Installation Guide
We assume, that the installation will be done by a skilled and well educated electrical technician taking
care of environmental circumstances like Air-condition and grounding requirements. The device should
always be mounted into a 19’’ Rack by the front screws and even better with some metal angles
avoiding bending of the units housing.
Power
When you connect the power source, make sure the source voltage fits to the PSU data.
Make sure the connected cables are in good condition. Avoid shortage of signal cables.
Make sure the power switch is OFF before you start to install the device
Environmental Requirement
Item
Requirement
Server operating room
and floor
Electric Isolation, Dust Free Volume resistivity of ground anti-static material:
1x10
7
...1x10
10
,
Grounding current limiting resistance:
1M
(Floor bearing should be greater than 450Kg/
㎡
)
Environmental
Temperature
5...40°C (sustainable )
,
0...45°C (short time), installing air-conditioning is
recommended
Relative Humidity
20%...80% sustainable 10%...90% short time
Pressure
86...105kpa
Door & Window
Installing rubber strip for sealing door-gaps and dual level glasses for
window
Wall
It can be covered with wallpaper, or brightness less paint.
Fire Protection
Fire alarm system and extinguisher
Power
Requiring device power, air-conditioning power and lighting power are
independent from each other. Device power requires AC 110V±10%,
50/60Hz or AC 220V±10%, 50/60Hz. Please carefully check before
connecting.
Grounding Requirement
The grounding requirements can vary from region to region but usually has to be considered according to
national norms and regulations. Opening the top case is strictly forbidden as long as the AC power source is
connected or the device is in fully operation.