KoMFort roto ec S2(e)200

14

POSSIBLE REASONS AND TROUBLESHOOTING

Problem

Possible reasons

Troubleshooting

The fan(s) do(es) no start.

No power supply.

Make sure the power supply line is connected correctly, 
otherwise troubleshoot a connection error.

The motor is jammed, the impeller blades are soiled.

Turn the unit off. Troubleshoot the motor jam and the 
impeller clogging. Clean the blades. Restart the unit.

Alarm in the system. System alarms are listed below.

Identify the system failure by entering the active alarms 
menu and eliminate the alarm. If the system alarm cannot be 
eliminated by the user contact the Seller.

Automatic circuit breaker 
trips following the unit 
turning on.

High current consumption due to short circuit in power 
line.

Turn the unit off. Contact the Seller.

Low air flow.

Low set fan speed.

Set higher speed.

The filters and the fans are clogged, the heat exchanger 
is clogged.

Clean or replace the filters, clean the fans, and the heat 
exchanger.

Ventilation system elements (air ducts, diffusers, louver 
shutters, grilles) are clogged, damaged or closed.

Clean or replace the ventilation system elements, such as air 
ducts, diffusers, louvre shutters, grilles.

Cold supply air.

The extract filter is soiled.

Clean or replace the extract filter.

The unit operates in Cooling mode.

Check the unit operation settings.

Noise, vibration.

The impeller(s) is soiled.

Clean the impeller(s).

The fan or casing screw connection is loose.

Tighten the screw connection of the fans or the casing 
against stop.

No anti-vibration connectors on air duct pipe flanges.

Install anti-vibration connectors.

SYSTEM ALARMS

Fire alarm.

Emergency system shutdown on command from the fire 
alarm board. This alarm interrupts the fan operation.

In case of such alarm follow the emergency instructions and 
leave the room and the building.

Temperature sensor failure.

Interruption or shortening in the temperature sensor 
circuit. This alarm interrupts the fan operation.

Contact the Seller.

Control panel failure.

Control panel communication error.

Check the connection of the control panel to the controller. 
Contact the Seller.

Low supply air 
temperature.

The supply air temperature is below +14 °C (factory 
setting).

Clean or replace the extract filter. Check the unit operation 
settings.

Filter replacement 
required.

Filter replacement interval expiration.

Clean or replace the filters.

STORAGE AND TRANSPORTATION REGULATIONS

•  Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range 

+5 ˚С...+40 ˚С  and relative humidity up to 70 %.

•  Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing 

deformation.

•  Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
•  Follow the handling requirements applicable for the particular type of cargo.
•  The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and 

mechanical damage. The unit must be transported only in the working position.

•  Avoid sharp blows, scratches, or rough handling during loading and unloading.
•  Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at 

least 3-4 hours.

Summary of Contents for KOMFORT Roto EC S2 200

Page 1: ...Heat recovery air handling unit USER S MANUAL EN KOMFORT Roto EC S2 200 KOMFORT Roto EC S2E200...

Page 2: ...on of its products at any time in order to incorporate the latest technological developments No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by...

Page 3: ...r Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any technical maintenance Do not store any exp...

Page 4: ...ain any flammable or explosive mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substa...

Page 5: ...ineral wool Filter extract G4 supply G4 F7 Connected air duct diameter mm 125 Weight kg 47 48 Heat recovery efficiency from 75 up to 92 Heat exchanger type rotary Heat exchanger material aluminium SEC...

Page 6: ...hood The kitchen hood must be equipped with an air damper to shut off the exhaust duct when the kitchen hood is not in use Unit design and operation principle service side view Intake filter Extract...

Page 7: ...able access to the fan the spigots may be covered with a protecting grille or other protecting device with mesh width not more than 12 5 mm While installing the unit ensure convenient access for subse...

Page 8: ...and install the humidity sensor into the mounting bracket on the exhaust duct wall Then connect the humidity sensor connector to the respective contact socket on the control unit 1 2 3 Contact socket...

Page 9: ...the unit for floor mounting Then undo the four self tapping screws and remove the plug in the bottom panel Lead the kitchen hood cable into the unit and connect it according to the external connection...

Page 10: ...on selection must be based on the maximum load current maximum conductor temperature depending on the wire type insulation length and installation method The external power input must be equipped with...

Page 11: ...connector for the kitchen hood X4 is located on the side wall of the unit It is necessary to lead the cable into the unit and connect it to the connector according to the wiring diagram For right han...

Page 12: ...and the control panel Phone cable up to 50 m AWG24 shielded cable up to 200 m External connections diagram of the KOMFORT Roto EC S2 E 200 S21 XS11 X1 1 C 2 NC 3 4 N 5 L Grey Black Yellow green Blue B...

Page 13: ...ncy regular cleaning is required To clean the heat exchanger remove it from the unit and clean the heat exchanger by using compressed air or a vacuum cleaner After cleaning re install the heat exchang...

Page 14: ...air duct pipe flanges Install anti vibration connectors SYSTEM ALARMS Fire alarm Emergency system shutdown on command from the fire alarm board This alarm interrupts the fan operation In case of such...

Page 15: ...air the user must provide the unit the user s manual with the purchase date stamp and the payment paperwork certifying the purchase The unit model must comply with the one stated in the user s manual...

Page 16: ...www blaubergventilatoren de KOMFORT Roto EC S2 E 200 16...

Page 17: ...www blaubergventilatoren de KOMFORT Roto EC S2 E 200 17...

Page 18: ...www blaubergventilatoren de KOMFORT Roto EC S2 E 200 18...

Page 19: ...__200 S___ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Name Installation Date...

Page 20: ...www blaubergventilatoren de B140 1EN 04...

Reviews: