background image

www.blaubergventilatoren.de

11

VENTO V50-1 / V50-1  S / V50-1 Pro / V50-1 S Pro

All electric connection to the control unit and the ventilator are performed 

with the socket connectors (detachable terminal blocks) for mounting and 

servicing facilitation.  Each mating part of the socket connector has colour 

marking in compliance with marking on the circuit board to ensure correct 

and quick electric installation.

The control panel SEA is used to set one of four operation mode of the 

unit, Fig. 23: 

1. Ventilation mode (air extract / air supply)* at the first speed with air 

flow 26 m

3

/h.

2. Ventilation mode (air extract / air supply)* at the second speed with air 

capacity 53 m

3

/h.

3. Reversible (regeneration) operation at the first speed with air flow 26 m

3

/h. 

The unit changes air  flow direction every 70 seconds.

* - air flow direction depends on position of the jumper JMP1 on the 

circuit board. The jumper is set to supply mode by default, Fig. 24.

Unit on

Unit off

First speed 

mode 

Reversible 

operation mode

Second speed mode

Extract/supply mode*

Fig. 23

The total wiring diagram for connection to the control panel SEA is shown 

in Fig. 24.

Two control channels are used to connect V50-1 to the control panel SEA. 

Such design solution provides flexible connection of several units.

The impeller rotation direction at start of the regeneration mode or in 

ventilation mode is determined by positioning the jumper JMP1 on the 

ventilation unit circuit board. The jumper positioned in «Flow In» position sets 

the unit to supply mode and the jumper positioned in «Flow Out» position 

sets the unit to extract mode. 

The VENTO V50-1 is connected to the control panel SEA with a five-wire 

cable. The wire colour marking corresponds to the supplied cable. The 

minimum conductor cross section is 0.25 mm

2

 (23 AWG).

Type and power of the step-down transformer T1 must be in compliance 

with the parameters in the table 2. Separate power supply (230 V / 50 Hz or 

120 V / 60 Hz) must be connected both to the control unit SEA (SEA-T) and 

to the ventilation unit to enable actuation of the automatic shutters (socket 

connectors 31-32 in each case).

Fig. 24. General wiring diagram for connection of Vento V50-1 unit to a single SEA control panel  

31

32

33
34
35
36

11
12
13
14

15

11

12
13

14

15

1

2

3

4
5

1

2

3

4

5

31

32

33

34

35

36

37
38
39
40

ÕÒ

3

25

21 22 23 24

15

14

13

12

11

5

1

2

3 4

1

2

3

4

5

31

32

33

34

35

36

37
38
39
40

ÕÒ

3

25

21 22 23 24

15

14

13

12

11

5

1

2

3 4

L

N

5

4

3

2

1

SEA control panel

VENTO V50-1

JMP1

Marking "1-5" on the 

connecting cable socket 

connector

Marking "11-15" on the 

controller socket

 connector

~120 V

or

~230 V

~120 V

or

~230 V

Marking "1-5" on the 

connecting cable 

socket connector

Marking "11-15" on the 

controller socket 

connector

Marking "21-25" on the 

controller socket 

connector

~120 V

or

~230 V

gre

y

br

own

yello

gr

een 

whit

grey

brown

yellow 

green 

white

white 

white 

red 

red

Transformer 12 W

АТ-12

Summary of Contents for 4058448022678

Page 1: ...VENTO V50 1 SINGLE ROOM REVERSIBLE UNIT WITH HEAT AND HUMIDITY RECOVERY OPERATION MANUAL EN...

Page 2: ...Safety rules 3 Transportation and storage rules 3 Manufacturer s warranty 3 Design and operating logic 4 Modifications and options 5 Delivery set 5 Technical data 6 Mounting 7 Connection and control...

Page 3: ...icky substances or fibrous materials The appliance is not designed for use in an inflammable and explosive medium Do not close or block the intake or exhaust vent of the appliance not to disturb the n...

Page 4: ...SEA T12 or the control panel SEA is used for operation mode control The delivery set of the units VENTO V50 1 Pro V50 1 S Pro includes the control and power unit SEA T12 consisting of the control pane...

Page 5: ...Pro The unit for the wall thickness from 120 up to 430 mm Equipped with the control panel and the control unit SEA T12 DELIVERY SET Unit 1 item Fixing set 1 item SEA T12 control and power unit for Pro...

Page 6: ...0 021 0 026 Max air flow m3 h 26 53 Sound pressure level at 1 m distance dB A 24 34 Sound pressure level at 3 m distance dB A 14 24 Outdoor sound pressure attenuation dB A 19 Transported air temperat...

Page 7: ...opic air ducts outer ventilation hood and laying out of electric cables final mounting before commissioning of a house It includes installation of the regenerator the filter connection of the ventilat...

Page 8: ...the back part of the ventilation unit Fig 14 7 Remove a screw from the bottom part of the ventilation unit and take off the front grille 8 Insert the dowels 5x25 in the wall and fix the ventilation u...

Page 9: ...l using the screws 4x40 from the delivery set 13 Install the front part of the outer ventilation hood 14 Install the control panel SEA T12 with a power unit inside a prepared hole in the wall see Fig...

Page 10: ...ery set of the unit model The control and power unit SEA T12 consists of a control panel and a 12 W power transformer Fig 22 In case of the control panel SEA either power transformer AT 12 or AT 40 ar...

Page 11: ...tion mode is determined by positioning the jumper JMP1 on the ventilation unit circuit board The jumper positioned in Flow In position sets the unit to supply mode and the jumper positioned in Flow Ou...

Page 12: ...5 The socket connectors of the connecting cable supplied with the unit are marked 1 to 5 and must be connected to the controller socket connectors marked 11 15 for outputs or 21 25 for inputs Cable ch...

Page 13: ...2W transformer wire leads to the contacts A1 35 36 of the controller A1 SEA using the socket connector at the cable K2 The cable is included into delivery set of the 40W transformer model Then connect...

Page 14: ...ow green white grey brown yellow green white 1 grey 2 brown 3 yellow 4 green 5 white 1 grey 2 brown 3 yellow 4 green 5 white 1 grey 2 brown 3 yellow 4 green 5 white 1 grey 2 brown 3 yellow 4 green 5 w...

Page 15: ...year Remove the screw in the bottom part of the fan grille remove and clean the grille Disconnect the wires from the ventilation unit by using the connectors Remove the four screws and take off the v...

Page 16: ...the approximation of the laws of the Member States relating to electromagnetic compatibility This certificate is issued following test carried out on samples of the product referred to above Approval...

Page 17: ..._____________________________________________ _______________________________________________________________________________________ __________________________________________________________________...

Page 18: ..._____________________________________________ _______________________________________________________________________________________ __________________________________________________________________...

Page 19: ..._____________________________________________ _______________________________________________________________________________________ __________________________________________________________________...

Page 20: ...www blaubergventilatoren de VENTO V50 1 v 1 6 EN...

Reviews: