KOMFORT EC S/SB
UNIT MOUNTING
!
Safety precautions:
The unit must be mounted to a rigid and stable structure.
The unit must be suspended using anchor bolts. Make sure that the base structure is capable of sustaining the unit weight.
The unit mounting is allowed only after power cut-off and full stop of the rotating parts.
Restrictions:
• Do not operate the unit beyond the determined temperatures, in aggressive and in explosive environment.
• Do not connect the clothes dryer or other similar equipment to the ventilation system.
• Do not use the unit for air/dust mixture handling.
WARNING
The unit mounting position must provide condensate drainage and access
to the hinged service panel for electric connection, maintenance and fi lter
replacement.
To attain the best performance of the unit and to minimise turbulence-
induced air pressure losses connect the straight air duct section to the spigots
on both sides of the unit while mounting.
Minimum straight air duct length:
•
equal to 1 air duct diameter on intake side
•
equal to 3 air duct diameters on outlet side
If the air ducts are too short or not connected, protect the unit parts from
ingress of foreign objects. To prevent uncontrollable access to the fans the
spigots may be covered with a protecting grille or other protecting device
with mesh width not more than 12.5 mm.
The unit must be mounted on a plane wall. Mounting of the unit to
an uneven surface can lead to the unit casing distortion and operation
disturbance.
When ordering an optional humidity sensor install it prior to unit
mounting.
Fig. 5.Overall dimensions of the S15 control panel
Fig. 6. Overall dimensions of the mounting box for wall fl ush mounting
Fig. 7. Overall dimensions of the mounting box for wall surface mounting
R1,5
OUT
OUT
OUT
IN
+
Rx
Tx
-
86
58
39
21
11,2
86
4
62,3
52
78
37
58
78
88
32
58
88
Table 5. Technical parameters of the S15 control panel
Parameter
Value
Ambient temperature [°C]
from 0 to +40
Humidity range [%]
from 5 to 80
(no condensation)
Cable cross section [mm
2
]
from 0,25 to 0,5
Cable length [m]
to 10
Ingress protection rating
IP30
The S15 control panel can be wall-mounted using the mounting box for
fl ush mounting, Fig. 6 (included in the delivery set).
The S15 control panel can be mounted on the wall using the mounting
box for surface mounting, Fig. 7 (included in the delivery set).