Laundry Installation and Setup Guide
11
L C 3 0 0 0 L
A U N D R Y
R
E A D E R
I
N S T A L L A T I O N
Preparing the Enclosure
Before mounting the enclosure, remove all
necessary knockouts to route wires and/or attach
conduits.
Remove only the knockouts required for your
installation.
• All knockouts are dimensioned for 1/2” conduit
fittings.
Flush-mounted enclosure: If installing a wired
laundry center, route machine wires through the
“3x3” cutout.
Surface-mounted enclosure: Remove conduit
knockouts, located on the top and bottom of the
enclosure, to route wire to the laundry machines.
• The enclosure provides two knockouts, in the upper
right, for power.
Flush-mounted enclosure: Remove the knockout
on the back side.
Surface-mounted enclosure: Remove the
knockout on the top.
Maintain 1/4" separation from AC wiring to other
wiring.
Install the LC3000 Enclosure
1
Inside the LC3000, remove the power supply cover
to access the upper right mounting hole.
Protect power supply from debris while mounting the
enclosure.
2
Secure the enclosure to a wall using hardware
appropriate for the wall material.
Mounting holes accept up to 1/4” hardware.
Disconnect external AC power when installing any
wiring.
Figure 4: Power Supply Installation
ACMAIN
Mount
Mount
Flush-mount
“3x3” cutout
Figure 3: Knockout areas
Surface-mount knockouts
AC Main Power
Line
Ground
Neutral