the power L...

Page 4: ...ctrical Code ANSI NFPA 70 and the Canadian Electrical Code Part I C22 1 UNPACKING a Visual Inspection Inspect equipment in order to detect any physical damage Any evidence of damage should be noted and reported immediately INVENTORY Review contents the following items should be included 1 FlexPoint Powered Chassis unit 2 Power supplies 2 for model LMC200A 2PS DC 1 for model LMC200A DC 14 L shape t...

Reviews: