e-mail: info@blauberg.us

Freshbox 100

The unit is rated for connection to single-phase AC mains 120 V / 60 Hz.
Connect the unit to power mains using the pre-wired power cord with the Euro Plug 

XP

Connect the unit to power mains through the external automatic circuit breaker 

QF

 with a magnetic trip. The position of the 

QF

 external 

automatic circuit breaker must ensure free access for quick power-off of the unit. The circuit breaker trip current must correspond to the 
unit current consumption, refer to the Technical data section. When selecting an automatic circuit breaker it is necessary to consider 
maximum permissible wire heating which depends on the wire type, its insulation, length and installation method (i.e. overhead, in cable 
ducts or inside the walls).

Connection of additional external controls

Additionally connected external controls are not included in the delivery set and must be ordered separately. Connection of additional 
external control contacts are shown in the wiring diagram (dashed).
Additionally connected external controls are not included in the scope of delivery. 
Connection of additional external control contacts is implemented in the control unit. For accessing the control unit open the unit door, 
release the screws fixing the shielding and remove it.

Connection of the automatic fire fighting system contact (PK).

Upon connecting the automatic fire fighting system contact remove the jumper between the terminals 5 and 6.
Remove the jumper between the terminals 5 and 6.
In this case the connection is made using a normally closed dry contact that breaks the control circuit and cuts off power supply to the 
unit on the signal from the fire alarm panel.

Connection of the external control unit contact (H). 

The unit design enables connecting a normally opened contact (NO-contact) of external controls, such as an external CO

2

 sensor, a 

humidity sensor, a switch etc. The contact is connected to the terminals 7 and 8.
When the contact closes the unit switches to maximum speed. 

L

N PE

QF

1 2 3

4 5 6 7 8 9 10

L N

PE LA PK PK

YN YL

H H

no

nc

ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID 

THE WARRANTY.

DISCONNECT THE UNIT FROM POWER MAINS PRIOR TO ANY OPERATIONS.

THE UNIT MUST BE CONNECTED TO POWER MAINS BY A QUALIFIED ELECTRICIAN.

THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE SHOWN ON THE RATING 

PLATE.

Connection to power mains

Summary of Contents for Freshbox 100

Page 1: ...05 e mail info blauberg us INSTALLATION GUIDE Toolsrequired Pencil ScotchTape Saw Mountingfoam Drill Ø6mm Screwdriver Dowel4 pcs Screws4 pcs AIR HANDLING UNIT WITH HEAT RECOVERY FRESHBOX 100 400 mm 15 3 4 200 mm 7 7 8 257 mm 10 1 8 590 mm 23 1 4 690 mm 27 3 16 Ø 100 mm Ø 3 15 16 3 holes ...

Page 2: ...een the wall and the air ducts with a mounting foam 4 holes Ø 8 5 16 and 90 mm 3 9 16 deep in the wall made using a mounting template 416 5 mm 16 3 8 647 mm 25 1 2 205 mm 8 1 16 162 mm 6 3 8 468 5 mm 18 7 16 102 5 mm 4 1 16 76 mm 3 400 mm 15 3 4 73 5 mm 2 7 8 547 mm 21 9 16 91 mm 3 9 16 230 mm 9 1 16 170 mm 6 11 16 188 5 mm 7 7 16 158 5 mm 6 1 4 77 mm 3 ADDITIONAL HOLE DRILL UPON CUSTOMER S REQUES...

Page 3: ...the unit mounting place 2 Remove the mounting template and drill two through holes Ø 105 mm Ø 4 1 8 for round air ducts When mounting the unit with an additional extract spigot prepare a hole in the wall for a connecting bend and for laying of a rectangular air duct A connecting bend rectangular and round air ducts are available separately Drill holes Ø 8 mm Ø 5 16 90 mm 3 9 16 deep to mount the u...

Page 4: ...l aligning the mounting template hole with a round end of the connecting bend Connect a rectangular duct to the connecting bend 4 Fill the spaces between the air ducts and the wall with a mounting foam through the specially designed holes in the mounting template Wait till a mounting foam hardens then take off the mounting template and remove the foam excess Cut off the protruding air duct parts t...

Page 5: ...heat exchanger Remove the magnetic plug from the exhaust grille if an additional extract spigot is not installed 7 Fix the unit on the wall using the supplied screws and expansion anchors Install the heat exchanger back and close the unit door Cut a part of the drain pipe protruding outside to a length not more than 10 mm 3 8 Fix the outer hood on the outer wall of the building see the ventilation...

Page 6: ...e not included in the scope of delivery Connection of additional external control contacts is implemented in the control unit For accessing the control unit open the unit door release the screws fixing the shielding and remove it Connection of the automatic fire fighting system contact PK Upon connecting the automatic fire fighting system contact remove the jumper between the terminals 5 and 6 Rem...

Reviews: