Introduction 

 
Blake Water Solutions’ Specialist Series™ point-of-entry (POE) Aerating Iron Oxidizer (AIO) filter systems function as a 
regenerable water treatment unit utilizing oxygen instead of potentially harmful chemicals to rejuvenate and enhance the 
performance of the selective filtration media.  The filtration media provided is specific to the water contaminant or contaminants 
that your water treatment specialist has identified. 
 
The AIO system utilizes the Clack WS1EE control valve equipped with air injection capability to remove ferrous (or clear water) 
iron, manganese, and sulfur from the water by both oxidation and filtration.  During the regeneration cycle, an air bubble is 
established in the head space of the filter tank above the media.  Then, during service, as untreated water enters the tank, it mixes 
with the air.  Oxygen present in the air oxidizes some of the iron and managese that are present in the water, causing them to 
precipitate into particles which become trapped in the filter media.  The remaining dissolved iron and manganese precipitate out in 
the filter bed as they are oxidized by the catalytic reactions occurring on the media surface. 
 
Unlike other iron filter alternatives, the Clack WS1EE AIO technology is designed for use in a single tank / valve system 
configuration, reducing both installation and maintenance costs, yet delivering years of trouble-free service. No chemical additives 
or air compressors are required for operation or regeneration with the Clack WS1EE AIO’s unique and advanced design.  
 

Do not install this system if methane is present in the water - DANGEROUS DEADLY GAS CAN ACCUMULATE 

 

This system is not intended to be used for treating water that is microbiologically                                                                             

unsafe or of unknown quality without adequate disinfection before or after the system. 

 
 

Installation Requirements

 

 
WATER PRESSURE: A least 30 psi of water pressure (2.7bar) is required for the injector to draw air and operate effectively. 
 
CAUTION: Water pressure must not exceed 80psi (5.5 bars), water temperature is not to exceed 110°F (43°C), and the unit cannot 
be subjected to freezing conditions. 
NOTE: Due to the air pocket, exceeding 80PSI will adversely impact performance. 
 
ELECTRICAL FACILITIES: An uninterrupted 120 VAC supply is required. The valve is supplied with a 12 VAC transformer. 
Please make sure your voltage supply is compatible with your unit before installation.   
 
EXISTING PLUMBING: Condition of existing plumbing should be free from scale and iron buildup. Piping that is built up heavily 
with scale and/or iron should be replaced.  
 
LOCATION OF FILTER AND DRAIN: The filter should be located close to a drain to prevent air breaks and back flow.  
 
DRAIN AIR GAP: Always provide the proper air gap distance of two drain pipe diameters. 

 

Summary of Contents for AIO

Page 1: ...XOWSEEAIO REV 06 2018 OPERATION AND INSTRUCTION MANUAL SPECIALIST SERIES AERATION FILTER SYSTEM For Residential Filter Systems with Clack WS1EE 4 Button AIO Control Valve ...

Page 2: ...ation Requirements Page 1 Installation Commissioning Page 2 Filtration Media Loading Page 3 Backwash Regeneration Cycles Page 4 Bypass Valve Page 5 Controller Page 6 Programming Setting Time of Day Installer Settings Page 8 Programming System Setup Page 9 Replacement Parts Page 10 Filtration Media Overview Page 11 ...

Page 3: ... use in a single tank valve system configuration reducing both installation and maintenance costs yet delivering years of trouble free service No chemical additives or air compressors are required for operation or regeneration with the Clack WS1EE AIO s unique and advanced design Do not install this system if methane is present in the water DANGEROUS DEADLY GAS CAN ACCUMULATE This system is not in...

Page 4: ...lowly slide the deflector over the distributor tube down about 1 When threading the AIO valve to the tank the bottom of the threads will slide the deflector down As shown below 7 Lubricate the distributor O ring and tank O ring Place the main control valve on tank Note Only use silicone lubricant 8 Solder joints near the inlet outlet drain must be done prior to making thoses connections Leave at l...

Page 5: ... application Again adding additional water to the vessel will assist in loading by minimizing dust and optimize leveling 4 Unplug the riser tube carefully position the valve over it and turn the valve into the threads in the fiberglass tank tightening securely into tank and secure to the existing piping bypass Note Ensure that the internal O ring in the valve fits securely over the riser tube Sili...

Page 6: ... were trapped during service to be dislodged from the media and flushed to drain The media is also de compacted and readied for the the air injection step After the 10 minutes of flow to drain the valve piston will drive to the draw position The Backwash step can be lengthened if necessary but it should never be shortened 2 Air Recharge 40 minutes During this cycle water flows to drain creating a ...

Page 7: ...ed during the backwash regeneration cycle 2 Bypass Operation The inlet and outlet handles point to the center of the bypass the control valve is isolated from the water pressure contained in the plumbing system Untreated water is supplied to the plumbing system 3 Diagnostic Mode The inlet handle points in the direction of flow and the outlet handle points to the center of bypass valve system water...

Page 8: ...ys User 1 Displays gallons until backwash not shown if set for time clock operation User 2 Displays number of days until next backwash User 3 Displays present flow rate in gallons per minute always reads 0 because no meter is installed User 4 Displays total volume in gallons since last reset always reads 0 because no meter is installed User 5 Shows current time ...

Page 9: ...volatile memory Control Operation during a Power Failure The control valve includes a coin cell backup battery In the event of power failure the control shifts into power saving mode and stops monitoring water usage The display and motor shut down but the control continues to keep track of the time for approximately 8 hours System configuration settings are stored indefinitely in non volatile memo...

Page 10: ...n 8 hours and the time of day flashes this indicates that the battery is depleted The time of day should be reset and the non rechargeable battery should be replaced The battery is a 3 Volt Lithium Coin Cell type 2032 Time of day should be reset when Daylight Savings Time starts ends Installer Settings To enter Installer Display press NEXT and simultaneously for about 5 seconds and release Day Ove...

Page 11: ...to previous step Step 7S Select the time for the third cycle using or Default oFF DO NOT CHANGE Press NEXT to go to Step 8S Press REGEN to return to previous step Step 8S Select the time for the fourth cycle using or Default oFF DO NOT EXCEED 1 MINUTE Press NEXT to go to Step 9S Press REGEN to return to previous step Step 9S Select the pounds for the fifth cycle using or Default oFF DO NOT CHANGE ...

Page 12: ...STON OV32 INLET CHECK VALVE OV15HT AIR DRAW CHECK VALVE H6061 AIR DRAW SCREEN KTSCREEN SCREEN W TUBE K74V4144AIO AIR DRAW ASSY COMPLETE AIOGROM GROMMET D7147 UPPER DEFLECTOR K74V30101F INJECTOR F BLUE RKWS1AIO AERATION MAINTANANCE KIT Includes Blue Injector Pistons Stack Assy Stack Puller Tool and Service Wrench VARIES DRAIN LINE FLOW CONTROL Injector may vary on larger tanks ...

Page 13: ...ides superior filtration down to 5 micron at high flows up to 12 18 gpm ft Advantages include the removal of a wide range of colloidal and soluble inorganic contaminants by surface sorption chemical binding charge neutralization coagulation reactions and or ion exchange phenomena Certified to NSF ANSI Standard 61 Corosex Color brownish white Density 75 lbs per CF Mesh size 6 x 16 Corosex is a spec...

Page 14: ...NOTES ...

Page 15: ...NOTES ...

Page 16: ...91 7867 MAINE BLAKE EQUIPMENT HERMON 1194 Odlin Road Hermon ME 04401 Phone 800 450 6822 BLAKE EQUIPMENT PORTLAND 70 Ingersoll Drive Unit 1 Portland ME 04103 Phone 800 308 2213 The Blake Group is a growing family of companies dedicated to providing our valued customers with superior products and technologies in commercial industrial and residential markets compliant with industry standards and meet...

Reviews: