SETUP OF THE OPERATION MODES 

 AND 

 

 – the fan is turned off.

«60», «70», «80», «90», «100», «110» – the fan operates in the mode of maintaining a constant air flow with a given value of the air flow rate 
displayed in cubic feet per minute (CFM).

Example 1

 = 

 = 

 – with these settings, the fan will constantly maintain the air flow rate of 60 CFM. Once the switch is turned 

on or a sensor is activated, the fan will operate at maximum possible performance. This setting is factory set and is the default setting for 
fans with a maximum air flow of 110 CFM. For the fans with a maximum air flow – 150 CFM 

 = 

Example 2

 = 

 = 

 – with these settings, the fan will be constantly turned off. Once the switch is turned on or a sensor is 

activated,  the fan will switch to maintain the air flow rate of 90 CFM.
By changing the parameters 

 and 

 in this way, you can select the desired fan mode.

The fan maintenance includes regular cleaning of the surfaces of dust and dirt. Replace the filter as required, but at least every 6 months.
The impeller cleaning is shown below. Clean the impeller blades thoroughly every 6 months. 

DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE 

ANY MAINTENANCE OPERATIONS!

TECHNICAL MAINTENANCE

Summary of Contents for Ceileo Compact DC 110

Page 1: ...Centrifugal ceiling extract fan USER S MANUAL EN Ceileo Compact DC 110 Ceileo Compact DC 110 H IR Ceileo Compact DC 110 Light Ceileo Compact DC 110 Light H IR...

Page 2: ...s manual is correct at the time of the document s preparation The Company reserves the right to modify the technical characteristics design or configuration of its products at any time in order to inc...

Page 3: ...he entire service life of the unit While transferring the unit control the user s manual must be turned over to the receiving operator UNIT INSTALLATION AND OPERATION SAFETY PRECAUTIONS Disconnect the...

Page 4: ...ances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact the Seller Do not open the unit during operation Do not dir...

Page 5: ...UT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORI...

Page 6: ...sign is constantly being improved thus some models may be slightly different from those described in this manual A E H d L2 L1 B L1 B C A E C b a h H d h L2 Ceileo Compact DC 110 Light Ceileo Compact...

Page 7: ...rative grille Surface mounted luminaire Lamps Casing Protective cap sensor panel Lamp connector Parameter Ceileo Compact DC 110 Ceileo Compact DC 110 H IR Ceileo Compact DC 110 Light Ceileo Compact DC...

Page 8: ...on and switches to high speed After no more motion is detected the fan keeps operating for a set turn off delay time period adjustable from 1 to 90 minutes and returns to its original state Humidity...

Page 9: ...lamp into the appropriate socket in the fan terminal box casing For models with the option of connecting H humidity or IR motion sensors remove the protective cap from the grille before installing the...

Page 10: ...FOR CONNECTING THE FAN TO POWER MAINS L2 L1 N L N LT N L N L QF 1 2 3 4 5 6 7 FAN 1 QF 100 240 V 50 60 Hz 100 240 V 50 60 Hz LIGHT the connector is only used in models with an LED module Remove the de...

Page 11: ...nce the button is pressed the indicator displays the turn on delay timer setting which can be edited with the buttons and Once the button is pressed again the Setup menu is displayed again and the edi...

Page 12: ...set and is the default setting for fans with a maximum air flow of 110 CFM For the fans with a maximum air flow 150 CFM Example 2 with these settings the fan will be constantly turned off Once the sw...

Page 13: ...the reverse order TROUBLESHOOTING TROUBLE POSSIBLE REASONS TROUBLESHOOTING The fan does not get started No power supply Check the electric connections and the operation status of the circuit breaker M...

Page 14: ...e suitable hoist machinery for handling and storage operations to prevent possible damage to the unit Follow the handling requirements applicable for the particular type of cargo The unit can be carri...

Page 15: ...l Contact the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s m...

Page 16: ...www blaubergventilatoren de Ceileo Compact DC 110 Light H IR 16...

Page 17: ...www blaubergventilatoren de Ceileo Compact DC 110 Light H IR 17...

Page 18: ...www blaubergventilatoren de Ceileo Compact DC 110 Light H IR 18...

Page 19: ...STALLATION CERTIFICATE The Ceileo Compact DC _____________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Insta...

Page 20: ...www blaubergventilatoren de B183EN 01...

Reviews: