background image

www.blaubergventilatoren.de

15

VENTO V50-1 / V50-1  S / V50-1 Pro / V50-1 S Pro

Fault 

Possible reasons

Fault handling

The fan does not start 

when the unit is on.

No power supply.

• 

Make sure of correct power supply, otherwise troubleshoot 

the connection error.

Jammed motor, soiled impeller blades.

• 

Turn the unit off. 

• 

Troubleshoot the motor jam and the impeller clogging. 

Clean the blades. 

• 

Restart the unit.

Automatic switch tripping 

during the unit start.

Short circuit in power grid as a result of short circuit.

• 

Turn the unit off. 

• 

Contact the seller.

Low air flow.

Low set fan speed. 

• 

Set higher speed.

The filter, the fan or the regenerator are soiled. 

• 

Clean or replace the filter. 

• 

Clean the fan and the regenerator.

Noise, vibration.

The impeller is soiled. 

• 

Clean the impeller. 

Loose screw connection of the unit casing or the outer 

ventilation hood. 

• 

Tighten the screws of the unit or the outer ventilation 

hood.

TROUBLESHOOTING

The unit technical maintenance consists in the periodic cleaning of the 

unit surfaces and cleaning or replacement of the filters. Remove dust 

with a soft brush, cloth or compressed air. Do not use water, abrasive 

detergents, solvents, sharp objects. 

1. Fan maintenance (once a year). 

• 

Remove the screw in the bottom part of the fan grille, remove and 

clean the grille. 

• 

Disconnect the wires from the ventilation unit by using the 

connectors.

• 

Remove the four screws and take off the ventilation unit. 

• 

Clean the impeller blade.

2. Regenerator and filter maintenance (4 times a year).

• 

Take off the ventilation unit.  Pull the cord to remove the regenerator 

and the filter from the air duct. Do not let the regenerator fall down.

• 

Clean the filter as often as required, but at least once in three 

months. To clean the filter flush it under running water or use a 

vacuum cleaner. Let the filter dry and install the dry filter inside the 

air duct. Contact a local distributor for the filters stated above in the 

section «Technical data». 

• 

Even regular filter maintenance may not completely prevent the 

dust ingress into the regenerating unit. Clean the regenerator with 

a vacuum cleaner at least once a year. 

3. Outer ventilation hood maintenance (once a year). 

The outer ventilation hood may get clogged with leaves and other objects 

that reduce the unit air capacity.  

Check the outer ventilation hood twice a year and clean it as often as 

required.

Cleaning of the outer ventilation hood: 

• 

remove the front part of the outer ventilation hood: 

• 

clean the outer ventilation hood and the air duct.

WARNING! 

Disconnect the unit from power mains prior to maintenance operations!

MAINTENANCE

Summary of Contents for 4058448022678

Page 1: ...VENTO V50 1 SINGLE ROOM REVERSIBLE UNIT WITH HEAT AND HUMIDITY RECOVERY OPERATION MANUAL EN...

Page 2: ...Safety rules 3 Transportation and storage rules 3 Manufacturer s warranty 3 Design and operating logic 4 Modifications and options 5 Delivery set 5 Technical data 6 Mounting 7 Connection and control...

Page 3: ...icky substances or fibrous materials The appliance is not designed for use in an inflammable and explosive medium Do not close or block the intake or exhaust vent of the appliance not to disturb the n...

Page 4: ...SEA T12 or the control panel SEA is used for operation mode control The delivery set of the units VENTO V50 1 Pro V50 1 S Pro includes the control and power unit SEA T12 consisting of the control pane...

Page 5: ...Pro The unit for the wall thickness from 120 up to 430 mm Equipped with the control panel and the control unit SEA T12 DELIVERY SET Unit 1 item Fixing set 1 item SEA T12 control and power unit for Pro...

Page 6: ...0 021 0 026 Max air flow m3 h 26 53 Sound pressure level at 1 m distance dB A 24 34 Sound pressure level at 3 m distance dB A 14 24 Outdoor sound pressure attenuation dB A 19 Transported air temperat...

Page 7: ...opic air ducts outer ventilation hood and laying out of electric cables final mounting before commissioning of a house It includes installation of the regenerator the filter connection of the ventilat...

Page 8: ...the back part of the ventilation unit Fig 14 7 Remove a screw from the bottom part of the ventilation unit and take off the front grille 8 Insert the dowels 5x25 in the wall and fix the ventilation u...

Page 9: ...l using the screws 4x40 from the delivery set 13 Install the front part of the outer ventilation hood 14 Install the control panel SEA T12 with a power unit inside a prepared hole in the wall see Fig...

Page 10: ...ery set of the unit model The control and power unit SEA T12 consists of a control panel and a 12 W power transformer Fig 22 In case of the control panel SEA either power transformer AT 12 or AT 40 ar...

Page 11: ...tion mode is determined by positioning the jumper JMP1 on the ventilation unit circuit board The jumper positioned in Flow In position sets the unit to supply mode and the jumper positioned in Flow Ou...

Page 12: ...5 The socket connectors of the connecting cable supplied with the unit are marked 1 to 5 and must be connected to the controller socket connectors marked 11 15 for outputs or 21 25 for inputs Cable ch...

Page 13: ...2W transformer wire leads to the contacts A1 35 36 of the controller A1 SEA using the socket connector at the cable K2 The cable is included into delivery set of the 40W transformer model Then connect...

Page 14: ...ow green white grey brown yellow green white 1 grey 2 brown 3 yellow 4 green 5 white 1 grey 2 brown 3 yellow 4 green 5 white 1 grey 2 brown 3 yellow 4 green 5 white 1 grey 2 brown 3 yellow 4 green 5 w...

Page 15: ...year Remove the screw in the bottom part of the fan grille remove and clean the grille Disconnect the wires from the ventilation unit by using the connectors Remove the four screws and take off the v...

Page 16: ...the approximation of the laws of the Member States relating to electromagnetic compatibility This certificate is issued following test carried out on samples of the product referred to above Approval...

Page 17: ..._____________________________________________ _______________________________________________________________________________________ __________________________________________________________________...

Page 18: ..._____________________________________________ _______________________________________________________________________________________ __________________________________________________________________...

Page 19: ..._____________________________________________ _______________________________________________________________________________________ __________________________________________________________________...

Page 20: ...www blaubergventilatoren de VENTO V50 1 v 1 6 EN...

Reviews: