background image

701-B00    page 4/12 

INSTALLATION 

PUMP RELIEF VALVE AND BYPASS VALVE 

NOTICE: 

The pump internal relief valve is designed to protect the 
pump from excessive pressure and must not be used as 
a system pressure control valve. 

For ALL liquefied gas applications, install an external bypass 
valve, and any necessary piping, back to the tank. DO NOT 
pipe the bypass valve back to the intake line. The setting on 
the external bypass valve must be at least 25 psi (1.7 bar) 
lower than the pump internal relief valve setting. The valve 
and piping must be of adequate size to accommodate the full 
flow from the pump when the discharge line is closed. The 
non-adjustable pump internal relief valve is factory set a 
approximately at 150 PSI (10.3 bar). 

Refer to Blackmer Bypass Valve Installation and Maintenance 
Instructions for bypass valve settings and adjustments. 

 

Figure3 – Bypass Valve Mounting 

 
 

CHECK VALVES 

The use of check valves or foot valves in the supply tank is 
not recommended with self-priming, positive displacement 
pumps.  

If the possibility of liquid backflow exists when the pump is off, 
a check valve in the pump discharge piping is recommended 
because the pump can motor in the reverse rotation and 
create undue stress on all attached components.  Never start 
a pump when it is rotating in the reverse rotation as the added 
starting torque can damage the pump and related equipment. 

 
 

PUMP MOUNTING 

Stationary Pumps 

A solid foundation reduces noise and vibration, and will 
improve pump performance. On permanent installations it is 
recommended the pumping unit be secured by anchor bolts 
as shown in Figure 4. This arrangement allows for slight 
shifting of position to accommodate alignment with the 
mounting holes in the base plate. 

For new foundations, it is suggested that the anchor bolts be 
set in concrete. When pumps are to be located on existing 
concrete floors, holes should be drilled into the concrete to 
hold the anchor bolts. 

When installing units built on channel or structural steel type 
bases, use care to avoid twisting the base out of shape when 
anchor bolts are tightened. Shims should be used under the 
edges of the base prior to tightening of the anchor bolts to 
prevent distortion. 

Truck Mounted Pumps 

CRL 

pump models can be bolted to the truck frame or on a 

saddle hung below the frame, and MUST be adequately 
supported.

 

 
 

PUMP DRIVES 

Stationary pumps are typically driven via a V-belt drive or via 
a flexible coupling and gear reducer. Truck mounted pumps 
are typically driven via the truck’s PTO drive or via a hydraulic 
motor. 
 
 

COUPLING ALIGNMENT 

The pump must be directly coupled to a gear and/or driver 
with a flexible coupling.  Verify coupling alignment after 
installation of new or rebuilt pumps.  Both angular and parallel 
coupling alignment MUST be maintained between the pump, 
gear, motor, etc. in accordance with manufacturer’s 
instructions.  See Figure 5. 
1.  Parallel alignment:  The use of a laser alignment tool or 

dial indicator is preferred.  If a laser alignment tool or dial 
indicator is not available, use a straightedge.  Turn both 
shafts by hand, checking the reading through one 
complete revolution.  Maximum offset should be less  
than .005" (.127 mm). 

2.  Angular alignment:  Insert a feeler gauge between the 

coupling halves.  Check the spacing at 90° increments 
around the coupling (four checkpoints).  Maximum 
variation should not exceed .005" (.127 mm).  Some 
laser alignment tools will check angular alignment as 
well. 

3.  Replace the coupling guards after setting alignment. 

 

Figure 5 – Coupling Alignment 

 

Figure 4 - Pipe Type 

Anchor Bolt Box

 

Summary of Contents for CRL2

Page 1: ...mer Service SAFETY DATA This is a SAFETY ALERT SYMBOL When you see this symbol on the product or in the manual look for one of the following signal words and be alert to the potential for personal inj...

Page 2: ...nd chock wheels before performing service can cause severe personal injury or property damage Do not operate without guard in place Operation without guards in place can cause serious personal injury...

Page 3: ...tions 1 Locate the pump as near as possible to the source of supply to avoid excessive inlet pipe friction 2 The inlet line should be at least as large as the intake port on the pump It should slope d...

Page 4: ...odate alignment with the mounting holes in the base plate For new foundations it is suggested that the anchor bolts be set in concrete When pumps are to be located on existing concrete floors holes sh...

Page 5: ...82 and the belt guard brace 182A to the unit base 32 Do not operate without guard in place Operation without guards in place can cause serious personal injury major property damage or death 9 Check th...

Page 6: ...cation every three months at minimum Refer to the Lubrication section of this manual Hydraulically driven units MUST contain speed control devices to prevent pump speeds above the maximum RPM specific...

Page 7: ...3 1 0 bar less than the external bypass valve setting Pump speeds which result in higher pressures nearing the valve setting forces the liquid to recirculate creating excessive wear on the pump and eq...

Page 8: ...ice can cause severe personal injury or property damage NOTICE Maintenance shall be performed by qualified technicians only Following the appropriate procedures and warnings as presented in this manua...

Page 9: ...and replace as required c Repeat steps a and b on the opposite shaft end 6 Remove the head capscrews 21 and carefully pry the head 20 away from the casing 12 7 Slide the head 20 off the shaft The hea...

Page 10: ...to the rotor slots with the rounded edges outward and the vane relief grooves facing TOWARDS the direction of rotation See Figure 10 c After the bottom vanes and push rods are installed insert the rot...

Page 11: ...24 Then using a spanner wrench tighten the nut the width of one lockwasher tang Tighten just past the desired tang then back off the nut to align the tang with the locknut slot Secure the nut by bendi...

Page 12: ...erly anchored piping 8 Bent shaft or drive coupling misaligned 9 Excessively worn rotor 10 Malfunctioning valve in the system 11 Relief valve setting too low 12 Liner installed backwards 13 Damaged va...

Reviews: