The reader must be configured by the administrator to operate in Wiegand mode. In addition to the wiring
shown above, the reader can also be connected to a network using the RJ-45 connector. This provides a
means of getting software updates for the Android OS.
Attendance Reader
When using the WR5000 as an attendance reader, the device must be connected to a network.
The WR5000 can be powered using an external power supply, or a Power Over Ethernet (POE) switch. If
using an external power supply, the power supply must have a regulated output of +12 Volts DC. If using
POE, a CAT-5 cable must be connected between the POE switch and the RJ-45 connector on the WR5000
(cable length must not exceed 100 meters).
WARNING
: When using a POE switch to power the WR5000, both the POE switch and
WR5000 must be installed within the same building or structure.
When using an external supply, wire the reader as shown in
Table 1-4:
Table 1-3: Wiegand Connection Points
WR5000
Terminal Block
Signal Name
Third-Party Controller connections
TB1-1
V+
Connect to regulated Power Supply (+6V to +24V)
TB1-2
GND
Connect to Ground
TB1-3
D0/DAT
Connect to Wiegand D0 input
TB1-4
D1/CLK
Connect to Wiegand D1 input
TB2-1
GLED
Connect to Green LED output
TB2-2
RLED
Connect to Red LED output
TB2-3
BEEPER
Connect to Beeper output
TB2-4
TAMPER
Connect to Tamper Input
Table 1-4: Power Supply Wiring
WR5000
Terminal Block
Signal Name
External Power supply
TB1-1
V+
Connect to regulated Power Supply (+6V to +24V)
TB1-2
GND
Connect to Ground