www.blaubergventilatoren.de
Helix/s-Vent
14
WIRING DIAGRAMS
QF: automatic circuit breaker
(not included in the delivery set)
X1: terminal block
1
2
3
4
X1
L
N
QF
L
~230 V
50 (60) Hz
N
PE
1.
1
2
3
4
5
6
X1
L
N
TW1
TW2
L
~230 V
50 (60) Hz
N
PE
QF
TW1
TW2
2.
QF: automatic circuit breaker
KM1: magnetic starter
S1, S2: control buttons
(QF, KM1, S1, S2 are not included in the delivery set)
X1: terminal block
X1
L
N
1
2
3
4
5
6
TW1
TW2
KM1
L
~230 V
50 (60) Hz
N
PE
S1
S2
3.
X1
U1
V1
W1
U2
V2
W2
PE
L1
L2
L3
L1
L2
L3
QF
PE
L3
L2
L1
~400 V
50 (60) Hz
1
2
3
4
5
6
7
QF: automatic circuit breaker (not included in the delivery set)
X1: terminal block
4.
Helix
Helix
with thermal switch
Helix
with magnetic starter
and a thermal switch
S-Vent
Wiring example for the Helix fan with external leads of the motor overheating protection and a magnetic starter is shown in Fig. 3.
The terminals TW1, TW2 are the leads of the normally closed contact of the motor overheating protection.
This contact must be serial connected to the power circuit of the magnetic starter coil that starts the motor.
In case of the motor overheating the contact is opened and breaks power supply to the starter coil. This way the motor is stopped.