background image

102-A00     page 3/16 

INSTALLATION 

 

NOTICE: 

Blackmer  power  pumps  must  only  be  installed  in 
systems designed by qualified engineering personnel.  
System  design  must  conform  with  all  applicable 
regulations  and  codes  and  provide  warning  of  all 
system hazards. 

 

 

  Install, ground and wire to local and 

National Electrical Code requirements. 

  Install an all-leg disconnect switch near 

the unit motor. 

  Disconnect and lockout electrical power 

before installation or service 

 

Electrical supply MUST match motor 
nameplate specifications. 

 

Hazardous voltage. 

Can shock, burn or 

cause death. 

  Motors equipped with thermal protection automatically 

disconnect motor electrical circuit when overload exists.  
Motor can start unexpectedly and without warning. 

 

 
 

PRE-INSTALLATION CLEANING 

NOTICE: 

New pumps contain residual test fluid and rust inhibitor.  
If necessary, flush pump prior to use. 

Foreign matter entering the pump WILL cause extensive 
damage.  The supply tank and intake piping MUST be 
cleaned and flushed prior to pump installation and operation. 
 
 

LOCATION AND PIPING 

An improperly designed piping system or improper unit 
installation WILL significantly reduce pump performance and 
life.  Blackmer recommends the following piping system 
layout and unit installation. 

1.  To minimize intake losses, locate the pump as close as 

possible to the source of supply. 

2.  Intake piping and fittings MUST be at least as large in 

diameter as the pump intake connection. 

3.  Minimize the number of intake line fittings (valves, 

elbows, etc.) and piping turns or bends.  When used, 
intake fittings must be located at least 5 - 10 pipe 
diameters from the pump intake. 

4.  Install an intake strainer 5 - 10 pipe diameters from the 

pump intake.  For viscosities less than 1000 SSU, the 
strainer should have a net open area of at least four 
times the area of the intake pipe.  For viscosities greater 
than1000 SSU, consult the strainer manufacturer 
instructions. 

5.  Strainers must be cleaned regularly to avoid pump 

starvation. 

6.  Intake and discharge piping MUST be free of all leaks. 
7.  Expansion joints, placed at least 36" (0.9m) from the 

pump, will compensate for expansion and contraction of 
the pipes. Contact the flexible connector/hose 
manufacturer for required maintenance/care and design 
assistance in their use. 

8.  Install pressure gauges in the NPT ports provided in the 

pump casing to check pump at start up. 

9.  ALL piping and fittings MUST be properly supported to 

prevent any piping loads from being placed on the pump. 

10.  Check alignment of pipes to pump to avoid strains which 

might later cause misalignment.  See Figure 1.  Unbolt 
flanges or break union joints.  Pipes should not spring 
away or drop down.  After pump has been in operation 
for a week or two, completely recheck alignment. 

 

Figure 1 

11.  When pumping liquids at elevated temperature, 

provisions should be made to compensate for expansion 
and contraction of the pipes, especially when long pipe 
lines are necessary.  Steel pipe expands approximately 
3/4” (1.9 cm) per 100 feet (30.49 m) per 100°F (37.8°C) 
rise in temperature. 

 
 

PUMP MOUNTING 

It is recommended the unit be permanently mounted by 
securing the base plate with adequately sized anchor bolts to 
a level concrete floor following recommended industry 
standards.  A solid foundation will reduce system noise and 
vibration, and will improve pump performance.  Refer to 
ANSI/HI standards or a suitable pump handbook for 
information on typical pump mounting and foundations.  
Check coupling alignment after pump and base assembly is 
secured to the foundation. 

  

Figure 2 - Pipe Type Anchor Bolt Box 

When installing units built on channel or structural steel type 
bases, use care to avoid twisting the base out of shape when 
anchor bolts are tightened. Shims should be used under the 
edges of the base prior to tightening of the anchor bolts to 
prevent distortion. 
 

Summary of Contents for HXL10E

Page 1: ...y be obtained from Blackmer s website www blackmer com or by contacting Blackmer Customer Service SAFETY DATA This is a SAFETY ALERT SYMBOL When you see this symbol on the product or in the manual loo...

Page 2: ...use a lifting device capable of supporting the full weight of the pump assemblies Heavy assemblies can cause personal injury or porperty damage PUMP DATA PUMP IDENTIFICATION A pump Identification tag...

Page 3: ...intake pipe For viscosities greater than1000 SSU consult the strainer manufacturer instructions 5 Strainers must be cleaned regularly to avoid pump starvation 6 Intake and discharge piping MUST be fre...

Page 4: ...is manual for parts removal and replacement instructions Figure 4 Reversing the Relief Valve CHECK VALVES If a check valve is used install it at the pump discharge The use of check valves or foot valv...

Page 5: ...culties during start up are experienced 1 Start the motor Priming should occur within one minute 2 Check the inlet and discharge pressure gauges to ensure the system is operating within expected param...

Page 6: ...alve HXL pump models are offered with an optional relief valve assembly bolted onto the pump casing Pumping volatile liquids under suction lift may cause cavitation Partial closing of the discharge va...

Page 7: ...68 Nm HXLJ8 178 lbs ft 241 Nm 50 lbs ft 68 Nm HXL10 178 lbs ft 241 Nm 100 lbs ft 136 Nm 50 lbs ft 68 Nm SCHEDULED MAINTENANCE STRAINERS Strainers must be cleaned regularly to avoid pump starvation Sch...

Page 8: ...he head assembly from the outboard nondriven side of the pump according to steps 4 8 in the Pump Disassembly section of this manual 4 Turn the shaft by hand until a vane comes to the top 12 o clock po...

Page 9: ...5 Remove the head O ring 72 and disc 71 If needed threaded holes are provided in the disc to break it free 6 Remove the top vane then rotate the shaft by hand to bring the next vane to the top until...

Page 10: ...se Refer to the Lubrication section for the recommended grease Install the bearing into the recess of the head g Inspect the grease seal 104 for wear or damage and replace as required Grease the outsi...

Page 11: ...ary O ring of the mechanical seal 153B 153D will come off with the hub a Pull the bearing 24 from the housing in the hub b To remove the mechanical seal stationary seat 153B remove the seal retaining...

Page 12: ...mp Install the six 6 disc retaining screws 71A and lockwashers 71B 7 Install a new head O ring 72 8 Using a hoist carefully attach the head 20 to the casing with the head drain hole towards the bottom...

Page 13: ...ckwasher tang into the slot in the locknut The pump should continue to turn freely when rotated by hand 16 Inspect the grease seal 104 for wear or damage and replace as required Grease the outside dia...

Page 14: ...vanes discs liner or rotor 6 Excessive restriction in discharge line causing partial flow through the relief valve 7 Relief Valve worn set too low or not seating properly 8 Vanes installed incorrectly...

Page 15: ...y too high for the pump speed 3 Relief valve not opening 4 Hydraulic hammer pressure spikes 5 Pump driver driveline drive shaft misalignment 6 Excessively worn vanes or vane slots 7 Settled or solidif...

Page 16: ...102 A00 page 16 16 1809 Century Avenue Grand Rapids Michigan 49503 1530 U S A Telephone 616 241 1611 Fax 616 241 3752 E mail blackmer blackmer com Internet Address www blackmer com...

Reviews: