background image

Centrifugal inline fan

USER’S MANUAL

EN

Centro-MZ  100 

Centro-MZ  125

Centro-MZ  150

Centro-MZ  150  max

Centro-MZ  200

Summary of Contents for 4058448015465

Page 1: ...Centrifugal inline fan USER S MANUAL EN Centro MZ 100 Centro MZ 125 Centro MZ 150 Centro MZ 150 max Centro MZ 200 ...

Page 2: ...rm without the prior written permission of the Company SAFETY REQUIREMENTS Please read the user s manual carefully prior to installing and operating the unit All user s manual requirements as well as the provisions of all the applicable local and national construction electrical and technical norms and standards must be observed when installing and operating the unit The warnings contained in the ...

Page 3: ...operate the unit outside the temperature range stated in the user s manual Do not operate the unit in aggressive or explosive environments Do not touch the unit controls with wet hands Do not carry out the installation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit T...

Page 4: ... produced by the unit towards open flame or ignition sources Do not block the air duct when the unit is switched on In case of continuous operation of the unit periodically check the security of mounting Do not sit on the unit and avoid placing foreign objects on it Use the unit only for its intended purpose THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE DO NOT DISPOSE THE ...

Page 5: ...on of hazardous substances toxic substances dust pathogenic germs THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY ...

Page 6: ...ower W Current A Max air flow m3 h RPM min 1 Noise level at 3 m dBA Transported air temperature С Centro MZ 100 1 230 82 0 36 278 3320 41 25 45 Centro MZ 125 85 0 37 357 3300 42 Centro MZ 150 78 0 34 475 3216 42 Centro MZ 150 max 174 0 76 750 3144 49 Centro MZ 200 240 1 05 1200 2850 49 The unit design is constantly being improved thus some models their wiring diagrams and terminal symbols may be s...

Page 7: ...ion in the system must be in compliance with the direction of the arrow on the fan casing Install a hood on outlet discharge spigot side in case of the vertical fan installation Provide a straight air duct section at least 1 m long on the intake spigot side in case of horizontal fan installation with maximum allowable humidity m Mounting sequence Remove the bolt from the casing 1 and install the f...

Page 8: ...al magnetic trip built into the stationary wiring to disconnect all the power mains phases The rated current must be not below the rated current consumption refer to the Technical data section The QF external switch location must ensure free access for quick shutdown of the fan The recommended circuit breaker nominal current is 1 A The recommended wire cross section is 0 75 mm2 The actual conducto...

Page 9: ...g of air ducts or other ventilation system elements Impeller clogging Damaged air ducts Air damper closure Clean the air ducts and other ventilation system elements as well as the impeller Check the air ducts for damage Make sure the air dampers and louvre shutters are open STORAGE AND TRANSPORTATION REGULATIONS Store the unit in the manufacturer s original packaging box in a dry closed ventilated...

Page 10: ...acturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual including submission with missing component parts previously dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user s manual User s failure to ensure timely technica...

Page 11: ...nit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date Signature The unit has been installed in accordance with the provisions of all the applicable local and national construction electrical and technical codes and standards The unit operates normally as intended b...

Page 12: ...www blaubergventilatoren de B05 1EN 10 ...