background image

AODDAMPENER™

AODDampener Model

AOD-10 (1”)

AOD-15 (1.5”)

AOD-20 (2”)

AOD-30 (3”)

PTFE Diaphragm Kit

AOD-10-100

AOD-15-100

AOD-20-100

AOD-30-100

PTFE Diaphragm Kit, ATEX

AOD-10-100-AT

AOD-15-100-AT

AOD-20-100-AT

AOD-30-100-AT

O-Ring Installation Tool

AD10-032

AD00-032

AD00-032

AD30-032

Replacement Kits and Tools

Diaphragm replacement kits include all parts necessary for replacement, including hardware and O-rings. The O-Ring Installation Tool 

is intended solely for use when installing O-rings in the automatic valve on the non-wetted housing of the AODDampener to ensure 

proper O-ring placement on reassembly.

Regularly inspect compressed air line for damage. If compressed air to dampener is reduced or stopped, diaphragm failure will 

occur.

DO NOT use dampener if the fasteners (nuts and bolts) are corroded. Check for fastener corrosion frequently, especially in 

atmospheres containing salt or corrosive chemicals, or if dampener leakage has occurred.

Read Before Installation

Maintenance and Repair

Figure 1

Prior to starting the pump, 

dampener must have the air supply connected and available to the dampener to avoid possible damage to 

diaphragms. Once the air supply connection is complete, the dampener is fully functional and will operate automatically when the pump 

is started.

To avoid damage to diaphragms, DO NOT start the pump before compressed air is supplied to dampener.

Step 3 — Startup 

If a diaphragm failure occurs, it is possible for the pumped product to enter the dampener air chamber and be expelled from 

the dampener exhaust. It is recommended that the exhaust be plumbed to a safe area or to a Blacoh SPILLSTOP

 unit if the 

dampener location and/or the nature of the pumped product presents a hazard.

If a diaphragm failure occurs, it is possible for the pumped product to enter the dampener air chamber and into the 

compressed air line. It is recommended that a one-way check valve be installed at the air connection to prevent backflow of 

product.

The exhaust port in the automatic valve is supplied with a muffler. Dampener will not operate if the exhaust port is blocked or, if 

an air supply is attached to that port.

Pump must be turned off and system pressure must be zero prior to dampener disassembly. In systems with a static 

head pressure, it is not sufficient to simply isolate the dampener. To prevent damage to the PTFE diaphragm, fluid system 

pressure must be relieved prior to removing charge pressure from dampener.

Diaphragm Replacement

Disassembly

1.  Turn pump off and allow system pressure to drop to zero pressure. Disconnect compressed air line to dampener.

Summary of Contents for AODDampener

Page 1: ...g system maximizing the reduction in pulsation When sized correctly and properly installed the AODDampener will greatly reduce the damaging effects of pressure variations and improve the efficiency of transferring fluids All dampeners manufactured by BLACOH use pressure bodies made in the USA to ensure quality Prior to shipment each and every dampener is factory pressure tested to assure proper fu...

Page 2: ... Fluid Controls Inc Model No Serial No Pump Area and Number Purchased From Contact Phone Email Installation Date MODEL Specifications Installation Information Table of Contents SAFETY Warnings 2 Safety Symbols 2 General Safety 2 Equipment Misuse Hazard 2 GENERAL Information 3 Must Read Before Installation 3 Installation Notes 3 ATEX Standard 3 Temperature Limits 3 Maintenance 3 Installation Operat...

Page 3: ...ain internal fluid air or gas pressure DO NOT pump incompatible fluids through dampener Consult distributor or factory if you are not sure of the compatibility of system fluids with dampener materials AODDampener models are designed to operate with compressed air only Other compressed gases have not been tested and may be unsafe to use DO NOT USE OXYGEN Always shut off air supply remove internal d...

Page 4: ...Standard Dampening of flow pulsations can only be effective if a minimum of 5 to 10 psi 0 4 to 0 7 bar back pressure downstream of dampener is available A Blacoh back pressure valve may be required downstream of dampener except when dampener is used as an inlet stabilizer for the inlet side of the pump It is recommended that a Blacoh pressure relief valve be installed in all pump systems to ensure...

Page 5: ...o conduct such regular inspections and replacement will void the product warranty given by the manufacturer and the manufacturer will have no liability whatsoever for any vessel failure or malfunction Step 1 Installation Position Install the dampener inline as close to the pump discharge as possible to absorb the pulse at its source and before any downstream equipment such as risers valves elbows ...

Page 6: ... dampener is fully functional and will operate automatically when the pump is started To avoid damage to diaphragms DO NOT start the pump before compressed air is supplied to dampener Step 3 Startup If a diaphragm failure occurs it is possible for the pumped product to enter the dampener air chamber and be expelled from the dampener exhaust It is recommended that the exhaust be plumbed to a safe a...

Page 7: ...and bolts Process liquid may be present if diaphragm failure has occurred Always wear safety glasses and other appropriate safety equipment when disassembling dampener 6 The backup diaphragm is attached to the air control shaft Gently pull down on the diaphragm to slide the shaft out from the automatic valve in the non wetted housing If the shaft does not slide out easily remove the muffler insert...

Page 8: ...until O ring grooves align b Position the first O ring into the first groove on the tool to install the O ring in groove 5 of the automatic valve Use your finger to cover the top of slide to prevent the O ring from slipping out of place and push the slide forward to properly position the O ring on the tool c With the slide held in place insert the tool into the automatic valve until the shoulder o...

Page 9: ...o the shaft with two hands and stop when hand tight Remove the diaphragm and shaft from the vise and insert the shaft into the automatic valve Reassembly 1 If removed on disassembly reinstall the backup plate Clean and dry the internal housing surface taking particular care to ensure the flange area is completely clean and dry Slide the backup plate onto the non wetted housing until it rests on th...

Page 10: ...holes aligned Ensure the diaphragms fit together snugly to minimize any air between them 6 Insert bolts with flat washers through the top side Attach flat washers and lock nuts on the bottom side for each bolt Lubricate bolt threads with anti seize compound or oil before installing nuts to prevent galling 7 Torque bolts in a star pattern according to the following torque specifications AOD 10 1 in...

Page 11: ...ed Housing 2 Non wetted Housing 3 Bolt 4 Washer 5 Nut 6 PTFE Diaphragm 7 Backup Diaphragm 8 Air Control Shaft 9 O Ring 10 Backup Plate 11 Retaining Ring 12 Plug 13 Muffler 14 Automatic Valve 13 3 4 2 12 10 11 9 8 7 6 1 4 5 14 Exploded View ...

Page 12: ... available on Blacoh s website at www Blacoh com M26E11_030 Manufacturer s Limited Warranty Return Policy PROUDLY MANUFACTURED IN THE USA Blacoh Headquarters 601 Columbia Ave Bldg D Riverside CA 92507 USA 951 342 3100 www Blacoh com Sales Blacoh com ...

Reviews: