background image

Heat and energy recovery air Handling unit

USER‘S MANUAL

EN

KOMFORT ERV D 100

KOMFORT ERV D 200

KOMFORT ERV D 300

KOMFORT ERV D 450

Summary of Contents for KOMFORT ERV D 100

Page 1: ...Heat and energy recovery air handling unit USER S MANUAL EN KOMFORT ERV D 100 KOMFORT ERV D 200 KOMFORT ERV D 300 KOMFORT ERV D 450...

Page 2: ...ractical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of th...

Page 3: ...ospheric agents rain sun etc Transported air must not contain any dust or other solid impurities sticky substances or fibrous materials Do not use the unit in a hazardous or explosive environment cont...

Page 4: ...f the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a safety hazard Ensure that the unit is switched off from the su...

Page 5: ...ltered stream of intake air The unit is not intended for organizing ventilation in swimming pools saunas greenhouses summer gardens and other spaces with high humidity Due to the ability to save heati...

Page 6: ...ample of new buildings The unit is rated as a Class I electrical appliance Hazardous parts access and water ingress protection rating IP22 for the unit connected to the air ducts IP44 for the unit mot...

Page 7: ...D B L L A B A B Model Dimensions mm D A A1 B B1 H H1 L KOMFORT ERV D 100 100 734 600 481 571 204 223 300 KOMFORT ERV D 200 100 987 854 704 793 222 241 480 KOMFORT ERV D 300 150 987 854 704 793 227 246...

Page 8: ...hen the air flows through the heat exchanger and is directed to the room with the supply fan Supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to...

Page 9: ...s 3 After temperature increase the unit returns to the previous operation mode In the Defrosting mode the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow To set...

Page 10: ...alist Before mounting make sure the casing does not contain any foreign objects e g foil paper The minimum distance between the unit and the ceiling should be at least 20 mm To attain the best perform...

Page 11: ...t label It is recommended to select the nominal current of the circuit breaker from the standard series following the maximum current of the connected unit The circuit breaker is not included in the d...

Page 12: ...nce a year Some dust may accumulate on the heat exchanger block even in case of regular maintenance of the filters To maintain high heat exchange efficiency periodical dry cleaning is recommended Use...

Page 13: ...and mechanical damage The unit must be transported only in the working position Avoid sharp blows scratches or rough handling during loading and unloading Prior to the initial power up after transpor...

Page 14: ...the Seller for warranty service The manufacturer s warranty does not apply to the following cases User s failure to submit the unit with the entire delivery package as stated in the user s manual inc...

Page 15: ...RTIFICATE The _____________________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation...

Page 16: ...www blaubergventilatoren de B147 1EN 02...

Reviews: