background image

108-A00: Page 3/12 

INSTALLATION 

NOTICE:

 

Blackmer seal-less pumps must only be installed in 

systems designed by qualified engineering personnel. 

System design must conform with all applicable 

regulations and codes and provide warning of all system 

hazards. 

 

 

Hazardous voltage. 

Can shock, burn or 

cause death. 

  Install, ground and wire to local and 

National Electrical Code requirements. 

  Install an all-leg disconnect switch near 

the unit motor. 

  Disconnect and lockout electrical power 

before installation or service 

 

Electrical supply MUST match motor 

nameplate specifications. 

  Motors equipped with thermal protection automatically 

disconnect motor electrical circuit when overload exists.  

Motor can start unexpectedly and without warning. 

 

 

 

PRE-INSTALLATION CLEANING

 

NOTICE: 

New  pumps  contain  residual  test  fluid  and  rust  inhibitor.  

If necessary, flush pump prior to use. 

Foreign matter entering the pump WILL cause extensive 

damage. The suction tank and piping MUST be cleaned and 

flushed prior to pump installation and operation. 

 

 

LOCATION AND PIPING

 

An improperly designed piping system or improper unit 

installation WILL significantly reduce pump performance and 

life. Blackmer recommends the following piping system layout 

and unit installation. 

1.  To minimize intake losses, locate the pump as close as 

possible to the source of supply. 

2.  Intake piping and fittings MUST be at least as large in 

diameter as the pump intake connection. 

3.  Minimize the number of intake line fittings (valves, elbows, 

etc.) and piping turns or bends. 

4.  It is recommended an intake strainer be installed at least 

24" (0.6m) from the pump intake. For viscosities less than 

1000 SSU the strainer should have a net open area of at 

least four times the area of the intake pipe. For viscosities 

greater than 1000 SSU consult the strainer manufacturer 

instructions. Strainers must be cleaned regularly to avoid 

pump starvation. 

5.  Intake and discharge piping MUST be free of all leaks. 

6.  Expansion joints, placed at least 36" (0.9m) from the 

pump, will compensate for expansion and contraction of 

the pipes. Contact the flexible connector/hose 

manufacturer for required maintenance/care and design 

assistance in their use. 

7.  Install vacuum and pressure gauges in the 1/4" NPT ports 

provided in the pump cylinder to check pump at start up. 

8.  ALL piping and fittings MUST be properly supported to 

prevent any piping loads from being placed on the pump. 

9.  Check alignment of pipes to pump to avoid strains which 

might later cause misalignment.  See Figure 1.  Unbolt 

flanges or break union joints.  Pipes should not spring 

away or drop down.  After pump has been in operation for 

a week or two, completely recheck alignment. 

 

Figure 1 

10.  When pumping liquids at elevated temperature, provisions 

should be made to compensate for expansion and 

contraction of the pipes, especially when long pipe lines 

are necessary.  Steel pipe expands approximately 3/4” 

(1.9 cm) per 100 feet (30.49 m) per 100°F (37.8°C) rise in 

temperature. 

 

 

CHECK VALVES 

The use of check valves or foot valves in the supply tank is not 

recommended with self-priming, positive displacement pumps.  
If the possibility of liquid backflow exists when the pump is off, 

a check valve in the pump discharge piping is recommended 

because the pump can motor in the reverse rotation and create 

undue stress on all attached components.  Never start a pump 

when it is rotating in the reverse rotation as the added starting 

torque can damage the pump and related equipment. 

 

 

PUMP MOUNTING

 

Permanently mount the unit by securing the base plate with 

adequately sized anchor bolts to a level concrete floor following 

recommended industry standards.  A solid foundation will 

reduce system noise and vibration, and will improve pump 

performance.  Refer to ANSI/HI standards or a suitable pump 

handbook for information on typical pump mounting and 

foundations. 

BOLT

 

BASE

 

STANDARD

PIPE

WASHER

 

Figure 2 

 

Summary of Contents for SMVP15B

Page 1: ... one of the following signal words and be alert to the potential for personal injury death or major property damage Warns of hazards that WILL cause serious personal injury death or major property damage Warns of hazards that CAN cause serious personal injury death or major property damage Warns of hazards that CAN cause personal injury or property damage NOTICE Indicates special instructions whic...

Page 2: ... Disconnecting fluid or pressure containment components during pump operation can cause serious personal injury death or major property damage Do not operate without guards in place Operation without coupling guard can cause serious personal injury death or major property damage PUMP DATA PUMP IDENTIFICATION A pump Identification tag containing the pump serial number I D number and model designati...

Page 3: ...t be cleaned regularly to avoid pump starvation 5 Intake and discharge piping MUST be free of all leaks 6 Expansion joints placed at least 36 0 9m from the pump will compensate for expansion and contraction of the pipes Contact the flexible connector hose manufacturer for required maintenance care and design assistance in their use 7 Install vacuum and pressure gauges in the 1 4 NPT ports provided...

Page 4: ...h the value in the Table the bushing MUST be repositioned with a new Dim B Loosen the bolts and setscrew If Measurement A is High Move the bushing towards the motor C Face New Dim B table Dim B less the difference between Measurement A and table Dim A If Measurement A is Low Move the bushing away from the motor C Face New Dim B table Dim B plus the difference between Measurement A and table Dim A ...

Page 5: ...etting of the pump relief valve by gradually closing a valve in the discharge line momentarily and noting the reading on the pressure gauge This pressure reading should be 10 20 psi 96 1 4 bar higher than the maximum system operating pressure DO NOT run the pump for more than 15 seconds with the discharge valve completely closed If adjustments need to be made refer to Relief Valve Setting and Adju...

Page 6: ...st a closed discharge valve RELIEF VALVE SETTING AND ADJUSTMENT The factory relief valve pressure setting is marked on a metal tag attached to the valve body It is recommended the relief valve be set at least 10 20 psi 69 1 4 bar higher than the operating pressure or the system pressure control valve setting DO NOT remove the R V Cap OR adjust the relief valve pressure setting while the pump is in...

Page 7: ...o not operate without guard in place Operation without guards in place can cause serious personal injury major property damage or death Hazardous pressure can cause serious personal injury or property damage Disconnecting fluid or pressure containment components during pump operation can cause serious personal injury death or major property damage Strong magnetic field can cause personal injury Fa...

Page 8: ...ary DO NOT damage the containment can or pump head Remove and discard the containment can O ring 51 Strong magnetic field can cause personal injury Failure to use care when handling magnets can cause personal injury 6 With properly sized snap ring pliers remove the snap ring 83 from the shaft end Pull the inner magnet 52 from the shaft Remove the shaft key 35 7 Remove the four SMVP or eight MVP so...

Page 9: ...zed arbor press remove the old bearing from the head b To aid installation and prevent damage heat the head in an oven to 200 F 93 C c Coat the new bearing with a quality grade of bearing grease and place it on the inside face of the head with the notched end UP Align the notch in the bearing with the groove in the head d Using an arbor press CAREFULLY press the bearing into the head until it is f...

Page 10: ...n the inboard shaft end 2 Align the inner magnet 52 with the key and slide the magnet over the shaft with the pump end of the magnet towards the inboard head 3 Fully and squarely install the snap ring 83 into the groove in the end of the shaft 4 Check to ensure the pump shaft rotates freely when turned by hand 5 Install a new containment can O ring 51 into the groove provided on the hub of the inb...

Page 11: ...e incorrectly set 2 Leaks in suction piping 3 Incorrect rotation 4 Broken shaft 5 Pump vapor locked 6 Incorrect pump speed 7 Vanes damaged worn or incorrectly installed 8 Cavitation 9 Damaged or worn pump or system components 10 Excessive piping system friction losses 11 Relief valve incorrectly set worn or damaged 12 Operating against a closed discharge 13 Shaft bent or misaligned 14 Worn or dama...

Page 12: ... 215 GPM HXL 6 8 10 Sliding Vane Pumps 130 to 2 220 GPM Refineries Terminals Barges Ships Reciprocating Gas Compressors Liquefied Gas Transfer Boosting Vapor Recovery Hand Operated Pumps Dispensing Transfer In line Accessories Gear Reducers Bypass Valves Strainers Visit www blackmer com for complete information on all Blackmer products 1809 Century Avenue Grand Rapids Michigan 49503 1530 U S A Tel...

Reviews: