background image

www.blaubergventilatoren.de

3

KOMFORT EC L S6

BLAUBERG Ventilatoren GmbH

 is happy to offer your attention the air 

handling unit with heat recovery KOMFORT EC L S6.

INTRODUCTION

The present operation manual contains a technical description, technical 

data sheets, operation and mounting guidelines, safety precautions and 

warnings for safe and correct operation of the unit.  

Read carefully and understand the operation manual, especially the safety 

requirements, before the unit mounting and start up.

Keep the operation manual available as long as you use the unit.

GENERAL

The air handling unit with heat recovery KOMFORT EC L S6 is designed for 

efficient and energy saving ventilation of domestic and public premises. 

The unit is not a ready to use product but a component part of central air 

conditioning and ventilation network. 

The unit is designed for wall mounting. 

The unit is rated for indoor application at ambient temperature from +1 °C up 

to +40 °C and relative humidity not exceeding 80 % with the transported air 

temperature from -25 °C up to +60 °C. 

Hazardous parts access and water ingress protection rating:

 

unit motors 

 IP44;

 

assembled unit connected to air ducts 

 IP22.

The unit design is regularly improved, so some models can slightly differ from 

those ones described in this service instruction.

SAFETY RULES

All operations related to the unit electrical connections, servicing and repair 

works are allowed only after the unit disconnection from power mains.  

The unit is rated as a Class I electrical appliance.

All mounting and servicing operations are allowed by duly qualified 

personnel. 

Please follow the safety regulations and working instructions (DIN EN 50 110, 

IEC 364).

Make sure the impeller and the casing are not damaged before connecting 

the unit to power mains. The casing internals must be free of any foreign 

objects which can damage the impeller blades.

The unit maintenance and repair is allowed only after power cut-off and full 

stop of the rotating parts.

Misuse of the unit or any unauthorized modification are not allowed. 

The unit is designed for connection to ac single-phase power mains, see 

«Technical Data». 

The unit is rated for permanent operation.

Take steps to prevent ingress of smoke, carbon monoxide and other 

combustion products into the room through open chimney flues or other 

fire-protection devices. Sufficient air supply must be provided for proper 

combustion and exhaust of gases through the chimney of fuel burning 

equipment to prevent back drafting.  The maximum permitted pressure 

difference per living units is 4 Pa.

The transported air must not contain any dust or other solid impurities, sticky 

substances or fibrous materials.

The unit is not rated for operation in a flammable or explosive medium. 

Fulfil the operation manual requirements to ensure a trouble-free and long 

service life of the unit. 

TRANSPORTATION AND STORAGE RULES

Transportation of the unit is allowed by any vehicle provided the unit is 

transported in the original package and is protected against weather and 

mechanical damages. 

Use hoist machinery for handling and transportation to prevent possible 

mechanical damages of the unit. Fulfil the requirements for transportation of 

the specified cargo type during cargo-handling operations. 

Store the unit in a dry and cool place in the original packing.

The storage environment must not be subjected to any aggressive and/

or chemical evaporations, admixtures, foreign objects that may provoke 

corrosion and damage connection tightness. 

Store the unit in an environment with minimized risk of mechanical damages, 

temperature and humidity fluctuations. 

Do not expose the unit to the temperatures below  +5 °C and above  +40 °C .

Connection of the unit to power mains is allowed after the unit has been kept 

indoor for minimum two hours.

MANUFACTURER’S WARRANTY

The unit complies with the requirements according to the EU norms and 

directives, to the relevant EU-Low Voltage Equipment Directives, EU-

Directives on Electromagnetic Compatibility. 

We hereby declare that the unit complies with the essential protection 

requirements of Electromagnetic Council Directive 2004/108/EC, 89/336/EEC 

and Low Voltage Directive 2006/95/EC, 73/23/EEC and CE-marking Directive 

93/68/EEC on the approximation of the laws of the Member States relating to 

electromagnetic compatibility. This certificate is issued following test carried 

out on samples of the product referred to above. Assessment of compliance of 

the product with the requirements relating to electromagnetic compatibility 

was based on the following standards.

The manufacturer hereby warrants normal operation of the unit over the 

period of two years from the retail sale date provided observance of the 

installation and operation regulations.

In case of failure due to manufacturing fault during the warranty period the 

consumer has the right to exchange it.

The replacement is offered by the Seller. 

If case of no confirmation of the sale date, the warranty period shall be 

calculated from the manufacturing date.

The manufacturer shall not be liable for any damage resulting from any 

misuse of or gross mechanical interference with the unit.

The manufacturer is not responsible for the damages resulted due to the use 

of  third party equipment or to third party equipment.

 

                WARNING

Do not dispose in domestic waste. The unit contains 

in part material that can be recycled and in part 

substances that should not end up as domestic waste. 

Dispose of the unit once it has reached the end of its 

working life according to the regulations valid in your 

country.

 

                  WARNING

The unit is not allowed for use by children and persons with reduced physi-

cal, mental or sensory capacities, without proper practical experience or 

expertise, unless they are controlled or instructed on the product operation 

by the person(s) responsible for their safety. Supervise the children and do 

not let them play with the product. 

!

Summary of Contents for KOMFORT EC L S6 Series

Page 1: ...OPERATION MANUAL KOMFORT EC L S6 AIR HANDLING UNIT WITH HEAT RECOVERY EN ...

Page 2: ...nufacturer s warranty 4 Design 4 Operating logic 4 Delivery set 5 Technical data 6 Mounting 10 Condensate drainage 11 Control panel mounting 11 Connection to power mains 12 Unit control 18 Troubleshooting and fault handling 19 Technical maintenance 21 Acceptance certificate 21 Connection certificate 21 Warranty card CONTENTS ...

Page 3: ...RANSPORTATION AND STORAGE RULES Transportation of the unit is allowed by any vehicle provided the unit is transported in the original package and is protected against weather and mechanical damages Use hoist machinery for handling and transportation to prevent possible mechanical damages of the unit Fulfil the requirements for transportation of the specified cargo type during cargo handling operat...

Page 4: ...m extract air warms up the heat exchanger After that the supply fan is turned on and the unit reverts to the normal operation mode If air temperature in the exhaust air duct downstream of the heat exchanger is below 3 C the supply fan is turned off As air temperature rises above 3 C the unit reverts to the previous operation mode Two built in panel filters with filtering class G4 provide efficient...

Page 5: ... 1 230 Max unit power W 140 210 334 Max unit current A 1 2 1 6 2 2 Max air capacity m3 h 300 400 810 RPM min 1 2300 2600 2860 Sound pressure level at 3 m distance dB A 24 45 30 45 Transported air temperature C 25 up to 60 C Casing material Zinc aluminium Insulation 25 mm mineral wool Extract filter G4 Supply filter G4 F7 Connected air duct diameter mm 150 160 200 250 Weight kg 36 67 83 Heat recove...

Page 6: ... other protecting device at outlet from the air duct with a mesh width not exceeding 12 5 mm MOUNTING Safety precautions The unit must be mounted to a rigid and stable structure The unit must be suspended using anchor bolts Before starting mounting check that the mounting structure has sufficient loading capacity for the unit weight The unit mounting is allowed only after power cut off and full st...

Page 7: ...ide 1 Remove 6 screws 2 Open the back panel and disconnect the ground cable Then remove the back panel 1 2 3 Cover dismantling on current service side 1 Remove six triangular screws 2 Open the cover and disconnect the ground cable Remove the cover Ground cable 1 2 4 Limit switch dismantling on current service side 1 Remove the spade terminals and disconnect the limit switch from the wires 2 Press ...

Page 8: ...he limit switch in the fixing bracket 3 Cover the wires with spade terminals to connect the limit switch 6 Cover mounting on selected service side 1 Connect the ground cable to the service panel on selected service side 2 Install the service cover and fix with six triangular screws 7 Back panel mounting Install the service panel and fix it with six screws ...

Page 9: ...ery set The unit is mounted to the wall with a specially designed fixing bracket Table 5 and the unit is installed on the floor using adjustable levelling feet Note wall mounting is not applicable for KOMFORT EC L600 S6 1 Fix the fixing bracket on the wall While mounting the fixing bracket consider the wall material and the unit weight 2 Install the unit on the fixing bracket 3 Tighten the triangu...

Page 10: ...ses fig 6 While laying the hoses provide the slope downward min 3 Fill the system with water prior to connecting it to power supply The U trap must always be filled with water Before starting the unit fill the drain system with water and keep the U trap always filled with water Provide free drainage for the condensed water otherwise it is accumulated inside the unit which may result in the equipme...

Page 11: ...ECTION TO POWER MAINS WARNING Read the operation manual prior to any electric installations Connection of the unit to power mains is allowed by a qualified electrician only The rated electrical parameter are stated on the rating plate No modifications of internal connections are allowed and will result in void warranty service Connect the unit only to power mains with valid electric standards Foll...

Page 12: ...r of the X3 terminal block are enclosed in brackets fig 8 PK contact for connection of the fire alarm panel While connecting the automatic fire alarm system remove the jumper between the terminals 1 and 2 In case of fire a normally closed dry contact opens the control circuit from the central fire alarm panel H contact for connection of the humidity sensor or CO2 sensor The humidity sensor or CO2 ...

Page 13: ... fig 10 Fig 10 Wall mounted control panel and remote controller Fig 11 Wall mounted control panel display in OFF status Fig 12 Wall mounted control panel display in ON status Unit ON OFF Operation control buttons see details below Fan speed control buttons Remote controller Wall mounted control panel Remote Controller Unit ON OFF Fan speed UP FanspeedDOWN High speed ON Low speed ON Medium speed ON...

Page 14: ...r Medium speed activation from the remote controller High speed activation from the remote controller 3 Timer The timer ensures automatic changeover from a current operation mode into high speed mode and revert to the previous operation mode in set time period To activate deactivate timer Timer activation using the wall mounted control panel pressing one time sets the timer for 20 minutes each sub...

Page 15: ... and hold for 3 sec Adjusted speed selection or Supply fan power step up down Each pressing increases decreases the fan power by 1 press and hold press stepping up stepping down Current supply fan power indication during adjustment Current supply fan power Supply fan setup indication when pressed Extract fan power step up down Each pressing increases decreases the fan power by 1 press and hold pre...

Page 16: ...aintenance section After the filter replacement connect the unit to power supply and press a respective button on the wall mounted control panel or on the remote controller to start the unit or Resetting motor hours press synchronously and 7 Date and time setting Press a respective button on the wall mounted control panel to turn the unit off Changeover to the date and time setup mode press and ho...

Page 17: ...using the wall mounted control panel Week day Time Entry number Fan speed press and hold press Selection of the scheduled operation mode parameters The set point blinks during setup press and hold press or Setting the required set point Parameters for scheduled operation setup Entry number each week day has four entries Week day setting week day Fan speed setting the fan speed for a current entry ...

Page 18: ...he impeller blades Automatic switch tripping Short circuit in power grid Turn the unit off and contact your seller for troubleshooting Low air flow Too low set speed Set higher speed The filters and the fans are soiled the heat exchanger is soiled Clean or replace the filters fans and heat exchanger The air dampers the supply diffusers or the exhaust grilles are closed or soiled Remove and clean t...

Page 19: ...times per year The unit technical maintenance includes regular cleaning and other works 1 Filter maintenance 3 4 times per year Dirty filters increase air resistance and decrease air capacity of the unit Clean the filter with a vacuum cleaner or flush it with water After two consecutive cleanings the filter must be replaced Install dry filters only Contact a local distributor for the filters state...

Page 20: ...results in the unit capacity decrease Clean the fan with a soft cloth or a brush Cleaning with water abrasive detergents sharp object or chemicals is not allowed 4 Condensate drain system maintenance once per year Extract air particles may accumulate in the condensate drain system and cause its clogging Pour a drain pan under the unit with water to check free water flow Clean a U trap and the drai...

Page 21: ...EEC and CE marking Directive 93 68 EEC on the approximation of the laws of the Member States relating to electromagnetic compatibility This certificate is issued following test carried out on samples of the product referred to above Approval mark Manufacturing date____________________ Company Name Date Signature The air handling unit with heat recovery KOMFORT EC L300 S6 KOMFORT EC L1 300 S6 KOMFO...

Page 22: ..._________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ ______________...

Page 23: ..._________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ ______________...

Page 24: ...www blaubergventilatoren de Komfort EC _L_v 1 3 _EN ...

Reviews: